1606-XLE-Series Power Supply Instruction Manual
Technical Data
1)
Technische Daten
1)
1606-
XLE80E
1606-XLE
120E
1606-XLE
120EC
2)
1606-
XLE120EN
1606-
XLE120EE
1606-
XLE240E
1606-
XLE240EP
1606-
XLE240EN
1606-
XLE240EE
1606-
XLE240F
Output Voltage Ausgangsspannung
nom.
24 - 28V 24 - 28V 24 - 28V 24 - 28V 24 - 28V 24 - 28V 24 – 28V 24 - 28V 48 - 52V
Factory Setting Werkseinstellung
typ.
24.1V 24.1V 24.1V 24.1V 24.1V 24.1V 24.1V 24.1V 48.0V
Output Current Ausgangsstrom
nom.
3.3 - 2.7A 5 - 4.3A 5 - 4.3A 5 - 4.3A 10 - 8.6A 10 - 8.6A 10 - 8.6A 10 - 8.6A 5 - 4.6A
Power Boost
N/A
14)
6 - 5.1A
3) 4)
6 - 5.1A
3) 4)
6 - 5.1A
3)
12 - 10.3A
3)
12 - 10.3
5)
12 - 10.3A
3)
12 - 10.3A
3)
6 - 5.5A
3)
Output Power Ausgangsleistung
nom.
80W 120W 120W 120W 240W 240W 240W 240W 240W
Power Boost
N/A
14)
144W
3) 4)
144W
3) 4)
144W
3)
288W
3)
288W
5)
288W
3)
288W
3)
288W
3)
Output Ripple
19)
Ausgangswelligkeit
19)
max.
50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 50mVpp 100mVpp
AC Input Voltage AC Eingangsspannung
nom.
100-240Vac
±10%
100-120Vac/
200-240Vac
±10%
100-120Vac
±10%
200-240Vac
±10%
100-120Vac/
200-240Vac
±10%
100-120Vac/
200-240Vac
±10%
100-120Vac
±10%
200-240Vac
±10%
100-120Vac/
200-240Vac
±10%
Wide-Range Auto-Select -- -- Auto-Select Auto-Select -- -- Auto-Select
AC Input Current
16)
AC Eingangsstrom
16)
typ.
1.4 / 0.75 2.6 / 1.4A 2.6A / -- -- / 1.4A 5.0 / 2.7A 5.0 / 2.4A 5.0A / -- -- / 2.7A 5.0 / 2.7A
DC Input Voltage
7)
DC Eingangsspannung
7)
88 - 375Vdc N/A
14)
N/A
14)
210 - 375Vdc N/A
14)
N/A
14)
N/A
14)
210 - 375Vdc N/A
14)
Power Factor
17)
Leistungsfaktor
17)
typ.
0.61 / 0.56 0.56 / 0.47 0.59 / -- -- / 0.5 0.59 / 0.51 0.59 / 0.57 0.57 / -- -- / 0.52 0.59 / 0.51
Harmonic Correction
18)
Oberwellenkorrektur
18)
No / Nein No / Nein No / Nein No / Nein No / Nein Yes / Ja No / Nein No / Nein No / Nein
EN 61000-3-2 EN 61000-3-2
Yes / Ja No / Nein N/A
14)
Yes / Ja No / Nein Yes / Ja N/A
14)
No / Nein No / Nein
Input Inrush Current
11)
Einschaltspitzenstrom
11)
120Vac, typ.
23A; 0.5A
2
s 3A; 1A
2
s 45A; 3A
2
s -- 3A; 1A
2
s 3A; 1A
2
s 85A; 8,5A
2
s -- 3A; 1A
2
s
230Vac, typ.
45A; 1.7A
2
s 3A; 1A
2
s -- 30A; 1A
2
s 3A; 1A
2
s 3A; 1A
2
s -- 48A; 3A
2
s 3A; 1A
2
s
Efficiency
17)
Wirkungsgrad
17)
typ.
88,0/89,8% 89,4/90,2% 90,0% / -- -- / 90,2%
91,0/91,6%
91,0/91,6% 90,8% / -- -- / 91,6% 91,4/92,0%
Power Losses
17)
Verlustleistung
17)
typ.
11,1/9,1W 14,5/13,2W 13,5W / -- -- / 13,2W
24,1/22,4W
24,1/24,1W 24,0W / -- -- / 22,7W 22,6/20,9W
Hold-up Time
17)
Pufferzeit
17)
typ.
29 / 120ms 80 / 78ms 80ms / -- -- / 78ms 46 / 47ms 46 / 42ms 46ms / -- -- / 45ms 46 / 47ms
Operational Temperature Betriebstemperatur
-25 - +70°C -25 - +70°C -10 - +70°C -10 - +70°C -25 - +70°C -25 - +70°C -10 - +70°C -10 - +70°C -25 - +70°C
Output Derating Leistungsrücknahme
+60 - +70°C
1.8W/°C 3W/°C 3W/°C 3W/°C 6W/°C 6W/°C 6W/°C 6W/°C 6W/°C
Storage Temp. Range Lagertemperaturbereich
-40 - +85°C -40 - +85°C -40 - +85°C -40 - +85°C -40 - +85°C -40 - +85°C -40 - +85°C -40 - +85°C -40 - +85°C
Humidity
20)
Feuchte
20)
IEC60068-2-30
5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H.
Vibration Schwingen
IEC 60068-2-6
2g 2g 2g 2g 2g 2g 2g 2g 2g
Shock Schocken
IEC60068-2-27
30g 6ms 30g 6ms 30g 6ms 30g 6ms 30g 6ms 30g 6ms 30g 6ms 30g 6ms 30g 6ms
Degree of Pollution Verschmutzungsgrad
EN 50078
2 2 2 2 2 2 2 2 2
Degree of Protection Schutzart
EN 60529
IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20 IP20
Class of Protection Schutzklasse
IEC 61140
I
6)
I
6)
I
6)
I
6)
I
6)
I
6)
I
6)
I
6)
I
6)
Over-temp. Protection
15)
Übertemperaturschutz
15)
No / Nein Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja
Over-voltage Protection
15)
Überspannungsschutz
15)
typ.
34Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 56Vdc
Return Voltages
8)
Rückspeisefestigkeit
8)
max.
35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 35Vdc 63Vdc
Parallel Use
12)
Parallelschaltbar
13)
No / Nein No / Nein No / Nein No / Nein No / Nein No / Nein No / Nein No / Nein No / Nein
Serial Use
13)
Serienschaltbar
14)
Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja
Dimensions
9)
(wxhxd) Abmessungen
9)
(BxHxT)
nom.
32x124x102 32x124x117 32x124x117 32x124x117 60x124x117 60x124x117 60x124x117 60x124x117 60x124x117
Weight Gewicht
max.
430g / 0.95lb 500g / 1.1lb 500g / 1.1lb 500g / 1.1lb 700g / 1.54lb 800g / 1.76lb 700g / 1.54lb 700g / 1.54lb 700g / 1.54lb
Approvals Zulassungen
10)
10)
10)
10)
10)
10)
10)
10)
10)
Limited Warranty (Year) Gewährleistung (Jahre)
1 1 1 1 1 1 1 1 1
1) All parameters are specified at 230Vac input voltage, nominal output current, 25°C ambient and after a 5
minutes run-in time unless otherwise noted.
2) The model 1606-XLE120EC are identical to the model 1606-XLE120E with the exception that the PC board
is conformal coated.
3) The PowerBoost is continuously allowed up to an ambient of 45°C. Above that temperature, do not use the
PowerBoost longer than a duty cycle of 10% and not longer than 1 minute every 10 minutes.
4) The unit can respond with a thermal shut-down when continuously loaded with more than 120W and
operated with a mains voltage of 100V or below.
5) Do not use the PowerBoost longer than a duty cycle of 10% and not max. 1 minute every 10 minutes.
6) PE connection required (Ground).
7) Use a battery or similar DC source. Connect +pole to L and -pole to N.
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the power supply.
The figure represents the maximum allowed feed-back voltage
9) Dimensions in mm. Depth without DIN-rail.
10) See datasheet or markings on the unit.
11) Peak value and inrush energy at an ambient temperature of 40°C and cold start.
12) The power supplies shall not be used in parallel in order to increase the output power. However, units can
be paralleled for building 1+1 redundancy systems or to deliver short-term peak currents to the load when
the average current is smaller than the current of one power supply.
13) Use only power supplies of the same type. The total output voltage should not exceed 150Vdc.
14) Not applicable
15) Output shut-down with automatic restart
16) At full load and the lower end of the input voltage of 120/230Vac
17) At full load and nominal input voltage of 120/230Vac
18) Harmonic correction describes whether the input current waveform is filtered in order to reduce the amount
of harmonic current. A not filtered unit does not necessarily mean that the EN 61000-3-2 is not fulfilled.
19) 50 Ohm measurement, bandwidth 20MHz
20) Do not energize while condensation is present.
1) Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, 25°C Umgebung und nach
einer Aufwärmzeit von 5 Minuten, wenn nichts anderes angegeben ist.
2) Das Model 1606-XLE120EC ist identisch zum Model 1606-XLE120E mit der Ausnahme, dass die
Leiterplatten mit Schutzlack überzeugen sind.
3) Der PowerBoost kann <45°C dauerhaft entnommen werden. Über 45°C ist eine max. Einschaltdauer
von 10% erlaubt, die nicht öfters als 1 Minute alle 10 Minuten wiederholt werden darf.
4) Bei einer Dauerbelastung >120W und einer Eingangsspannung <120Vac kann das Gerät thermisch
abschalten.
5) Der PowerBoost darf mit einer max. Einschaltdauer von 10% und nicht öfters als 1 Minute alle 10
Minuten entnommen werden.
6) PE Verbindung erforderlich.
7) Geeignet sind Batterien oder ähnliche Quellen. Den + Pol an L und - Pol an N anschließen.
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils rückspeisen.
Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Abmessungen in mm. Tiefe ohne DIN-Schiene
10) Siehe Datenblatt oder Prüfzeichen auf dem Gerät.
11) Spitzenwert und Einschaltenergie bei einer Umgebungstemperatur von 40°C und Kaltstart
12) Ausgänge der Stromversorgung sollen nicht parallel geschaltet werden. Eins Parallelschaltung ist nur
für 1+1 Redundanzanwendungen oder zur Abdeckung kurzer Spitzenlasten erlaubt, wenn der mittlere
Ausgangsstrom kleiner ist als der Nennstrom eines Gerätes
13) Nur gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
14) Nicht anwendbar
15) Ausgang schaltet ab und macht regelmäßig automatische Startversuche
16) Bei Nennlast und dem unteren Ende der Eingangsspannung von 120/230Vac
17) Bei Nennlast und Nenneingangsspannung von 120/230Vac
18) Die Angabe Oberwellenkorrektur gibt an ob die Kurvenform des Eingangsstromes gefiltert ist. Ein
nicht gefiltertes Gerät kann aber trotzdem die Anforderungen der EN 61000-3-2 erfüllen.
19) 50 Ohm Messung, Bandbreite 20MHz
20) Nicht betreiben, solange das Gerät Kondensation aufweist.
EMC Electromagnetic Compatibility
These devices are suitable for applications in industrial environment as well as in residential,
commercial and light industry environment. Please note that for some units restrictions may apply
since the EN 61000-3-2 requirements are not fulfilled on all units. See also datasheet for details.
These devices comply with FCC Part 15 rules. Operation is subjected to following two conditions: (1)
this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
CE mark is in conformance with EMC directive 89/336/EC, 93/68/EC and 2004/108/EC and the low-
voltage directive (LVD) 73/23/EC, 93/68/EC, 2006/95/EC.
EMC Immunity: EN 61000-6-1, EN 61000-6-2
EMC Emission: For all units: EN 61000-3-3, EN 61000-6-4, FCC Part 15 Class B
EN 61000-6-3, EN 61000-3-2: For units which are marked with “Yes” in the row EN
61000-3-2 of the technical data table.
EMV Elektromagnetische Verträglichkeit
Diese Geräte erfüllen die Anforderungen für Anwendungen sowohl in industrieller Umgebung
als auch für den Wohn-, Geschäfts- und Gewerbebereich.
Einige dieser Gerätetypen erfüllen die Anforderungen der EN 61000-3-2 nicht und es kann
daher zu Einschränkungen bei Anwendungen kommen. Siehe auch Details im Datenblatt.
Die Geräte erfüllen auch die Anforderungen der FCC Teil 15.
Das CE Zeichen ist angebracht und erklärt die Erfüllung der EMV Richtlinien 89/336/EG,
93/68/EG, 2004/108/EG und der Niederspannungsrichtlinie 73/23/EG, 93/68/EG, 2006/95/EG.
EMV Störfestigkeit: EN 61000-6-1, EN 61000-6-2
EMV Störaussendung: Für alle Geräte: EN 61000-3-3, EN 61000-6-4, FCC Part 15 Klasse B
EN 61000-3-2, EN 61000-6-3: Für Geräte die in der Spalte EN
61000-3-2 der Tabelle mit den technischen Daten den Eintrag „Ja“
haben.