Haier 3U24GS1ERA Guida d'installazione

Categoria
Condizionatori d'aria a sistema split
Tipo
Guida d'installazione

Questo manuale è adatto anche per

INSTALLATION MANUAL
MULTI-SPLIT AIR CONDITIONER
Please read this manual carefully before installation.
Keep this operation manual for future reference.
No. 0150508607 D
INSTALLATION MANUAL
MULTI-SPLIT AIR CONDITIONER
Please read this manual carefully before installation.
Keep this operation manual for future reference.
3
4
4
5
7
7
7
7
12
12
14
15
Contents
English
Safety Precautions
Accessories
Precautions for Selecting the
Location
Installation drawings of indoor and
outdoor units
Precautions on Installation
Outdoor Unit Installation Guideline
Limitations on the installation
Refrigerant piping work
Pump Down Operation
Wiring work
Test running
Trouble shooting
3
Safety Precautions
WARNING
CAUTION
WARNING
CAUTION
Read these Safety Precautions carefully to ensure correct installation.
This manual classifies the precautions into WARNING and CAUTION.
Be sure to follow all the precautions bellow: they are all important for ensuring safety.
Failure to follow any of WARING is likely to result in such grave consequences as death or serious injury.
Failure to follow any of CAUTION may in some cases result in grave consequences.
The following safety symbols are used throughout this manual:
Be sure to observe this instruction Be sure to establish an earth connection Never attempt
After completing installation, test the unit to check for installation errors. Give the user adequate instructions conceming the use and cleaning
of the unit according to the Operation Manual.
Installation should be left to the dealer or another professional.
Improper installation may cause water leakage, electrical shock, or fire.
Install the air conditioner according to the instructions given in this manual.
Incomplete installation may cause water leakage, electrical shock, or fire.
Be sure to use the suplied or specified installation parts.
Use of other parts may cause the unit to cometo lose, water leakage, electrical shock, or fire.
Install the air conditioner on a solid base that can support the unit's weight.
An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice.
Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection.
Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.
(Failure to do so may cause abnormal heat, electric shock or fire.)
Use the specified types of wires for electrical connections between the indoor and outdoor units.
Firmly clamp the interconnectiong wires so their terminals terminals receive no external stresses. Incomplete connections or clamping may cause terminal overheating or fire.
After connectiong interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical
covers or panels.
Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.
If any refrigerant has leaked out during the installation work, ventilate the room.
(The refrigerant produces a toxic gas if exposed to flames.)
After all installation is complete, check to make sure that no refrigerant is leaking out.
(The refrigerant produces a toxic gas if exposed to flames.)
When installing or relocating the system, be sure to keep the refrigerant circuit free from substancs other than the specified
refrigerant(R410A), such as air.
(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)
During pump-down, stop the compressor before removing the refrigerant piping.
If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the rcompressor is run, causing abnormal pressure in the freezer
cycle which will lead to breakage and even injury.
Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.
In complete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks, or fire.
Do not install the aire conditioner in a place where there is danger of exposure to inflammable gas leakage.
If the gas leaks and builds up around the unit, it may catch fire.
Establish drain piping according to the instructions of this manual.
Inadequate piping may cause flooding.
Tighten the flare nut according to the specified method such as with a torque wrench.
If the flare nut is tightened too hard, the falre nut may crack after a long time and cause refrigerant leakage.
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
4
Accessories
Precautions for Selecting the Location
NOTE:
CAUTION
Construct a large canopy.
Construct a pedestal.
Install the unit high enough off the
ground to prevent burying in snow.
Accessories supplied with the outdoor unit:
1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot aire discharged from the unit or the operation noise, will not cause a nuisance to the neighbors of the
user.
3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient space for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
Locate the unit so that the noise and the discharged hot air will not annoy the neighbors.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is to prevent interference to
images and sounds. (Noises may be heard even if they are more than 3 meter away depending on radio wave conditions.)
8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9)Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.
Cannot be installed hanging from ceiling or stacked.
When operationg the air conditioner in a low outdoor ambient
temperature, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its suction
side facing the wall.
2) Never install the outdoor unit at a site where the suction side may be
exposed directly to wind.
3)To prevent exposure to wind, it is recommended to install a baffle plate
on the air discharge side of the outdoor unit.
4) In heavy snowfall areas, select an installation site where the snow
will not affect the unit.
5
Installation figure please refers to
1. Do not connected the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor
unit in ordor to add another indoor unit later. Make sure no dirt or mositure gets into eigher side of the embedded branch piping.
2.It is impossible to connect the indoor unit for one room only.
Installation drawings of indoor and outdoor units
If there is the danger of the unit falling or overturning, fix the unit with foundation bolts, or with wire or other means.
If the location does not have good drainage, place the unit on a level mounting base(or a plastic pedestal).
Install the outdoor unit in a level position. Failure to do so may result in water leakage or accumulation.
Arrangement of piping directions
Rear left
Rear right
Right
Below
Left
Wrap the insulation pipe with the finishing tape
from bottom to top.
Cut thermal insulation pipe to an appropriate
length and wrap it with tape, making sure that no
gap is left in the insulation pipe's cut line.
more than 10cm
more than 10cm
more than 60cm
more than 25cm
More than 5cm
More than 10cm
Attention must be
paid to the rising
up of drain hose
6
Installation drawings of indoor and outdoor units
Connection cautions
model
connection priority between indoor and
stop valve higher from down to up
when there is 1 indoor,the prior stop
valve is
when there are 2 indoors,the prior
stop valves are
when there are 3 indoors,the prior
stop valves are
when there are 4 indoors,the prior
stop valves are
when there are 5 indoors,the prior
stop valves are
Note: For better oil return and more reliable system, please execute as the above when connecting indoor unit.
C
C B
C B A
D
D C
D C B
D C B A
E
E D
E D C
E D C B
E D C B A
7
20
Precautions on Installation
Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts.(Prepare four sets of M8 or M10
foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.
Outdoor Unit Installation Guideline
Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines below.
For any of the below installation pattems, the wall height on the exhaust side should be 1200mm or less.
Limitations on the installation
2.Selecting a location for installation of the indoor units
The maxinum allowable length of refrigerant piping, and the maxmum allowable height difference between the outdoor and indoor units,
are listed below. (The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. Shortest
allowable length per room is 3m)
1.Precautions on installation
Check the strength and level of the installation ground so that unit will not cause any operating vibration or noise after installation.
In accordance with the foundation drawing in fix the unit securely by means of the foundation bolts.
It is best to screw in the foundation bolts unit their length are 20 mm from the foundation surface.
More than 50 More than 300
1200 or
less
Side view
Wall facing one side
More
than 100
More
than 100
More
than 50
More
than 300
Side view
Wall facing two sides
More than 150
More
than 50
More than 300
Side view
Wall facing three sides
8
Refrigerant piping work
1. Installing outdoor unit
1) When installing the outdoor unit, refer to "Precautions for Selecting the Location" and the "Indoor/Outdoor Unit Installation Drawings".
2)If drain work is necessary, follow the procedures below.
2. Drain work
1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 30mm in height under the
outdoor unit's feet.
3) In cold areas, do not use a drain hose with the outdoor unit.(Otherwise, drain water may freeze, impairing heating performance.)
Drain elbow
Hose
Drain elbow
Hose
Indoor Unit
Outdoor Unit
Level
difference:
15m max.
Level
difference:
7.5m max.
If the outdoor unit is positioned higher than the indoor units.
Outdoor Unit
Indoor Unit
Level
difference:
15m max.
Level
difference:
7.5m max.
If the outdoor unit is positioned higher than the indoor units.
(If lower than one or more indoor units.)
Limitations on the installation
9
4. Purging air and checking gas leakage
WARNING
3. Refrigerant piping work
When piping work is completed, it is necessary to purge the air and check for gas leakage.
1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerents may damage the vacuun pump
or the unit.
If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional
refrigerant.
Use a hexagonal wrench (4mm) to operate the stop valve rod.
All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque.
Connect projection side of charging hose(Which comes from gauge manifold) to gas stop valve's service port.
Fully open gauge manifold's low-pressure valve(Lo) and completely close its high-pressure valve(Hi).
(High-pressure valve subsequently requires no operation.)
Apply vacuum pumping. Check that the compound pressure gauge reads-0.1MPa(-76cmHg).
Evacuation for at lease 1 hour is recommended.
Close gauge manifold's low-pressure valve(Lo) and stop vacuum pump.
(Leave as is for 4-5 minutes and make sure the coupling meter needie does not go back.
If it does go back, this may indicate the presence of moisture or leaking from connecting parts. After inspecting all the connection and
loosening then retightening thenuts, reqeat steps 2-4. )
Remove covers from liquid stop valve and gas stop valve.
Turn the liquid stop valve's rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods.
After the check is complete, wipe all soapy water off.
Disconnect charging hose from gas stop valve's service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rodj beyond its stop.)
Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques. See "3
Refrigerant piping " on page 6 for details.
Refrigerant piping work
2)To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare. (Use refrigeration oil for R410A)
Torque spanner
Spanner
Pipe joint
Cone nut
10.8-14.7N.m(110-150kgf.cm)
Valve cap tightening torque
Liquid pipe 26.5-32.3N.m(270-330kgf.cm)
Gas pipe 48.1-59.7N.m(490-610kgf.cm)
Service port cap tightening torque
Coat here with refrigeration oil
1). Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the tor wrenches.
Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas.
Flare nut fightening torque
14.2-17.2N.m(144-175kgf.cm)
32.7-39.9N.m(333-407kgf.cm)
49.5-60.3N.m(505-615kgf.cm)
61.8-75.4N.m(630-769kgf.cm)
Flare nut for 6.35
Flare nut for 9.52
Flare nut for 12.7
Flare nut for 15.88
10
5. Refilling the refrigerant
6. Charging with refrigerant
Notes:
Gas pipe
Gas pipe insulation
O.D.:9.52mm,12.7mm
Thickness:0.8mm
I.D.:12-15mm,12.7mm
Thickness:13mm min.
Liquid pipe
Liquid pipe insulation
O.D.:6.35mm
Thickness:0.8mm
I.D.:18-10mm
Thickness:10mm min.
7.Precautions for Laying Refrigerant Piping
Cautions on pipe handling
1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for bending.(Bending radius should be 30 to 40mm or larger.)
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following :
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK(0.035to 0.045kcal/mh
o
C)
Refrigerant gas pipe's surface temperature reaches 110
o
C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Check the type of refrigerant to be used on the machine namiplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not.(It should have something like "liquid filling siphon attached"
displayed on it.)
2) Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
1) This system must use refrigersant R410A.
2) Add refrigerant 20g per meter when the total piping length
exceeds the standard value, but make sure that the total liquid
piping length should be less than the max. value.
1) When using this product, you need not to set the address. But the L/N wires between indoor & outdoor units must be corresponded,
or there will be communication failure.
2) Quiet Operation Setting. Set the DIP "8" to ON position of SW5, the system will run with lower noise, but the max. capacity will also
reduce slightly.
3) Do not change the settings of other switchs, wrong settings can make the system damage or other malfunctions.
Refrigerant piping work
Filling a cylinder with an attached siphon
Stand the cylinder upright when filling.
There is a siphon pipe inside, so the
cylinder need not be upside-down
to fill with liquid.
Filling other cylinders
Turn the cylinder upside-down
when filing.
11
8.Cutting and Flaring work of piping
Pipe cutting is carried out with a pipe cutter and burs must be
removed.
After inserting the flare nut, flaring work is carried out.
Refrigerant Piping Work
WARNING
3) Use separate thermal insulation pipes for gas and liquid refrigerant
pipe.
It becomes high
midway.
The end is immersed
in water It waves.
Less than
5cm
It gap with the ground its
too small.
There is the bad
smell from a ditch.
Please pour water in the drain pan of the indoor unit, and confirm that drainage is carried out serely to outdoor.
In case that the attached drain hose is in a room, please apply heat insulation to it without fail.
9. On drainage
Please install the drain hose so as to be downward slope without fail. Please don't do the drainage as shown below.
Correct Incorrect
Lean Damage of flare Crack Partial Too outside
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would educe the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incom;ete flaring may cause refrigerant gas leakage.
Cut exactly at right
angles.
Remove burrs
Flare's inner
surface must be
flaw-free.
The pipe end
must be evenly
flared in a perfect
circle.
Make sure that the
flare nut is fitted.
Check
A
Flare tooling die
Pipe diameter Size A (mm)
Liquid side
Gas side
6.35mm(1/4")
9.52mm(3/8")
0.8~1.5
1.0~1.5
12.7mm(1/2") 1.0~1.5
Pipe
Be sure to
place a cap.
If no flare cap is
available, cover the
flare mouth with tape
to keep dirt or water
out.
Rain
Wall
Inter unit wiring
Gas pipe
Gas pipe
insulation
Finishing tape
Drain hose
Liquid pipe
insulation
Liquid pipe
A
Flare tooling die
Set exactly at the position shown below.
Flare tool for R410A
Clutch-type
0-0.5mm
Conventional flare tool
Clutch-type(Rigid-type)
1.0-1.5mm
Wing-nuttype(Imperial-type)
1.5-2.0mm
12
1. Electric wiring
The air conditioner must use special circuit , and wiring by the qualified electrician according to the wiring rules specified in national
standard.
The grounding wire and the neutral wire shall be strictly separated. Connect the neutral wire with grounding wire is incorrect.
The electric leakage breaker must be installed.
All the electric wire must be copper wire.Power supply:
The wiring method of power line is Y connection. If the power line is damaged, in order to avoid risk of electric shock, it must be replaced
by the manufacturer or its repair center or other similar qualified person.The connecting cable must be shielded.
Fuse: T3.15A 250VAC T16A 250VAC (Please check with the outdoor unit wiring diagram.)
Please check the circuit diagram about the fuse replaced.
Wiring method of orbicular terminals
For the connection wire with orbicular terminals, its wiring method is as shown in
the right figure: remove the connecting screw, put the screw through the ring on
the end of the wire, then connect to the terminal block and fasten screw.
Wiring method of straight terminals.
Crimp connection method for wires without terminals
For the connection wire without orbicular terminals, its wiring method is: loosen
the connection screw, and insert the end of the connection wire completely into
the Terminal block, then fasten the screw.
Slightly pull the wire outwards to confirm it is firmly held.
Note: Power line and communication wire are provided by consumers themselves.
Pump Down Operation
liquid
stop valve
Gas
stop valve
Valve cap
Hexagonal
wernch
Close
In order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Remove the valve caps from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
4) After two to three minutes, close the gas stop vaile and stop forced cooling
operation.
Crimp connection method for connection wire
After connection,the wire must be fastened by wire cover. The wire cover shall press on the protection
coat of the connection wire,as shown in right top figure.
Note:When connecting the wiring,confirm the terminal number of indoor and outdoor units carefully.
Incorrect wiring will damage the controller of air conditioner or the unit can not operate.
3. Wiring method of outdoor unit:
Power line
Remove the repair board of the outdoor unit and loosen the wire cover A,then put the live wire, neutral wire and grounding wire through
the wire cover ,and connect them to terminal block correspon dingly. After connection, fasten wire cover to its previous state.
Communication wire of indoor unit.
Loosen wire cover , put the communication wire through the wire cover B, and connect them to terminal block correspondingly. After
connection, fasten wire cover B to its previous state.
2. Wiring method
Wiring Method for
Ring Terminal Block
Connect the wire with
same diameter to the
two sides of the terminal
Do not connect the
wire with same diameter
to the same side
Do not connect the
wire with different
diameters
Wiring work
Correct Pressing
Wrong Pressing
Terminal
block
Pressing
Clamps
13
Wiring diagram please refers to
Loosen wire cover and connect the power line and communication wire of indoor unit to the terminal correspondingly.
Note:
When connecting power line to power supply terminal, please pay attention to the following items:
Do not connect the power line with different dimensions to the same connection wire end.
Improper contact will cause heat generation.
Do not connect the power line with different dimensions to the same grounding wire end.
Improper contact will affect protection.
Do not connect the power line to the connecting end of communication wire.
Incorrect connection will cause damage to the connected unit.
4. Wiring method of indoor unit
Wiring work
Valve cover
–¨ 25.400
Terminal block
Wire cover A
Wire cover B
Wire cover C
Wire cover A
Wire cover B
Wire cover C
Wire cover D
Wire cover E
Terminal block
Valve cover
5. Example wiring diagram.
14
Switch on all the 4 dip-switches on the outdoor unit small service PC-board as shown on the right. Then power
off the unit and power on again, the system will enter the operation of "Wiring Error Check". After 3 minutes
stand-by, the unit starts for automatic wiring checking.
Approximately 30 ~ 50minutes (depends on how many units installed in the system) after the unit starts, the
Errors of the wiring will be shown by the LEDs (1 to 5).
Before starting the test running, please confirm the following works have been done successfully.
1) Correct piping work;
2) Correct wiring work;
3) Correct match of indoor and outdoor unit;
4) Proper recharge of refrigerant if needed.
Make sure that all the stop valves are fully open.
Check the voltage supplied to the outdoor and indoor units, please cinfirm that is 230V.
Test running
Test running.
1) If the temperature is lower than 16
O
C, it is impossible to test cooling with remote controller, and also when the temperature is higher than
30
O
C, it is impossible to test heating.
2) To test cooling, set the lowest temperature at 16
O
C. To test heating,set the highest temperature, at 30
O
C.
3) Please check both cooling and heating operation of each unit individually and then also check the simultaneous operation of all indoor
units.
4) After ruuning the unit for about 20 minutes, check the indoor unit outlet temperature.
5) After the unit is stopped, or working mode changed, the system will not start again for about 3 minutes.
6) During cooling operation, frost may ocur on the indoor unit or pipes, this is normal.
7) Operate the unit according to the operation manual. Please kindly explain to our customers how to operate through the instruction manual.
ON
4321
CN2 CN3
CN1
CN4
SW1
4321
5
Seven-segment numeric display
1) When unit is runing, this seven-segment numeric will display the frequency of compressor. For
example," " means compressor running frequency is 40 Hz, " " means compressor running
frequency is 108Hz.
2) When faulty happens, seven-segment numeric will flash and display some numbers, this number is
failure code. For example, a flashing " " means No.32 failure, that is indoor and outdoor communication
error.
Communication LED
5 green LED means 5 indoor units. If one LED keep lighting that means the corresponding indoor unit has good communication with outdoor
unit. If one LED is not lighting, that means there is no communication between indoor and outdoor.
Wiring Error Check
This product is capable of automatic checking of wiring error.
ON
4321
CN2 CN3
CN1
CN4
SW1
4321
5
During this operation, the digital-number will alternately show the compressor working frequency (e.g. 50 stands for the current running
frequency) and letter "CH"(means checking).
After this operation, if all the wiring is correct, the digital-number will show "0", if there has wrong wiring, the digital-number will show "EC"(error
connection) and also it will flashing.
The service monitor LEDs indicate the error of wiring, as shown in the table below. For details about how to read the LED display, refer to
the service manual.
If self-checking is not possible, check the indoor unit wiring and piping in the usual manner.
Status
Only one LED flashing
15
Trouble shooting
Timer lamp
flash time
Running lamp
flash time
Faulty of outdoor unit EEPROM 1 15 2 1
IPM overcurrent or short circuit 2 16 2 2
Communication failure between Module and ECU
Communication cables broken or not well connected.
41824
Module operated overload 5 19 2 5
Module low or high DC voltage(under 192V or above
375V)
6 1A 2 6
Discharging temperature overheating.Lack of refrigerant,
ambient temperature too high or PMVs blocked.
81C28
Malfunction of the DC fan motor 9 1D 2 9
Malfunction of defrosting temp. sensor 10 1E 3 0
Malfunction of compressor suction temp. sensor 11 1F 3 1
Malfunction of ambient temp. sensor 12 20 3 2
Malfunction of compressor discharge temp. sensor 13 21 3 3
Communication failure between indoor&outdoor unit 15 23 3 5
Lack of refrigerant or discharging pipe blocked 16 36 3 6
4-way valve switching failure 17 25 3 7
Module overcurrent /Module switch failure 18 26 3 8
Indoor overload 20 28 4 0
Indoor frosted 21 29 4 1
Module temperature too high (Overload Protecter) 23 2B 4 3
Compressor overcurrent 24 2C 4 4
Input overcurrent 25 2D 4 5
MCU reset 26 2E 4 6
Module current detect circuit malfunction 27 2F 4 7
Malfunction of liquid pipe temp. sensor for indoor unit A 28 30 4 8
Malfunction of liquid pipe temp. sensor for indoor unit B 29 31 4 9
Malfunction of liquid pipe temp. sensor for indoor unit C 30 32 5 0
Malfunction of liquid pipe temp. sensor for indoor unit D 31 33 5 1
Malfunction of gas pipe temp. sensor for indoor unit A 32 34 5 2
Malfunction of gas pipe temp. sensor for indoor unit B 33 35 5 3
Malfunction of gas pipe temp. sensor for indoor unit C 34 36 5 4
Malfunction of gas pipe temp. sensor for indoor unit D 35 37 5 5
Malfunction of gas pipe temp. sensor for indoor unit E 36 38 5 6
Malfunction of module temp.sensor 38 3A 5 8
Malfunction of condensing temp. sensor 39 3B 5 9
Malfunction of liquid pipe temp. sensor for indoor unit E 40 3C 6 0
Malfunction of piping temp. sensor 41 3D 6 1
System high pressure switch off 42 3E 6 2
System low pressure switch off 43 3F 6 3
System high pressure protection.Refrigerant
overabundance,High condensing temp. or
malfunction of fan motor.
44 40 6 4
System low pressure protection.Refrigerant shortage,
Low defrosting temp., or malfunction of fan motor.
45 41 6 5
Malfunction of module temp.sensor 46 42 6 6
Cassette and convertible
indoor display outdoor error
code use the timer and runing
lamp
Wired
controller
display
Outdoor LED
display
Possible reasons
MANUAL DE INSTALACIÓN DEL APARATO DE AIRE
ACONDICIONADO DE TIPO MULTISPLIT
Contenido
Precauciones de seguridad
---------------- 3
Accesorios
------------------------------------ 4
Precauciones para seleccionar la
ubicación
---------------------------------------- 4
Esquemas de instalación de las
unidades
interior y exterior
------------------------------ 5
Precauciones a la hora de realizar
instalación
-------------------------------------- 7
Guía de instalación de la unidad
exterior
------------------------------------------ 7
Limitaciones en la instalación
------------- 7
Acometida de los tubos de
refrigerante
------------------------------------- 7
Funcionamiento de la bomba de
vacío
-------------------------------------------12
Cableado
--------------------------------------12
Prueba del aparato
--------------------------14
Resolución de problemas
-----------------15

Lea detenidamente este manual antes de instalar el aparato.
Guarde este manual de uso para futuras consultas.
Español
CONFORMIDAD DE LOS MODELOS
SEGÚN LAS NORMATIVAS EUROPEAS
CE
Todos los productos cumplen los requisitos de las siguientes
normas europeas:
- Directiva de baja tensión 73/23/CEE
- Directiva de baja tensión 2006/95/CE
- Compatibilidad electromagnética 89/336/CEE
- Compatibilidad electromagnética 2004/108/CE
ROHS
Los productos cumplen los requisitos de la directiva 2002/95/
CEE establecida por el Parlamento Europeo y el Consejo sobre
la Restricción del uso de determinadas sustancias peligrosas en
aparatos eléctricos y electrónicos (Directiva RoHS de la Unión
Europea).
WEEE
De acuerdo con la directiva 2002/96/CE del Parlamento Europeo,
se informa al consumidor acerca de los requisitos que han de
cumplirse para deshacerse de productos eléctricos y electrónicos.
REQUISITOS DE DESECHO:
Su aparato de aire acondicionado ha sido
marcado con este símbolo que significa que
los productos de tipo eléctrico y electrónico
no deben mezclarse con la basura doméstica
sin clasificar. No intente desmontar el sistema
por sí mismo: tanto el desmontaje del sistema de aire
acondicionado como la manipulación del refrigerante, el
aceite y cualquier otro componente deben ser llevados
a cabo por un instalador cualificado, de acuerdo con la
legislación local y nacional aplicable. Los aparatos de aire
acondicionado deben ser tratados en instalaciones de
manipulación especializadas para su reutilización, reciclado
y recuperación. Al garantizar la correcta eliminación de
este producto, estará contribuyendo a evitar las posibles
consecuencias negativas que podría provocar sobre el
medioambiente y la salud humana. Póngase en contacto
con el instalador o la autoridad local pertinente si desea
obtener más información. Las pilas deben ser extraídas del
mando a distancia y eliminadas de forma independiente, de
acuerdo con la legislación local y nacional aplicable.
INFORMACIÓN IMPORTANTE ACER-
CA DEL REFRIGERANTE UTILIZADO
Este producto contiene gases fluorados de efecto invernadero
regulados por el Protocolo de Kioto. No los libere a la atmósfera.
Tipo de refrigerante: R410A
Valor GWP*: 1975 1975
GWP = Potencial de contribución al calentamiento global
Escriba con tinta indeleble:
• 1 La carga de refrigerante que contiene el producto de fábrica
• 2 La cantidad de refrigerante adicional cargada in situ y
• 1+2 La carga total de refrigerante en la etiqueta de refrigerante
suministrada con el producto. Una vez escritos los datos
correspondientes, la etiqueta deberá adherirse cerca de la
conexión de carga del producto (por ejemplo, sobre la parte interna
de la cubierta de la válvula de retención).
A Contiene gases fluorados de efecto invernadero regulados por
el Protocolo de Kioto.
B Carga de refrigerante que contiene el producto de fábrica:
consulte la placa de características de la unidad.
C Cantidad de refrigerante adicional cargada in situ.
D Carga total de refrigerante.
E Unidad exterior.
F Botella de refrigerante y analizador para carga.
Haier Industrial Park, No.1 Haier Road, Qingdao, República Popular China
Contiene gases uorados de efecto invernadero
regulados por el Protocolo de Kioto.
Kg
Kg
Kg
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82

Haier 3U24GS1ERA Guida d'installazione

Categoria
Condizionatori d'aria a sistema split
Tipo
Guida d'installazione
Questo manuale è adatto anche per