TEC40D EV Operating the generator
17
OIL TEMP PRESS
Insufficient engine oil.
Engine temperature too high.
The generator stops. Fill up with oil (see chapter
“Checking the oil level” on
page 18).
Leave the generator to cool
down for a few minutes then start
up the generator again.
GENERATOR ALERT!
General alarm message
The generator stops. Check the system by referring to
the troubleshooting table.
If the problem persists, contact
the manufacturer's branch office
in your country (addresses on the
back page).
OVERLOAD!
The consumers generate an
overload at the output.
The inverter switches off, there-
fore no voltage is supplied but
the engine carries on running
until it goes off.
Reduce the connected load and
start the generator again.
SHORT CIRCUIT
The consumers cause a short
circuit at the output.
The inverter switches off, there-
fore no voltage is supplied but
the engine carries on running
until it goes off.
Check the connected consum-
ers then start the generator
again.
OVER TEMPERATURE
The inverter temperature is too
high.
The inverter switches off, there-
fore no voltage is supplied to
cool the generator, but the
engine carries on running.
Leave the generator to cool
down for a few minutes then start
up the generator again.
LOW POWER ENGINE
The inverter supply voltage has
dropped.
The generator stops. Reduce the connected load and
start the generator again.
GEN CAL
A message appears when the
generator is started up; it shows
the calibration phase which
takes place before each start-up.
The generator does not supply
any voltage.
The generator is running but
does not supply any voltage.
Wait a moment.
GEN WAIT
A message appears while you
are waiting for the generator to
start again.
The generator is switched off. Wait until the message has disap-
peared then attempt ignition
again.
Display message
Description
Generator behaviour Measures