DN4234 Installation Manual
Product Description
The DN4234 is a stand-alone power supply for three-phase mains systems, which provides a
stabilized and galvanically separated PELV/ES1 output voltage at 4 outputs via two output connectors.
The negative potential of the outputs is permanently connected to PE within the unit.
The housing is rated as IP65 and IP67 according IEC60529 and provides protection against electrical,
mechanical and fire hazards.
Intended Use
This indoor use device is intended for commercial use, such as in industrial control, process control,
monitoring, measurement or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or
threaten human life, without additional appropriate safety devices, that are suited for the end-
application.
If used in a manner outside of its specification, the protection provided by the device may be impaired.
Installation Instructions
Install the device with the terminals on the bottom of the device. Other mounting orientations require a
reduction in output current. When installing watch out for the risk of injury from sharp edges and
assure that when installed any sharp edges on the back cannot be accessed and cannot cause injury.
Use 4 screws ( 2 on top and 2 on bottom mounting holes) suitable for the underground and a strength
comparable to M4 or UNC 8-32 screws.
The device is designed for pollution degree 3 areas in controlled environments.
The enclosure of the device provides a degree of ingress protection of IP65 and IP67 when installed
with all mating connectors firmly connected.
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use
without a proper PE (Protective Earth) connection.
For TN,TT mains systems with earthed neutral and IT star mains systems with insulation monitoring
the device is designed for overvoltage category III zones up to 2000m (6560ft) and for overvoltage
category II zones up to 5000m (16400ft). For TN, TT, IT delta mains systems or IT star mains
systems without insulation monitoring the device is intended for overvoltage category II zones up to
2000m (6560ft). The device is designed to be safe in case of a single phase loss and does not require
an external protection.
The device is designed for convection cooling without a fan. Do not obstruct airflow.
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required and the operation is limited according mains systems description above.
Keep the following minimum installation clearances: 50mm on top and bottom, 10mm on the front and
10mm left and right side.
The device is designed, tested and approved for branch circuits up to 20A (UL) and 32A (IEC) without
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
Make sure that you only use plugs and cables rated for the device output current and the required
temperature range. Follow all local and national codes for installation. Do not parallel devices or
outputs for higher output currents.
The maximum permissible ambient air temperature is +70°C (+158°F). The operational temperature is
the same as the ambient or ambient air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Do not connect the negative potential of any output to PE.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including inductive and capacitive loads. If capacitors with a capacitance >20mF are
connected to one output, this output might switch off after turning the unit or the output on or
connecting the load. Do not apply return voltages from the load to the output terminals higher than
35V. Feed-back energy from a load must be below 4J.
The green Status LED reports an output above 90% of the adjusted voltage of a running device and all
three phase voltages are present.
The device has an internal overtemperature protection. If the temperature is too high the unit shuts
down and starts automatically again after cooling off. Each output will get the same state as before the
shutdown.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.5V. The unit
shuts down and automatically attempts to restart..
LED bargraph and push-buttons:
Normal operation of the LED bar is the monitoring mode showing the actual output power as
percentage of 500W (100% is 500W). Percentages above 100% is shown in orange flashing. Pressing
the up/down buttons shows the percentage of each output. The steady orange LED indicates the
selected output. Pressing the “Set” button let all LEDs flash for a short time and changes the LED bar
into the configuration mode. Pressing the up or down button for 1.25s deactivates the user hurdle.
With the up/down buttons the voltage can be changed to the values indicated by the single flashing
green LED, while all orange LED are dark. The voltage is set as soon as the “Set” button is pressed,
and the value stored until the next change. Pressing up and down buttons for at least 1s.
simultaneously, undo the last step. Pressing the “Set” button again, changes into “monitoring”. To
change the current limit of the outputs, you have to select the channel with up/down button. The
orange LED indicates the selected output. Pressing “Set” changes into the “configuration” of the
selected channel. Pressing the up or down button for 1.25s deactivates the user hurdle. With the
up/down buttons the current limit can be changed to the values indicated by the single flashing green
LED. The current limit value is set as soon as the “Set” button is pressed, and stored until the next
change. Pressing the “Set Mode” button again, changes into “monitoring”. Select other outputs with
up/down button and press the “Set” button to change to “configuration”. Without further pressing of
push-buttons, the LED bar will return from any other mode to “monitoring” after 30s.Further details of
the operating you can find in the “operating diagram”, next page. With the buttons at each channel, the
channel can turned on/off manually by pressing for at least 1s.
Mating connectors:
For the mating input voltage connector (X1) use a 7/8” 5 pin female connector. The Pin assignment is
Pin 1 for L1, Pin 4 for L2, Pin 5 for L3 and Pin 3 for PE.
For mating the output voltage connectors (X3,X4) use a standard M12 L-coded male connectors.
Pin assignment X3 (X4) is Pin 1 is 24VDC Out1(3); Pin 2 is 0V DC Out2(4); Pin 3 is 0V DC Out1(3);
Pin4 is 24V DC Out2(4); Pin5 is FE;
All values are typical figures specified at 3x 400Vac 50Hz input voltage,
symmetrical phase voltages, 24V,
500W output load, 25°C ambient
temperature and after a 5 minutes run-in time unless otherwise noted.
Derate linearly between +45°C and +70°C
Settable per output; up to 12A
At 3x400 / 480Vac,
temp. independent
Output Characteristic per output
Hole Pattern for Mounting
All dimensions in mm connectors X1 to X4 from left to right
Allowed output power
Ambient temperature
0
-25 0+70°C
600W
700W
+45
1000W
350W
B
A: continuous
B: short term (max. 5s)
A
+55
500W