Kamstrup EM24 DIN 1-phase, 3-phase & CT Guida utente

Tipo
Guida utente
ENGLISH
GENERAL WARNINGS
DANGER! Live parts. Heart attack, burns and other
injuries. Disconnect the power supply and load before
installing the analyzer. Protect terminals with covers.
The energy analyzer should only be installed by qualied/
authorized personnel.
These instructions are an integral part of the product. They
should be consulted for all situations tied to installation and
use. They should be kept within easy reach of operators, in
a clean place and in good conditions.
MAINTENANCE AND DISPOSAL
Cleaning
Use a slightly dampened cloth to clean the instrument display; do not
use abrasives or solvents.
Responsibility for disposal
The product must be disposed of at the relative recycling
centers specied by the government or local public authorities.
Correct disposal and recycling will contribute to the prevention
of potentially harmful consequences to the environment and
persons.
SERVICE AND WARRANTY
This product was specically developed to be used with the data acquisition systems
provided by Kamstrup. In the event of malfunction, fault, requests for information,
contact [email protected] or +45 89 93 10 00.
Connection diagrams
65A Self power supply, system type selection 3P.n
[1]- 3-ph, 4-wire unbalanced/balanced load. F= 250mA time-delay
65A Self power supply, system type selection 3P
[2]- 3-ph, 3-wire, unbalanced/balanced load
65A Self power supply, system type selection 1P
[3]- 1-ph, 2-wire. F= 250mA time-delay
10A System type selection 3P.n
[4]- 3-ph, 4-wire, unbalanced load, 3-CT connection. F= 250mA time-delay
10A System type selection 3P
[5]- 3-ph, 3-wire, unbalanced load, 3-CT connection. F= 250mA time-delay
EM24 DIN W1_01
[1] [2] [3]
[4] [5]
AV2 3X
AV5
ITALIANO
AVVERTENZE GENERALI
PERICOLO! Parti sotto tensione. Arresto cardiaco,
bruciature e altre lesioni. Scollegare l’alimentazione e il carico
prima di installare l’analizzatore. Proteggere i morsetti con le
coperture. L’installazione degli analizzatori d’energia deve
essere eseguita solo da persone qualicate/autorizzate.
Queste istruzioni sono parte integrante del prodotto. Devono
essere consultate per tutte le situazioni legate all’installazione e
all’uso. Devono essere conservate in modo che siano
accessibili agli operatori, in un luogo pulito e mantenuto in
buone condizioni.
MANUTENZIONE E SMALTIMENTO
Pulizia
Per mantenere pulito il display dello strumento installato usare un panno
leggermente inumidito; non usare abrasivi o solventi.
Responsabilità di smaltimento
Smaltire con raccolta dierenziata tramite le strutture di raccolte
indicate dal governo o dagli enti pubblici locali. Il corretto
smaltimento e il riciclaggio aiuteranno a prevenire conseguenze
potenzialmente negative per l’ambiente e per le persone
.
ASSISTENZA E GARANZIA
Questo prodotto è stato specicatamente sviluppato per essere utilizzato con i sistemi di
acquisizione dati forniti da Kamstrup. In caso di malfunzionamento, guasto o informazioni
sulla garanzia contattare [email protected] o +45 89 93 10 00.
Schemi di collegamento
65A, selezione sistema tipo 3P.n
[1]- 3 fasi, 4 fili carico squilibrato/equilibrato. F= 250mA ritardato
65A, selezione sistema tipo 3P
[2]- 3 fasi, 3 fili, carico squilibrato/equilibrato
65A, selezione sistema tipo 1P
[3]- 1 fase, 2 fili. F= 250mA ritardato
10A, selezione sistema tipo 3P.n
[4]- 3 fasi, 4 fili, carico squilibrato, connessione da 3 TA.
F= 250mA ritardato
10A, selezione sistema tipo 3P
[5]- 3 fasi, 3 fili, carico squilibrato, connessione da 3 TA.
F= 250mA ritardato
DEUTSCH
ALLGEMEINE SICHERHEITSHINWEISE
GEFAHR! Spannungsführende Teile. Gefahr von Herzstillstand,
Verbrennungen und sonstigen Verletzungen. Vor Beginn der Installation
des Energieanalysators elektrische Versorgung und Last trennen. Die
Klemmen mit den entsprechenden Abdeckungen schützen. Die Installation
der Energieanalysatoren darf nur von qualizierten und befugten Personen
ausgeführt werden.
Diese Anweisungen sind fester Bestandteil des Produkts. Sie
müssen vor der Installation und Verwendung sorgfältig gelesen
werden. Diese Anweisungen sicher an einem sauberen Ort
aufbewahren und für Bedienpersonen jederzeit verfügbar halten.
INSTANDHALTUNG UND ENTSORGUNG
Reinigung
Das Display am installierten Gerät mit einem leicht befeuchteten Tuch reinigen.
Keine Scheuer- oder Lösungsmittel verwenden.
Verantwortlichkeit für Entsorgung
Dieses Produkt muss bei einem geeigneten von der Regierung
oder lokalen öentlichen Autoritäten anerkannten
Recyclingbetrieb entsorgt werden. Ordnungsgemäße
Entsorgung und Recycling tragen zur Vermeidung möglicher
schädlicher Folgen für Umwelt und Personen bei
.
KUNDENDIENST UND GARANTIE
Dieses Produkt wurde speziell für die Datenerfassungssysteme von Kamstrup entwickelt.
Bei Störungen oder Fehlern bzw. wenn Sie Auskünfte bezüglich der Garantie benötigen,
kontaktieren Sie bitte [email protected] oder +45 89 93 10 00.
Anschlusspläne
65A, Systemwahl: 3P.n
[1]-3-ph, 4-Adern, asym./sym. Last
65A, Systemwahl: 3P
[2]- 3-ph, 3-Adern, asym./sym. Last.
65A, Systemwahl: 1P
[3]- 1-ph, 2-Adrig. F= 250mA zeitverzögert
(10A) Systemwahl: 3P.n
[4]- 3-ph, 4-Adrig, asymmetrische Last, 3 Stromwandleranschluss. F= 250mA
zeitverzögert
10A, Systemwahl: 3P
[5]- 3-ph, 3-Adrig, asymmetrische Last, 3 Stromwandleranschlüsse. F= 250mA
zeitverzögert
FRANÇAIS
AVERTISSEMENTS GÉNÉRAUX
DANGER! Pièces sous tension Crise cardiaque, brûlures
et autres blessures Débranchez l’alimentation électrique et
chargez le dispositif avant d’installer l’analyseur. Protégez les
bornes avec des couvercles. L’analyseur d’énergie doit être
installé par un personnel qualié/agréé.
Ces instructions sont partie intégrante du produit. Elles doivent
être consultées pour toutes les situations liées à l’installation et
à l’utilisation. Elles doivent être conservées de manière à être
facilement accessibles aux opérateurs, dans un endroit propre
et en bon état.
ENTRETIEN ET ÉLIMINATION
Nettoyage
Utilisez un chion légèrement mouillé pour nettoyer l’écran de l’instrument ; n’utilisez pas
d’abrasifs ou de solvants.
Responsabilité en matière d’élimination
Éliminer selon le tri sélectif avec les structures de récupération
indiquées par l’État ou par les organismes publics locaux. Bien
éliminer et recycler aidera à prévenir des conséquences
potentiellement néfastes pour l’environnement et les personnes
.
ENTRETIEN ET GARANTIE
Ce produit a été spécialement développé pour être utilisé avec les systèmes d’acquisition
de données fournis par Kamstrup. En cas de dysfonctionnement, de panne ou de besoin
d’informations sur la garantie, contactez [email protected] ou +45 89 93 10 00.
Schémas de branchement
65A Entrée auto-alimentée, sélection du type de réseau: 3P.n
[1]- 3 phases, 4 câbles, charge équilibrée/déséquilibrée. F= 250mA retardé
65A Entrée auto-alimentée, sélection du type de réseau: 3P
[2]- 3 phases, 3 câbles, charge équilibrée/déséquilibrée.
65A Entrée auto-alimentée, sélection du type de réseau: 1P
[3]- 1 phase, 2 câbles. F= 250mA retardé
10A Sélection du type de réseau: 3P.n
[4]- 3 phases, 4 câbles, charge déséquilibrée, connexions 3 TC. F= 250mA retardé
10A Sélection du type de réseau: 3P
[5]- 3 phases, 3 câbles, charge déséquilibrée, connexions 3 TC. F= 250mA retardé
ESPAÑOL
ADVERTENCIAS GENERALES
¡PELIGRO! Elementos sometidos a tensión. Ataque al
corazón, quemaduras u otras lesiones. Desconecte la fuente
de alimentación y carga antes de instalar el analizador.
Proteja los bornes con casquillos aislantes. El analizador de
energía sólo lo debe instalar personal cualicado/ autorizado.
Estas instrucciones forman parte integral del producto. Se
tienen que consultar para todo lo que tenga que ver con la
instalación y el funcionamiento. Se deben guardar donde estén
accesibles para los operarios, en un lugar limpio y en buenas
condiciones.
MANTENIMIENTO Y ELIMINACIÓN
Limpieza
Utilice un trapo ligeramente mojado para limpiar la pantalla; no use abrasivos o
disolventes.
Responsabilidad de eliminación
Eliminar mediante recogida selectiva a través de las estructuras
de recogida indicadas por el gobierno o por los entes públicos
locales. La correcta eliminación y el reciclaje ayudarán a prevenir
consecuencias potencialmente negativas para el medioambiente
y para las personas
.
REPARACIÓN Y GARANTÍA
Este producto fue desarrollado especícamente para ser utilizado con los sistemas de
adquisición de datos proporcionados por Kamstrup. Si se producen fallos o anomalías
en el funcionamiento o quiere conocer las condiciones de garantía póngase en
contacto con [email protected] o +45 89 93 10 00.
Diagramas de conexión
65A, Autoalimentado, selección del sistema: 3P.n
[1]- Trifásico, 4 hilos, carga equilibrada y desequilibrada.
F= 250mA temporizado.
65A, Autoalimentado, selección del sistema: 3P
[2]- Trifásico, 3 hilos, carga equilibrada y desequilibrada
65A, Autoalimentado, selección del sistema: 1P
[3]- Monofásico, 2 hilos. F= 250mA temporizado.
10A, selección del sistema: 3P.n
[4]- Trifásico, 4 hilos, carga desequilibrada, conexión 3 trafos de intensidad. F=
250mA temporizado.
10A, selección del sistema: 3P
[5]- Trifásico, 3 hilos, carga desequilibrada, conexión 3 trafos
de intensidad. F= 250mA temporizado.
DANSK
GENERELLE ADVARSLER
FARE! Spændingsførende dele. Hjerteanfald,
forbrændinger og andre kvæstelser. Afbryd strømtilførslen og
belastningen, inden analysatoren installeres. Beskyt
klemmerne med afdækninger. Energianalysatoren må kun
installeres af fagkyndigt/autoriseret personale.
Denne vejledning er en integreret del af produktet. Den skal
konsulteres i alle situationer, som drejer sig om installation og
brug. Den skal være tilgængelig for operatørerne, opbevares
på et rent sted og holdes i god stand.
VEDLIGEHOLDELSE OG BORTSKAFFELSE
Rengøring
Brug en let fugtig klud til rengøring af målerens display; brug ikke slibende midler
eller opløsningsmidler.
Ansvar for bortskaelse
Produktet skal bortskaes på en lokal, godkendt genbrugssta-
tion. Korrekt bortskaelse og genbrug vil bidrage til at mindske
eventuelle skadelige konsekvenser for miljøet, mennesker og
dyr.
SERVICE OG GARANTI
Dette produkt blev specikt udviklet til at blive brugt sammen med
dataindsamlingssystemerne leveret af Kamstrup. Hvis der opsr fejlfunktioner og
defekter, eller hvis der er brug for oplysninger om garantien, bedes du kontakte
[email protected] eller +45 89 93 10 00.
Tilslutningsdiagrammer
65 A, egen strømforsyning, valg af systemtype: 3-fa.n
[1]- 3-fa.n, 4 ledere, ubalanceret/balanceret belastning.
F= 250mA træg
65 A, egen strømforsyning, valg af systemtype: 3P
[2]- 3-fa.,3 ledere, ubalanceret/balanceret belastning.
F= 250mA træg
65 A, egen strømforsyning, valg af systemtype:
[3]- 1-fa., 2 ledere. F= 250mA træg
10 A, valg af systemtype: 3-fa.n
[4]- 3-fa., 4 ledere, ubalanceret belastning, 3-CT tilslutning.
F= 250mA træg
10 A, valg af systemtype: 3P
[5]- 3-fa., 3 ledere, ubalanceret belastning, 3-CT tilslutning.
F= 250mA træg
User manual www.productselection.net/MANUALS/UK/em24_W1_01_im_use.pdf
2014/53/EU (RED)
2011/65/EU (Rohs)
MID: EN5470-1, EN50470-3
Electromagnec compability (EMC) - emissions and immunity: IEC/
EN62052-11
Electrical safety: EN50470-1, EN61010-1
Accuracy: EN50470-3, IEC/EN 62053-23
AV2 1X
10A
AV5
65A
AV2
Dear installer
Scan this QR code to open the
Getting Started Guide.
Dear property owner
To get the most out of your new meter,
please create an account and register the
serial number.
Follow the instruction at
kamstrup.com/getting_started_guide
TECHNICAL SPECIFICATIONS
Voltage
AV2 AV5
Connection Direct Direct
Rated voltage L-N
(from Un min to Un max)
From 133 to 230 V 230 V
Rated voltage L-L
(from Un min to Un max)
From 230 to 400 V 400 V
Voltage tolerance -20, +15%
Overload Continuous: 1.15 Un max
For 500 ms: 2 Un max
Input Impedance Refer to “Power supply”
Frequency 50 Hz
Current
AV2 AV5
Connection Direct Via CT
CT ratio - 1 to 2615
In -5 A
Ib 10 A -
Imin 0.5 A 0.05 A
Imax 65 A 10 A
Ist 0.04 A 0.01 A
Overload
Continuous
• 500 ms
• 10ms
65A @50Hz
-
1950A,@ 50Hz
10A @50Hz
200A, @ 50Hz
-
Input
impedance < 1.1 VA < 0.6 VA
Crest factor 4 3
Power supply
Type Self power supply
Consumption AV2 3X, AV5: 1.8 W; 2.7 VA
AV2 1X: 0.8 W; 1.7 VA
Wireless M-Bus
Protocols Wireless M-Bus according to EN13757-3,
EN13757-4
Frame format B
Frequency 868 MHz
Mode C1
Encryption AES-128 Counter Mode
Transmission interval 96 s
LED
Red. Weight: proportional to energy consumption and depending on the CT
and VT/PT ratio product (16 Hz maximum frequency):
AV5 models
CT Weight (kWh per pulse)
≤ 7 0.001
> 7 ≤ 70.0 0.01
> 70 ≤ 700.0 0.1
> 700 1
AV2 models
CT Weight (kWh per pulse)
- 0.001
General
Protection degree Front: IP50. Screw terminals: IP20.
Insulation (for 1 minute) 4kV (between measurement input and Ethernet port)
Measurement category Cat. III
Dielectric strength 4000 VRMS for 1 minute.
Connections Screw-type.
Cable cross-section area AV2: max. 16 mm2 ; min. 2.5 mm2 (by cable lug)
AV5: Max. 1.5 mm2
Mounting DIN-rail.
Weight 400 g (packing included).
800 g with external antenna (packing included).
Environmental specifications
Operating temperature -25°C to +55°C (-13°F to 131°F)
Storage temperature -30°C to +70°C (-22°F to 158°F)
ENGLISH
CARATTERISTICHE TECNICHE
Tensione
AV2 AV5
Connessione Diretta Diretta
Tensione nominale L-N
(da Un min a Un max)
Da 133 a 230 V 230 V
Tensione nominale L-L
(da Un min a Un max)
Da 230 a 400 V 400 V
Tolleranza tensione -20, +15%
Sovraccarico Continuo: 1,15 Un max
Per 500 ms: 2 Un max
Impedenza d’ingresso Vedere “Alimentazione”
Frequenza 50 Hz
Corrente AV2 AV5
Connessione Diretta Via CT
Rapporto CT - da 1 a 2615
In -5 A
Ib 10 A -
Imin 0,5 A 0,05 A
Imax 65 A 10 A
Ist 0,04 A 0,01 A
Sovraccarico
Continuo
• 500 ms
• 10ms
65A @50Hz
-
1950A,@ 50Hz
10A @50Hz
200A, @ 50Hz
-
Impedenza
d’ingresso
< 1,1 VA < 0,6 VA
Fattore di cresta 4 3
Alimentazione
Tipo Autoalimentato
Consumo AV2 3X, AV5: 1,8 W; 2,7 VA
AV2 1X: 0,8 W; 1,7 VA
Wireless M-Bus
Protocollo Wireless M-Bus secondo EN13757-3, EN13757-4
Formato del frame B
Frequenza 868 MHz
Modalità C1
Crittografia AES-128 Counter Mode
Intervallo di trasmissione 96 s
LED
Rosso. Peso: proporzionale al consumo di energia e dipendente dal pro-
dotto dei rapporti di TA e di TV (frequenza max: 16Hz):
Modelli AV5
CT Peso (kWh per impulso)
≤ 7 0,001
> 7 ≤ 70,0 0,01
> 70 ≤ 700,0 0,1
> 700 1
Modelli AV2
CT Peso (kWh per impulso)
- 0,001
Generali
Grado di protezione frontale: IP50. Connessioni: IP20.
Isolamento (per 1 minuto) 4kV (tra ingresso di misura e porta Ethernet)
Categoria di misura Cat. III
Rigidità dielettrica 4000 VRMS per 1 minuto.
Connessioni a vite.
Sezione del cavo AV2: max. 16 mm2 ; min. 2.5 mm2 (tramite capocorda)
AV5: Max. 1.5 mm2
Montaggio a guida DIN.
Peso 400 g (imballo incluso).
800 g con antenna esterna (imballo incluso).
Caratteristiche ambientali
Temperatura di funzionamento da -25°C a +55°C (da -13°F a 131°F)
Temperatura di immagazzinamento da -30°C a +70°C (da -22°F a 158°F)
ITALIANO DEUTSCH FRANÇAIS ESPAÑOL DANSK
TECHNISCHE DATEN
Spannung: Modelle AV2, AV5
AV2 AV5
Anschlüsse Direkt Direkt
Nennspannung L-N
(Un min bis Un max)
133 bis 230 V 230 V
Nennspannung L-L
(Un min bis Un max)
230 bis 400 V 400 V
Spannungstoleranz -20, +15%
Überlastspannung Dauer: 1,15 Un max
Für 500 ms: 2 Un max
Eingangsimpedanz Siehe “Stromversorgung”
Frequenz 50 Hz
Strom AV2 AV5
Anschlüsse Direkt Mittels CT
CT-Verhältnis - 1 bis 2615
In -5 A
Ib 10 A -
Imin 0,5 A 0,05 A
Imax 65 A 10 A
Ist 0,04 A 0,01 A
Überlaststrom
Dauer
• 500 ms
• 10ms
65A @50Hz
-
1950A,@ 50Hz
10A @50Hz
200A, @ 50Hz
-
Eingangsimpedanz < 1,1 VA < 0,6 VA
Scheitelwertfaktor 4 3
Stromversorgung
Typ eigenversorgt
Leistungsafunahme AV2 3X, AV5: 1,8 W; 2,7 VA
AV2 1X: 0,8 W; 1,7 VA
Wireless M-Bus
Protokolle Wireless M-Bus gemäß EN13757-3, EN13757-4
Rahmenformat B
Frequenz 868 MHz
Modus C1
Verschlüsselung AES-128 Counter Mode
Übertragungsintervall 96 s
LED-Leuchten
Rot. Gewichtung: Proportional zum Energieverbrauch und abhängig vom
Produkt der Verhältnisse TA und TV (Max. Frequenz: 16 Hz):
Modelle AV5
CT Gewichtung (kWh pro Impuls)
≤ 7 0,001
> 7 ≤ 70,0 0,01
> 70 ≤ 700,0 0,1
> 700 1
Modelle AV2
CT Gewichtung (kWh pro Impuls)
- 0,001
Allgemeines
Schutzgrad IP50 (Vorderseite).
Schraubenklemmen: IP20.
Isolationsspannung
(für 1 Minute)
4kV (zwischen Messeingang und Ethernet-Port)
Messkategorie Kat. III
Durchschlagfestigkeit 4000 VRMS für 1 Minute.
Anschlüsse Schraubklemmen.
Kabel-querschnitt AV2: max. 16 mm2 ; min. 2.5 mm2 (mit Kabelschuh)
AV5: Max. 1.5 mm2
Montage DIN-Schiene.
Gewicht 400 g (incl. Verpackung).
800 g mit externer Antenne (incl. Verpackung).
Umgebungsbedingungen
Betriebstemperatur -25°C bis +55°C (-13°F bis 131°F)
Lagertemperatur -30°C bis +70°C (-22°F bis 158°F)
CARACTÉRISTIQUES D’ENTRÉE
Tension
AV2 AV5
Connection Directe Directe
Tension nominale L-N
(de Un min à Un max)
De 133 à 230 V 230 V
Tension nominale L-L
(de Un min à Un max)
De 230 à 400 V 400 V
Tolérance de tension -20, +15%
Surcharges de tension Continu: 1,15 Un max
Pour 500 ms: 2 Un max
Impédance d’entrée Voir “Alimentation”
Fréquence 50 Hz
Courant AV2 AV5
Connection Directe Via CT
Rapport CT - 1 à 2615
In -5 A
Ib 10 A -
Imin 0,5 A 0,05 A
Imax 65 A 10 A
Ist 0,04 A 0,01 A
Surcharges de courant
Continue
• 500 ms
• 10ms
65A @50Hz
-
1950A,@ 50Hz
10A @50Hz
200A, @ 50Hz
-
Impédance d’entrée < 1,1 VA < 0,6 VA
Facteur de crête 4 3
Alimentation
Type auto-alimentée
Consommation d’énergie AV2 3X, AV5: 1,8 W; 2,7 VA
AV2 1X: 0,8 W; 1,7 VA
Wireless M-Bus
Protocoles Wireless M-Bus selon EN13757-3, EN13757-4
Format de trame B
Fréquence 868 MHz
Mode C1
Cryptage AES-128 Counter Mode
Intervalle de transmission 96 s
LED
Rouge. Poids : proportionnel à la consommation d’énergie et selon le
produit du rapport CT et VT/PT (fréquence max: 16Hz):
Modèle AV5
CT Peso (kWh par impulsion)
≤ 7 0,001
> 7 ≤ 70,0 0,01
> 70 ≤ 700,0 0,1
> 700 1
Modèle AV2
CT Peso (kWh par impulsion)
- 0,001
Généralités
Indice de protection face avant: IP50. Terminaisons de vis:
IP20.
Isolation (pendant 1 minute) 4kV (entre l’entrée de mesure et le port
Ethernet)
Catégorie de mesure cat. III
Tension diélectrique 4000 VRMS pour 1 minute.
Connexions a vis.
Section de câbles AV2: max. 16 mm2 ; min. 2.5 mm2 (avec
raccord de câble)
AV5: Max. 1.5 mm2
Montage sur rail DIN
Poids 400 g (emballage inclus)
800 g avec antenne externe (emballage
inclus).
Spécifications environnementales
Température de fonctionnement -25°C à +55°C (13°F à 131°F)
Température de stockage -30°C à +70°C (22°F à 158°F)
ESPECIFICACIONES TÉCNICAS
Tensión
AV2 AV5
Conexion Directa Directa
Tensión nominal L-N (desde
Un min hasta Un max)
De 133 a 230 V 230 V
Tensión nominal L-L (desde
Un min hasta Un max)
De 230 a 400 V 400 V
Tolerancia de tensión -20, +15%
Protección contra
sobrecargas intensidad
Continua: 1,15 Un max
Durante 500 ms: 2 Un max
Impedancia de entrada Ver “Alimentación”
Frecuencia 50 Hz
Intensidad
AV2 AV5
Conexion Directa Mediante CT
Relación CT - de 1 a 2615
In -5 A
Ib 10 A -
Imin 0,5 A 0,05 A
Imax 65 A 10
Ist 0,04 A 0,01 A
Protección contra
sobrecargas de
tensión
Continua
• 500 ms
• 10ms
65A @50Hz
-
1950A,@ 50Hz
10A @50Hz
200A, @ 50Hz
-
Impedancia de
entrada
< 1,1 VA < 0,6 VA
Factor de cresta 4 3
Alimentación
Tipo Autoalimentación
Consumo de potencia AV2 3X, AV5: 1,8 W; 2,7 VA
AV2 1X: 0,8 W; 1,7 VA
Wireless M-Bus
Protocolos Wireless M-Bus según EN13757-3,
EN13757-4
Formato de marco B
Frecuencia 868 MHz
Modo C1
Encriptación AES-128 Counter Mode
Intervalo de transmisión 96 s
LED
Rojo. Peso: proporcional al consumo de energía y dependiente del CT y el
producto de relación VT/PT (frecuencia máxima:16 Hz):
Modelos AV5
CT Peso (kWh por pulso)
≤ 7 0,001
> 7 ≤ 70,0 0,01
> 70 ≤ 700,0 0,1
> 700 1
Modelos AV2
CT Peso (kWh por pulso)
- 0,001
General
Grado de protección panel frontal IP50. Conexiones: IP20.
Aislamiento (durante 1
minuto)
4kV (entre entrada de medición y puerto
Ethernet)
Categoría de medida Cat. III
Resistencia dieléctrica 4000 VRMS durante 1 minuto.
Conexiones a tornillo
Sección del cable AV2: max. 16 mm2 ; min. 2,5 mm2 (terminal
para embarrado)
AV5: Max. 1,5 mm2
Caja DIN
dimensiones (Al x An x P):
71x90x64,5mm.
Montaje carril DIN
Peso 400 g (embalaje incluido)
800 g con antena externa (embalaje incluido).
Especificaciones ambientales
Temperatura de trabajo
-25°C a +55°C (-13°F a 131°F)
Temperatura almacenamiento
-30°C a +70°C (-22°F a 158°F)
TEKNISKE SPECIFIKATIONER
Spænding
AV2 AV5
Tilslutning Direkte Direkte
Mærkespænding L-L
(fra Un min til Un max)
Fra 133 til 230 V 230 V
Mærkespænding L-N
(fra Un min til Un max)
Fra 230 til 400 V 400 V
Spændingstolerance -20, +15%
Spændingsoverbelastninger Fortsat: 1,15 Un max
For 500 ms: 2 Un max
Indgangsimpedans Se “Strømforsyning”
Frekvens 50 Hz
Strøm AV2 AV5
Tilslutning Direkte Via CT
Omsætningsforhold - fra 1 til 2615
In -5 A
Ib 10 A -
Imin 0.5 A 0.05 A
Imax 65 A 10 A
Ist 0.04 A 0.01 A
Overbelastning
Kontinuerlig
• 500 ms
• 10ms
65A @50Hz
-
1950A,@ 50Hz
10A @50Hz
200A, @ 50Hz
-
Inputimpedans < 1,1 VA < 0,6 VA
Crest faktor 4 3
Strømforsyning
Type egen strømforsyning
Forbrug AV2 3X, AV5: 1,8 W; 2,7 VA
AV2 1X: 0,8 W; 1,7 VA
Wireless M-Bus
Protokoller Wireless M-Bus ifølge EN13757-3, EN13757-4
Rammeformat B
Frekvens 868 MHz
Mode C1
Kryptering AES-128 Counter Mode
Transmissionsinterval 96 s
LED
Rød. Vægt: proportional med energiforsyningen og afhængigt af CT og VT/
PT produktforhold (16 Hz maksimumsfrekvens):
AV5
CT Vægt (kWh pr. puls)
≤ 7 0.001
> 7 ≤ 70.0 0.01
> 70 ≤ 700.0 0.1
> 700 1
AV2
CT Vægt (kWh pr. puls)
- 0.001
Generelt
Beskyttelsesgrad Front: IP50. Skrueklemmer: IP20.
Isolering (i 1 minut) 4kV (mellem målingsinput og Ethernet-port)
Målekategori Kat. III
Stødspænding 4000 VRMS i 1 minut
Forbindelser Skrueterminaler
Område for kabeltværsnit AV2: maks. 16 mm2 ; min. 2.5 mm2 (ved kabelsko)
AV5: maks. 1.5 mm2
Montering DIN-skinne
Vægt 400 g (inkl. emballage)
800 g med ekstern antenne (inkl. emballage).
Specifikationer for driftsomgivelserne
Driftstemperatur Fra -25 til +55 °C/fra -13 til +131 °F
Opbevaringstemperatur Fra -30 til +70 °C/fra -22 til +158 °F
CARLO GAVAZZI Controls SpA
via Saorze, 8 32100 Belluno (BL)Italy
www.gavazziautomaon.com
802191610-2019
  • Page 1 1
  • Page 2 2

Kamstrup EM24 DIN 1-phase, 3-phase & CT Guida utente

Tipo
Guida utente