nextys NCU120 series Manuale utente

Tipo
Manuale utente
1
Fig.1
Connection
Fig.2
Dimensions Fig.3
Distances Fig.4
Hook up
(1) AC/DC input
(2) DC output (load)
(3) Battery connection
(4) Diagnostic Output
dry contact:
NC load supplied by Power S.
NO load supplied by Battery
(5) Green LED: output by P.S.
(6) Red LED: output by Battery
(7) Output voltage adjustment
Dimension
W
D
H
mm (inc)
54 (2.16)
110 (4.33)
115 (4.52)
Distance
A
B
mm (inc)
20 (0.8)
20 (0.8)
Unhook
Fig.5 – Recommended connecting cable Fig.6 – Input protection
0.5-0.6 Nm
4.42-5.30 lbf in
Solid: 2.5mm² / 12AWG
Stranded:1.5mm² / 12AWG
L: 6.0-7.5mm / 0.24-0.30 in
Fuse 4AT or MCB 4A C curve (see point 4 next page).
For USA and Canada, use the fuse type closest to the European equivalent type
Fig.7 – Input connection
Instruction Manual
Models NCU120 Series Single phase / DC input power supply – Battery Charger
File No.: I.S.NCU120.V1.0 Rev.: 1.0
Nextys SA. Via Luserte Sud 8, 6572 Quartino – Switzerland
Phone: +41-(0)91 8401446 / 8401448; Fax: +41-(0)91 8401447
READ THIS CAREFULLY BEFORE INSTALLATION! LEGGERE ATTENTAMENTE PRIMA
DELL’INSTALLAZIONE! A LIRE ATTENTIVEMENT AVANT L’INSTALLATION!
Before operating, read this manual thoroughly and retain it for
future reference.
Non-respect of these instructions may reduce performances
and safety of the devices and cause danger for people and
property.
The products must be installed, operated, serviced and
maintained by qualified personnel in compliance with
applicable standards and regulations.
Don’t open the device, it does not contain replaceable
components, the tripping of the internal fuse (if included) is
caused by an internal failure.
Don’t repair or modify the device, if malfunction or failure
should occur during operation, send unit to the factory for
inspection.
No responsibility is assumed by Nextys SA for any
consequences deriving from the use of this material.
Prima dell’installazione, leggere attentamente queste istruzioni
e conservarle per future consultazioni.
L’inosservanza delle presenti istruzioni può compromettere le
caratteristiche e la sicurezza dell’apparecchio e causare
pericolo per le persone e le cose.
Il prodotto deve essere installato, utilizzato e riparato da
personale qualificato e nel rispetto delle normative vigenti.
Non aprire il prodotto, esso non contiene componenti
sostituibili, il guasto del fusibile interno (se previsto) è causato
da un guasto interno. Non tentare di riparare o modificare il
prodotto, se durante il funzionamento si verificano guasti o
anomalie, inviarlo al produttore per il controllo.
Nextys SA non si assume nessuna responsabilità per
qualunque conseguenza derivante dall’uso di questo materiale.
Lisez ces instructions avant l'installation, conservez ce manuel
pour référence future.
Défaut de se conformer à ces instructions peut affecter les
caractéristiques et la sécurité du dispositif de danger et de
causer aux personnes ou aux biens.
Le produit doit être installés, exploité et entretenus par
personnel qualifié et en conformité avec les règlements.
N'ouvrez pas le produit, il ne contient aucune pièce réparable,
le déclenchement du fusible interne (le cas échéant) est
causée par un défaut interne. Ne pas tâtonné pour réparer ou
modifier le produit, si des défaillances se produisent pendant le
fonctionnement ou les dysfonctionnements, le retourner au
fabricant pour inspection.
Nextys SA n'assume aucune responsabilité des conséquences
éventuelles découlant de l'utilisation de cette documentation.
CAUTION ATTENZIONE AVVERTISSEMENT
RISK OF BURNS, EXPLOSION, FIRE, ELECTRICAL
SHOCK, PERSONAL INJURY.
Never carry out work on live parts! Danger of fatal injury! The
product’s enclosure may be hot, allow time for cooling product
before touching it. Do not allow liquids or foreign objects to
enter into the products.
To avoid sparks, do not connect or disconnect the device
before having previously turned-off input power and wait for
capacitors discharge.
RISCHIO USTIONI, ESPLOSIONE, INCENDIO, SCOSSA,
LESIONI GRAVI.
Non effettuare mai operazioni sulle parti in tensione! Pericolo di
lesioni letali! Il contenitore può scottare, lasciar quindi
raffreddare il dispositivo prima di toccarlo. Non far entrare
liquidi o oggetti estranei nel dispositivo.
Per evitare scintille, non collegare o scollegare
l'apparecchiatura prima di avere tolto tensione di ingresso e
prima che sia avvenuta la scarica dei condensatori.
RISQUE DE BRULURES, EXPLOSION, INCENDIE,
ELECTROCUTION, DOMMAGE AUX PERSONNES.
Ne jamais effectuer des opérations sur les parties sous
tension! Danger de mort! Le récipient peut graver, le laisser
refroidir avant de toucher l'appareil.
Ne vous laissez pas liquide ou corps étranger dans l'appareil.
Pour éviter des étincelles, ne pas connecter ou déconnecter
l'équipement jusqu'à ce que vous avez supprimé la tension
d'entrée et avant qu'elle n'ait lieu de décharge des
condensateurs.
INTENDED USE USO PREVISTO UTILISATION
These are Class I isolation devices suitable for SELV and
PELV circuitry and are designed to be mounted on DIN rail and
installed inside a protective enclosure. They are intended for
general use such as in industrial control, communication, and
instrumentation equipment.
Don’t use these devices in applications where malfunction may
cause injury or death.
Sono dispositivi in classe di isolamento I e adatti per
applicazioni SELV e PELV, sono dotati di aggancio per il
montaggio su guida all’interno di quadri elettrici o contenitori di
protezione per l’utilizzo con controllori industriali, unità di
comunicazione o apparecchi di misura.
Non utilizzare in applicazioni in cui un eventuale guasto può
comportare rischio di lesioni o di morte.
Les produits sont de classe I isolement, propice pour les
circuits TBTS et TBTP et sont équipé d'un crochet pour
montage sur rail dans les armoires ou conteneurs sécurisés,
pour utilisation avec les contrôleurs industriels, des modules de
communication ou les unités de mesure.
Ne pas utiliser ces dispositifs dans l'application où un
dysfonctionnement pourrait entraîner des blessures ou morts.
ENVIRONMENTAL CHARACTERISTICS CARATTERISTICHE AMBIENTALI CARACTÉRISTIQUES D'ENVIRONNEMENT
Installation in a Pollution Degree 2 environment, Overvoltage
Category II, according to IEC 664-1
Do not use in wet area or subject to moisture.
Carefully recycle the product and related batteries according to
local regulations.
Usare in ambienti con Grado di Inquinamento 2 e Categoria di
Sovratensione II, secondo IEC 664-1.
Non far funzionare l'apparecchio in un ambiente umido o
soggetto a formazione di condensa.
Riciclare il prodotto e le batterie collegate, nel rispetto delle
normative locali vigenti.
Utilisé dans les environnements avec degré de pollution 2,
catégorie de surtension II selon IEC 664-1.
Ne pas faire fonctionner l'appareil dans un environnement
humide ou soumis à la condensation.
Recycler les produits et les accus, conformément à la
réglementation locale.
INSTRUCTIONS
1) Description: DIN rail mountable primary switched-mode power supply with 90...265Vac - 110…345Vdc input, suitable for Single phase main line and DC line.
Functions:
Power supply: the units can be used as standard power supplies with 12-15V/7A (-12 Version) and 24V/5A (-24 Version) output rating.
Battery charger: charging current regulator limits the charging current to 0.8A, thus avoiding higher charging currents dangerous for the battery life.
DC UPS function: in case of the power supply incapacity of supplying the load (mains failure or unit failure) the load will continue to receive power from the battery without ANY
interruption, until the mains recovers or the battery reaches the “Deep Discharge Voltage” threshold ( 9.5V for -12 Version and 19V for -24 Version).
Deep discharge protection: disconnects the battery from the load when its voltage is lower than 9.5V (-12 Version) or 19V (-24 Version).
The higher the charging current the higher the temperature of the battery, therefore the battery life increases if deep discharge is avoided (the battery life depends also by the numbers
of the charge/discharge cycles, their durations and by other various factors).
Battery reverse polarity protection: in case of reverse connection of the battery the resettable fuse will trip and protect all circuitry.
Auto-resetting short circuit protection: connected in series to the line fed by the battery (the power supply output is actively protected against short circuit and overload)
Status signals: a green LED, a red LED and a dry SPST contact displays the working status of the product, indicating “Load on Power Supply “ or “Load on Battery” .
2) Installation: use DIN-rails according to EN 60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where the device is to
be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).
The device is provided with a thermal protection, a limited air flow can causes the thermal protection tripping.
The SMPS automatically restarts after cooling.
To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce the load.
3) Connections: the device is equipped with pluggable screw terminals. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input power and
waited capacitors discharge.
In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of 60°C (for ambient <45°C) and 75°C (for ambient <
60°C).
Strip the connecting ends of the wires according to the indication on Fig.5 and ensure that all strands of a stranded wire enter the terminal connection.
4) Input protection : the device input is provided with varistors against overvoltage. Input isn’t provided with internal fuses, thus an external short circuit/overcurrent protection must be
provided by the end user (see Fig.6).
For operation on a single-phase system, a protection fuse on the phase must be provided.
5) AC input connection: the device can be connected to single-phase AC lines with Un 120…240 Vac (see Fig.7).
6) DC input connection: connect L terminal to + pole, N terminal to – pole and I terminal to GND. Rated voltage 110...345Vdc.
The device is also suitable for photovoltaic or wind turbine applications.
2
7) Output connection: the device is suitable for SELV and PELV circuitry.
Uout can be adjusted with a potentiometer (see Fig.1)
Check Uout before connecting the power supply to the load. With output voltage set to the max. value, the continuous current must not exceed the nominal power.
8) Parallel connection and redundancy: not recommended.
9) Output protection: the device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT).
OL and SC: are controlled by an hiccup auto-reset protection with the following behaviour:
OL behaviour: Max. OL = In x 1.5 with constant output voltage. If the current is In x 1.5 the unit enters the OL protection and starts an ON/OFF cycle (hiccup).
SC behaviour: the device supplies the indicated short circuit peak current for 50 ms if the output current exceeds In x 1.5 the device enters into a controlled ON/OFF cycles (hiccup mode).
The output voltage drops to a voltage value depending on the impedance of the failed load circuit.
Output OV circuit protection: the output is protected against potential OV due to internal malfunction or coming from the load for Uout Unom x 1.2 – 1.3, depending on the model.
OT protection: turns off the device if the internal temperature exceeds a safe limit. The Battery can continue to supply the Load.
The device restarts automatically after cooling down. To recover to normal operation reduce air temperature surrounding the power supply, increase cooling or reduce load.
When operating at normal load and > 45°C reduce the output power with 4.0W/°C.
10) Feeding DC motors: it is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it can trigger
overcurrent protection.
NOTE: motors can generate high conducted noise on the DC line. Therefore it is not recommended to feed on the same line motors and equipment sensitive to noise.
11) Warranty: the devices are guaranteed free from factory defects for the time specified in the “Sales Conditions”
Failures caused by misuse, external and/or abnormal events (i.e. overvoltage, over temperatures) or non-respect of above parameters and standards, are not covered by warranty.
Opening the housing of the product makes warranty to be no longer valid.
In order to improve the products Nextys SA reserves the right to change product specifications, ratings and data without previous advice.
NOTES:
The total current sunk by the load and by the battery during the max. current required by the charging process (0.8A), must not exceed 7A (-12 Version ), 5A (-24 Version) continuous,
thus the max. continuous load must be 6.2A (-12 Version)/ 4.2A (-24 Version).
The charging time of the battery depends on its capacity in Ah, on its charge level, on ambient temperature, on the efficiency status of the battery, its age, on the charging voltage of the
device (recommended: 14.4V for -12 version, 27.5V for -24 version).
Normally the charging current of lead batteries must not exceed 10% of rated Ah. Higher charging current reduces battery life, too low charging current leads to a longer charging time
and incomplete charge.
Lead batteries in normal charge conditions and efficiency have a good self regulating capacity on charging current, independently form the current supplied by the charger.
To calculate the duration of voltage/current that a battery can supply, refer to the data sheet of the battery. Basically the Ah that a lead battery can supply depends on its efficiency
status, on the charge level and other factors such as T ambient (low ambient temperatures reduces the capacity of the battery) ageing reduces the capacity of the battery.
The average life span of a properly used lead battery is 4/5 years.
DECLARATION OF CONFORMITY
NEXTYS SA. (www.nextys.com)
Via Luserte Sud 8, 6572 Quartino - Switzerland
Phone: +41-(0)91 840 14 46 / 840 14 48; Fax: +41-(0)91 840 14 47
This Declaration of Conformity is suitable to the European Standard EN 45014 "General criteria for supplier’s declaration of conformity".
We declare under our sole responsibility that the material under described:
Code Description
NCU120-12 Single phase switching power supply with integrated UPS function IN 120 - 240 Vac (110 - 345Vdc) / OUT 12 Vdc 7.0 A
NCU120-24 Single phase switching power supply with integrated UPS function IN 120 - 240 Vac (110 - 345Vdc) / OUT 24 Vdc 5.0 A
Has passed all processing inspections and the final test and it is in conformity with the product requirements, including all reference codes and supply specifications.
ROHS compliance: the product respects the EC requirements related to ROHS substances, according to “Restriction of Hazardous Substances” as per document
2011/65/UE
REACH compliance: the product respects the EC requirements related to REACH SVHC directive (2010)
Note: all the reported information comes from our suppliers, NEXTYS SA. Has not run any test to evaluate if the specific elements are present.
Certifications and approvals
Reference standards:
2006/95/EC (2006) (Low Voltage Directive)
EN60950-1 (2006-04/A11:2009) (Safety Standards)
UL508 (Safety Standards)
EN61000-6-2 (2005) (Generic immunity standard, industrial environment)
EN61000-6-4 (2007) (Generic emission standard, industrial environment)
Date: 21.11.2013
Place: Quartino, Switzerland
The product manager
Marius Ciorica
TECHNICAL DATA (1) NOTES
Model type NCU120-12 NCU120-24
INPUT DATA
Input rated voltage (2) AC: single phase, 120…240Vac (range 90…265Vac)
DC: 110...345Vdc
Frequency 47...63 Hz / DC
Input rated current
Vin = 120Vac
Vin = 230Vac
(3)
2.0A
1.1A
Inrush peak current
Vin = 230Vac
< 20A
Power factor
Vin = 230Vac
> 0.65
Internal protection fuse Fuse 3.15AT/250Vac (not user replaceable)
External protection on AC line Fuse 4AT or MCB 4A C curve – (See Fig.6)
OUTPUT DATA
Rated voltage 12…15Vdc 24Vdc
Voltage adjustment 12…15Vdc 23…27.5Vdc
Continuous current (Uout nom.) 7.0A 5.0A
Overload limit 11A 8A
Short circuit peak current > 18A / 50ms > 12A / 50ms
Load regulation < 1%
Ripple (4) 80 mVpp
Hold up time
Vin = 120Vac
Vin = 230Vac
(3)
> 20ms
> 80ms
> 15ms
>70ms
Output protections Hiccup at the overload limit with auto reset - over temperature - overvoltage (See point 9 on “Instructions” page)
Output overvoltage protection (5) > 18Vdc > 33Vdc
“LOAD ON PSU”
LED (green) on = all functions and IN/OUT parameter are OK
off = Uout < 0.9 x Unom
“LOAD ON BATTERY”
LED (red) on = the load is supplied by the Battery
off = if both LED green and red are OFF, the Load isn’t supplied
Status signals
State Dry contact
Contact changes state when the SMPS is turned on:
it indicates that the load is supplied by the power supply.
it indicates that the load is supplied by the battery.
Its state is correlated with the LEDs status.
Alarm contact threshold Uout < 9.0Vdc Uout < 18Vdc
Parallel connection See point 8
Redundant parallel connection See point 8
BATTERY INFO
Rated Voltage 12…14.4Vdc 22…26.4Vdc
Max Charging current 0.8A
Battery Protection
against short-circuit with resettable fuse (9A)
against reverse polarity connection
against deep discharge ( 9V for -12 and 18V for -24 model)
GENERAL DATA
Efficiency > 83% > 86%
Dissipated power < 20W < 19W
Operating temperature - 20°C…+60°C / overtemperature protection
Derating - 4.0W/°C over 45°C
Overvoltage category
Pollution degree II
2 (IEC 664-1 )
Input / output isolation 4.2 kVdc
Input / ground isolation 2.2 kVdc
Output / ground isolation 0.75 kVdc
Standards, Approvals / Certifications UL508 (reference) – EN60950 (reference) – CE Marking
EMC Standards EN61000-6-4, EN61000-6-2
Protection degree IP20 acc. to EN60529
Connection terminals 2.5 mm², screw type pluggable (24...12 AWG)
Case Material Aluminum
Mounting Rail IEC 60715/H15/TH35-7.5(-15)
Approx. weight 0.500 kg (0.88 lbs)
Size (W x H x D) 54.0 x 115.0 x 110.0mm (See Fig.2)
Rail mounting information Vertical – Horizontal, allow 20mm spacing between adjacent items (See Fig.3)
NOTES
(1) if not diversely specified, all technical data are typical and measured at 25°C, Uin 230Vac, and nominal U, I output.
(2) see points 5) and 6) on “instructions” page.
(3) at full load, at 25°C.
(4) at full load, at 25°C, measured with probe connected to 100nF/20MHz termination.
(5) protected, with a crow bar diode, against voltage peaks and overvoltage coming from the DC line caused by inductive loads, see point 9) on “instructions” page.