Congure the system
EM24 M1/M2 - Instruction manual | CARLO GAVAZZI Controls SpAEM24 M1/M2 - Instruction manual | CARLO GAVAZZI Controls SpA
Settings from EM24 M1/M2
General settings
The available settings depend on the application set.
Page title Sub-menu Description Values Default value
Cng PASS - Change password From 0 to 9999 0
APPLiCAt Application tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.I
tYP.I
User USEr 1 User From 1 to 9999 1
USEr 2 From 1 to 9999 2
USEr 3 From 1 to 9999 3
SELECtor SELEC. 1 Page displayed according to selector
position among the available pages for
each application (see “Frontal selector”
on page 14)
From 1 to 20 17
SELEC. 2 From 1 to 20 19
SELEC. 3 From 1 to 20 20
SELEC.LoC From 1 to 20 20
SYS - System 3P.n
3P.1
2P
1P
3P
Note: MID (PFA, PFB): only 3P.n
3P.n
Ut rAtio - Voltage transformer ratio (VT) From 1 to 6000 1
Ct rAtio - Current transformer ratio (CT) From 1 to 60000 1
P int.ti - Dmd integration time (min) From 1 to 30 15
FiLtEr.S - Interval of lter intervention with respect
to full scale (%)
From 0 to 100 2
FiLtEr.Co - Filter coefcient From 1 to 32 2
AddrESS AddrESS Primary AddrESS From 0 to 247 0
bAudrAtE Baud rate 300/2400/9600 2400
Ene t.rES Reset of all the total counters YES/no no
End - Exit and save - -
Note: the Ut rAtio is available for compatibility with other versions, even though the AV5 version is not meant to be used with voltage transformers. It should
be therefore set to 1.
General settings - SFA models
The available settings depend on the application set.
Page title Sub-menu Description Values Default value
Cng PASS - Change password From 0 to 9999 0
FiLtEr.S - Interval of lter intervention with respect
to full scale (%)
From 0 to 100 2
FiLtEr.Co - Filter coefcient From 1 to 32 2
AddrESS AddrESS Primary AddrESS From 0 to 247 0
bAudrAtE Baud rate 300/2400/9600 2400
End - Exit and save - -