6. Installation / Connection / Commissioning
The meter may only be installed by authorized trained personnel.
The meter must be installed in accordance with the regulations in force. Compliance with the
directives of the gas supply company or, in the case of Germany, of the DVGW Code of Practice
G600 (DVGW-TRGI), in the version currently valid in each case, is required for the installation of
gas meters.
Before installation please ensure:
– that the protective caps and/or plastic sheeting is or are removed,
– that the meter and accessories have been inspected for transport damage,
– that the accessories have been checked for completeness and
– that you only use seals made from approved materials.
Then install the meter
– gas-tight,
– in the driest possible environment and where it may be easily read (the meter must not come
into contact with surrounding masonry),
– only in ow direction (as marked by an arrow on the meter housing),
– free of mechanical stress, and make sure when inserting the seals that the seal faces are
clean and undamaged, and that the seals are concentrically aligned and do not protrude into
the pipe cross-section. For the compression of seals and the resulting tightening torques
for the connection elements, the seal or the screw manufacturers’ speci cations must be
observed.
– Only use the seals once!
Placing the system into operation
– Slowly fi ll the system until operating pressure is reached.
– The pressure rise may not exceed 15 mbar/s.
– Do not exceed the measuring range or the max. operating pressure even brie y!
– Pipe tests at pressures exceeding the maximum allowable operating pressure of the gas
meter are to be performed without the meter.
– Conduct a tightness test!
– Compliance with the speci ed operating and ambient conditions as indicated on the type
label is absolutely essential for safe operation of the meter and additional equipment.
– Recalibration is made in accordance with national Directives.
Installation instruction for tightening of screws at the
flange:
Tighten the screws diagonally in several stages until the desired torque is reached. It is very
important that the screws are tightened diagonally and gradually in order to prevent the ange
bending (both anges must be parallel to each other).
Elster GmbH
© Elster GmbH · All rights reserved · Subject to technical modication
When the gas meter is stored or installed outdoors, protect the site against rain.