UniPOS FD5301 Manuale del proprietario

Tipo
Manuale del proprietario
Ìîäóë
òèï FD5301
Ïàñïîðò 05-5301-02-17
1. Âúâåäåíèå
Ìîäóë FD5301 å ïðåäíàçíà÷åí çà ñúâìåñòíà ðàáîòà ñ ïîæàðîãàñèòåëíà öåíòðàëà FS5200E.
Óñòðîéñòâîòî ïîçâîëÿâà ÷àñò îò óïðàâëÿâàùèòå îðãàíè è èíäèêàòîðè íà öåíòðàëàòà, ñâúðçàíè ñ ïðîöåñà íà ãàñåíå, äà áúäàò äóáëèðàíè è èçíåñåíè
íà îïðåäåëåíî ðàçñòîÿíèå.
Oñíîâíèòå ôóíêöèè, êîèòî èçäåëèåòî óïðàâëÿâà äèñòàíöèîííî ñà:
- ðú÷íî çàäåéñòâàíå íà ãàñåíåòî;
- èçáîð íà ðåæèìèòå íà ðàáîòà íà öåíòðàëàòà - ðú÷íî-àâòîìàòè÷åí/ðú÷åí;
- çàáðàíà íà ãàñåíåòî;
- çàäúðæàíå íà ãàñåíåòî.
Äóáëèðàíè ñà èíäèêàòîðèòå çà:
- ïîæàð 2-ðà ñòåïåí;
- çàáðàíåíî ãàñåíå;
- ðú÷åí ðåæèì;
- ðú÷íî-àâòîìàòè÷åí ðåæèì.
Ôèã.1
Ïðîèçâîäèòåë: ÓíèÏÎÑ ÎÎÄ, Ð. Áúëãàðèÿ, 5800 Ïëåâåí, óë. Ñàí Ñòåôàíî 47, http://www.unipos-bg.com
2. Òåõíè÷åñêè õàðàêòåðèñòèêè
Èíäèêàöèÿ - ñâåòîäèîäíà
Òîêîçàõðàíâàíå - (28V DC) îò öåíòðàëàòà èëè àâòîíîìåí èçòî÷íèê
îòãîâàðÿù íà èçèñêâàíèÿòà íà EN54-4
Ãàáàðèòíè ðàçìåðè - (313x218x85)mm
Ìàñà - 1,125 kg
3. Ñúñòàâ è êîìïëåêòíîñò íà äîñòàâêàòà:
- Ìîäóë FD5301 - 1 áð.
- Ñåêðåòåí êëþ÷ - 2 áð.
- Ïàñïîðò - 1 áð.
- Òðàíñïîðòíà îïàêîâêà - 1 áð.
- Çàùèòåí ñòèêåð çà ôèêñèðàíå ïðåäïàçèòåëÿ - 1 áð.
íà áóòîí Ðú÷íî çàäåéñòâàíå
4. Óêàçàíèÿ èà èçèñêâàíèÿ ïî îõðàíà íà òðóäà
Ïåðñîíàëúò, èçâúðøâàù ìîíòàæà, ðåìîíòà è òåõíè÷åñêîòî îáñëóæâàíå íà ìîäóëà, å äëúæåí äà çíàå óñòðîéñòâîòî è ðàáîòàòà íà
àïàðàòóðàòà è îáùèòå èçèñêâàíèÿ ïî òåõíèêà íà áåçîïàñíîñò.
Ïîâðåäèòå òðÿáâà äà ñå îòñòðàíÿâàò ñëåä ðàçåäèíÿâàíå íà çàõðàíâàíåòî.
Ìîäóëúò ìîæå äà ñå ìîíòèðà â çàêðèòè ïîìåùåíèÿ ñ íîðìàëíà ïîæàðíà îïàñíîñò, ñúãëàñíî äåéñòâàùèòå ñòàíäàðòè è íîðìàòèâè.
1
2
3
4
5
67 8
9 11
10
13
12
Ôèã.2
5. Ìîíòàæ
5.1. Çàêðåïâàíå
Ìîäóëà ñå ðàçîïàêîâà îò òðàíñïîðòíàòà îïàêîâêà;
Ëèöåâèÿ êàïàê ñå îòêëþ÷âà. Îòêëþ÷âàíåòî ñå èçâúðøâà ñ ìîíåòà, êîÿòî ñå ïîñòàâÿ â
ïðîðåçà íà ïëàñòìàñîâàòà êëþ÷àëêà è ñå çàâúðòà íà 90 ãðàäóñà â ïîñîêà îáðàòíà íà
÷àñîâíèêîâàòà ñòðåëêà;
Ëèöåâèÿ êàïàê ñå îòâàðÿ;
Íà îïðåäåëåíîòî ìÿñòî ñå ìîíòèðàò äþáåëèòå çà çàêðåïâàíå íà óñòðîéñòâîòî;
Ìîäóëúò ñå çàêðåïâà êúì äþáåëèòå ïðåç òðèòå îòâîðà íà êóòèÿòà (ïîç.1, 6, 12, ôèã.2);
Îñâîáîäåíèòå ìåñòà íà ãîðíàòà ñòðàíà íà êóòèÿòà ñå ïðîáèâàò è ñå ïîäâåæäàò
êàáåëèòå.
5.2. Këåìîðåä
Âñè÷êè ïðèñúåäèíÿâàíèÿ ñå îñúùåñòâÿâàò ñ ïîìîùòà íà êëåìè (ïîç.8, ôèã.2),
ìîíòèðàíè íà ïå÷àòíàòà ïëàòêà (ôèã.3).
Manual ReleaseÈçõîä ñ êîíòðîë íà ñúñòîÿíèåòî íà ëèíèÿòà. Ñëóæè çà ïîäàâàíå íà
ñèãíàë êúì öåíòðàëàòà, îò ðú÷åí áóòîí, çà ñòàðòèðàíå íà ïðîöåäóðà çà ãàñåíå.
Mode SelectÈçõîä ñ êîíòðîë íà ñúñòîÿíèåòî íà ëèíèÿòà. Ñëóæè çà ïîäàâàíå íà
ñèãíàë êúì öåíòðàëàòà, îò ïðåâêëþ÷âàòåë, çà ðåæèìà íà ðàáîòà. Ðåæèìèòå ñà Ðú÷íî-
Àâòîìàòè÷åí è Ðú÷åí.
HoldÈçõîä ñ êîíòðîë íà ñúñòîÿíèåòî íà ëèíèÿòà. Ñëóæè çà ïîäàâàíå íà ñèãíàë êúì
öåíòðàëàòà, îò ðú÷åí áóòîí èëè óïðàâëÿåì êîíòàêò, çà çàäúðæàíå (îòëàãàíå) íà
ïðîöåäóðà çà ãàñåíå.
• “On/Off Exting” – Èçõîä ñ êîíòðîë íà ñúñòîÿíèåòî íà ëèíèÿòà. Ñëóæè çà ïîäàâàíå íà
ñèãíàë êúì öåíòðàëàòà, îò ïðåâêëþ÷âàòåë, çà çàáðàíà íà ïðîöåäóðà çà ãàñåíå.
Rele FireÊëåìè çà âðúçêà ñ “Rel 2ST” îò öåíòðàëàòà (èçõîä íà öåíòðàëàòà, ðåëååí,
áåçïîòåíöèàëåí, ñúñòîÿíèåòî íà ëèíèÿòà íå ñå ñëåäè. Ñëóæè çà óïðàâëåíèå íà
óñòðîéñòâà ïðè ñúñòîÿíèå Ïîæàð Âòîðà ñòåïåí íà öåíòðàëàòà).
+28V-–Êëåìè çà çàõðàíâàíå íà èçäåëèåòî îò öåíòðàëàòà èëè îò âúíøåí èçòî÷íèê.
OK1Êëåìè íà ëèíèÿòà çà óïðàâëåíèå íà èíäèêàöèÿòà ïðè ñðàáîòèë Èçõîä îòâîðåí
êîëåêòîð â öåíòðàëàòà /êîãàòî å àêòèâåí ïîäàâà ïîòåíöèàë GND, à ïðè íåàêòèâåí èìà
ïîòåíöèàë +28V ïðåç ðåçèñòîð 47kÙ/0.125W/. Âõîäúò å àêòèâåí, êîãàòî öåíòðàëàòà å
ðåãèñòðèðàëà èçòè÷àíå íà ãàñèòåëåí ðåàãåíò.
OK2Êëåìè íà ëèíèÿòà çà óïðàâëåíèå íà èíäèêàöèÿòà Èçõîä îòâîðåí êîëåêòîð â
öåíòðàëàòà /êîãàòî å àêòèâåí ïîäàâà ïîòåíöèàë GND, à ïðè íåàêòèâåí èìà ïîòåíöèàë
+28V ïðåç ðåçèñòîð 47kÙ/0.125W/. Âõîäúò å àêòèâåí, êîãàòî öåíòðàëàòà å â ðåæèì
Çàáðàíà Ãàñåíå.
OK3Êëåìè íà ëèíèÿòà çà óïðàâëåíèå íà èíäèêàöèÿòà Èçõîä îòâîðåí êîëåêòîð â
öåíòðàëàòà /êîãàòî å àêòèâåí ïîäàâà ïîòåíöèàë GND, à ïðè íåàêòèâåí èìà ïîòåíöèàë
+28V ïðåç ðåçèñòîð 1kÙ/0.125W/. Âõîäúò å àêòèâåí, êîãàòî öåíòðàëàòà å â Ðú÷åí ðåæèì.
On/Off Mode Manual
+ 28V - Exting Select HOLD Release
B A D C
O K1
O K2
O K3
Rele
Fire
Ôèã.3
Ñõåìàòà íà ñâúðçâàíå íà ìîäóë FD5301 êúì FS5200E å äàäåíà íà ôèã.5.
 öåíòðàëàòà FS5200E ñå ïðîìåíÿ àêòèâíîñòòà íà âõîäà Holdâ ìåíþ Ñèñòåìíè ôóíêöèè/Íàñòðîéêà/Âõîä-èçõîäè/Âõîä Hold”, îò Îòâîðåí
â Çàòâîðåí”.
Çàáåëåæêà: Êîíòàêòèòå íà ðåëå Rel 2STâ ãàñèòåëíàòà öåíòðàëà òðÿáâà äà áúäàò êîíôèãóðèðàíè ÷ðåç äæúìïåðà êàòî íîðìàëíî îòâîðåíè”.
6. Èíäèêàöèÿ
7.2. Äåéñòâèÿ ñ áóòîíèòå ïðè ïîæàð:
Çàáðàíà íà ãàñåíåòî - Çàâúðòà ñå ñåêðåòíèÿ
êëþ÷ â ïîçèöèÿ Çàáðàíà ãàñåíå. Ñâåòâà
èíäèêàòîðà (ïîç.5, ôèã.4);
Çàäúðæàíå íà ãàñåíåòî - Íàòèñêà ñå áóòîí
“HOLD”, êîåòî âîäè äî óâåëè÷àâàíå âðåìåòî çà
åâàêóàöèÿ (ïîç.1, ôèã.4);
Ïðèíóäèòåëíî çàäåéñòâàíå íà ãàñåíåòî
- êúñà ñå çàùèòíèÿ ñòèêåð;
- ïëúçãà ñå çàùèòíàòà ïëàíêà äî îòêðèâàíå
íà áóòîí “Extinguish”;
- íàòèñêà ñå áóòîíà, ñ êîåòî ñå çàäåéñòâà
ãàñåíåòî (ïîç.9, ôèã.4).
8. Óñëîâèÿ çà åêñïëîàòàöèÿ, ñúõðàíåíèå è
òðàíñïîðò
8.1. Åêñïëîàòàöèÿ è ñúõðàíåíèå
Ìîäóëúò ñå èçïîëçâà è ñúõðàíÿâà â
çàòâîðåíè ïîìåùåíèÿ ïðè ñëåäíèòå ãðàíè÷íè
óñëîâèÿ:
Òåìïåðàòóðà
î î
- íà ñúõðàíåíèå îò 5 Ñ äî 35 Ñ
î î
- íà òðàíñïîðò îò ìèíóñ 10 Ñ äî 50 Ñ
î î
- ðàáîòíà îò ìèíóñ 5 Ñ äî 40 Ñ
Îòíîñèòåëíà âëàæíîñò
- íà ñúõðàíåíèå - äî 80%
- ðàáîòíà - äî 93%
8.2. Òðàíñïîðò
Ìîäóëúò ñå òðàíñïîðòèðà â çàêðèòè
òðàíñïîðòíè ñðåäñòâà, âúâ ôàáðè÷íà îïàêîâêà è
ïðè ãîðåïîñî÷åíèòå àòìîñôåðíè óñëîâèÿ.
9. Ãàðàíöèîííè çàäúëæåíèÿ
Ôèðìàòà - ïðî èçâîäèòåë ãàðàíòèðà
ñúîòâåòñòâèå íà èçäåëèåòî ñ ÁÄÑ EN 54-2:1997,
À1:2000, ÁÄÑ EN 54-4:1997, À1:2002, À2:2006 è
ÁÄÑ EN 12094-1: 2003.
Ãàðàíöèîííèÿò ñðîê å 24 ìåñåöà îò äàòàòà íà
ïðîäàæáàòà, ïðè óñëîâèå ÷å:
- ñà ñïàçåíè óñëîâèÿòà íà ñúõðàíåíèå è
òðàíñïîðò;
- ïóñêúò ñå èçâúðøâà îò îòîðèçèðàíè îò
ôèðìàòà - ïðîèçâîäèòåë ëèöà;
- ñå ñúáëþäàâàò èçèñêâàíèÿòà çà åêñïëîàòàöèÿ,
óêàçàíè â íàñòîÿùèÿ ïàñïîðò.
Ïðîèçâîäèòåë: ÓíèÏÎÑ ÎÎÄ, Ð. Áúëãàðèÿ, 5800 Ïëåâåí, óë. Ñàí Ñòåôàíî 47, http://www.unipos-bg.com
Èíäèêàòîð Çàõðàíâàíå” - ïîñòîÿííà çåëåíà ñâåòëèíà êîãàòî ìîäóëà å çàõðàíåí
(ïîç.8, ôèã.4)
Îáù èíäèêàòîð Ïîæàð Âòîðà ñòåïåí” - ïîñòîÿííà ÷åðâåíà ñâåòëèíà (ïîç.6, ôèã.4)
Èíäèêàòîð Ðú÷åí ðåæèì - ïîñòîÿííà æúëòà ñâåòëèíà (ïîç.4, ôèã.4)
Èíäèêàòîð Ðú÷íî-Àâòîìàòè÷åí ðåæèì - ïîñòîÿííà æúëòà ñâåòëèíà (ïîç.3, ôèã.4)
Èíäèêàòîð Çàáðàíà ãàñåíå - ïîñòîÿííà æúëòà ñâåòëèíà (ïîç.5, ôèã.4)
Èíäèêàòîð Ïîâðåäà íèñêî íàëÿãàíå - ïîñòîÿííà æúëòà ñâåòëèíà (ïîç.7, ôèã.4)
1
23 4 5 6
7
8
9
Ôèã.4
Exting Select Release
A B C D
On/Off HOLD Mode Manual
GND
Rel
1ST
Rel
2ST
OK1
+28V
OK2
+28V
OK3
+28V
Rele
Fire
O K1
O K2
O K3
On/Off Mode Manual
+ 28V - Exting Select HOLD Release
F D 5301
FS5200E
B A D C
1,5kÙÁóòîí çà ðú÷íî àêòèâèðàíå íà ãàñåíåòî
Ïðåâêëþ÷âàòåë ðåæèì ðú÷åí/ðú÷íî-àâòîìàòè÷åí
Áóòîí çà çàäúðæàíå íà ãàñåíåòî
Ïðåâêëþ÷âàòåë çà çàáðàíà íà ãàñåíåòî
7. Ðàáîòà ñ áóòîíèòå
7.1. Èçáîð íà ðåæèì:
Ðú÷íî àâòîìàòè÷åí – Çàâúðòà ñå ñåêðåòíèÿ êëþ÷ â ïîçèöèÿ Ðú÷íî-àâòîìàòè÷åí ðåæèì”. Ñâåòâà èíäèêàòîðà (ïîç.3, ôèã4);
• Ðú÷åí ðåæèì - Çàâúðòà ñå ñåêðåòíèÿ êëþ÷ â ïîçèöèÿ Ðú÷åí ðåæèì. Ñâåòâà èíäèêàòîðà (ïîç.4, ôèã.4);
Ôèã.5
Module
type FD5301
Instruction manual 05-5301-02-17
1.Introduction
Module FD5301 is designed to operate together with Fire Extinguishing Control Panel FS5200E.
The device allows remote access on a part of the panel controlling components and indicators, related with the extinguishing process.
The remotely controlled panel basic functions are:
- Manual activation of Extinguishing;
- Selecting the Control Panel Modes of operation Manual/Auto mode or only Manual mode;
- Disable Extinguishing;
- Hold Extinguishing.
The following indicators are duplex controlled:
- Fire Condition 2nd Stage;
- Disable Extinguishing;
- Gas Released;
- Manual Mode;
- Manual/Auto Mode.
Fig.1
Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com
2. Òechnical Data
Indication - LED
Power Supply - 28 V DC of the Control Panel or an autonomous
power supply, compatible with the EN54-4 requirements
Dimensions - (313õ218õ85) mm
Weight - 1,125 kg
3. Complete Set
- Module FD5301 - 1 pc.
- Keyswitch - 2 pcs.
- Instruction Manual - 1 pc.
- Transport package - 1 pc.
- Safety sticker for fixing the - 3 pcs.
fuse of button Manual Release
4. Labour Protection Requirements
Personnel, involved in installation and maintenance of the module must know the structure and operation of the equipment and the basic safaty
requirements.
Faults must be removed after disconnecting the power supply.
The module can be installed in premises with a normal fire hazard under the current standards and regulations.
1
2
3
4
5
67 8
9 11
10
13
12
Fig.2
5. Installation and preparing for operation
5.1. Fixing the module
• Unpack the device;
Open the module after unlocking.To unlock use a coin, place the coin into the slot of the
plastic door lock and rotate 90 counterclockwise;
Mount the dowels for fixing on the proper place;
Fix the module to the dowels through the three openings of the box (pos.1, 6, 12, fig.2);
Bore the holes at the top of the box, on the vacant places and pass the cables.
5.2. Terminal Bus
All signal and power cables are connected using the terminals (pos.8, fig.2), mounted on
the printed-circuit board (fig.3).
Manual Release” – The output is used for manual activation of the extinguishing
process in the control panel.
Mode SelectThe output is used for selection of the operating mode in the Control
Panel.
HoldThe output is used to hold, (delay) the extinguishing process in the Control Panel.
On/Off Exting” – The output is used for releasing a signal to the Control Panel from a
switcher for disabeling the extinguishing procces;
Rele Fire” – Terminals for connection withRel 2STof the Control panel (output of the
panel, relay, potential-free, the line status is not controlled. It is used to control the devices
when the Control Panel has entered Fire Condition 2nd Stage).
+28V-Terminals for power supplying the device from the control panel or external power
supply;
OK1Terminals for control of the FD5301 indication, triggered on activated Control
Panel open collector /GND on active panel open collector, +28V on inactive panel open
collector/. The input is active when the Control panel has registered a leak of extinguishing
agent.
OK2Terminals for control of the FD5301 indication, triggered on activated Control
Panel open collector /GND on active panel open collector, +28V on inactive panel open
collector/. The input is active when the Control Panel has Disabled Extinguishing Mode.
OK3Terminals for control of the FD5301 indication, triggered on activated Control
Panel open collector /GND on active panel open collector, +28V on inactive panel open
collector/. The input is active, when the Control Panel is in Manual Mode.
On/Off Mode Manual
+ 28V - Exting Select HOLD Release
B A D C
O K1
O K2
O K3
Rele
Fire
Fig.3
Manufacturer: UniPOS Ltd., 47 San Stefano Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com
The scheme of connecting module FD5301 to FS5200E is given in fig.5.
Note1: From the Control Panel FS5200E menu System Functions/SetUp/Input-outputs/Input Holdthe activity of the input Holdmust be changed from
Îpento Closed”.
Note2: Contacts of the relay "Rel 2ST" in the extinguishing panel must be configured by the jumper as "normally open''.
6. Indication
7.2. Using the buttons in case of Fire Condition:
Disable Extinguishing - Turns the secret
keyswitch in position “Disable Extinguishing. The LED
is on (pos.5, fig.4);
• Hold Extinguishingpress buttonHOLD”. The
evacuation time is extended (pos.1, fig.4);
Forced Extinguishing activation:
- tear-off the protective sticker;
- slide the protective plate untill discovering
button Extinguish”;
- press the button to activate the
extinguishing (pos.9, fig.4).
8. Conditions of transport, storage and operation
8.1. Operation and Storage
The module is to be used and kept in closed premises
under the following boundary conditions:
Temperature range
î î
-storage temperature range 5 Ñ to 35 Ñ
î î
-transport temperature range minus 10 Ñ to 50 Ñ
î î
-operating temperature range minus 5 Ñ to 40 Ñ
Relative humidity resistance
- storage up to 80%
- operation up to 93%
8.2. Transport
The module is to be transported in closed vehicles, in
factory packaging and at the mentioned above
wheather conditions.
9. Warranty
The manufacturer guarantees that the device is in
compliance with EN 54-2:1997, À1:2000, BDS EN 54-
4:1997, À1:2002, À2:2006 and EN 12094-1: 2003.
The warrant period is 24 months from the date of the
purchase providing that:
- The conditions of the storage and transport are
observed;
- Start-up is gone by authorized by the company -
manufacturer person;
- The operating requirements of the Instruction
manual here in have been observed.
IndicatorPower supply” - Ìîdule is power supplied (pos.8, fig.4)
Common IndicatorFire Condition 2nd Stage ” – continuous red light (pos.6, fig.4)
IndicatorManual Mode” – continuous yellow light (pos.4, fig.4)
IndicatorManual-Auto Mode” – continuous yellow light (pos.3, fig.4)
IndicatorDisable Extinguishing” – continuous yellow light (pos.5, fig.4)
IndicatorLow Pressure” – fault condition Low pressure into the Extinguishing
installation - continuous yellow light (pos.7, fig.4)
1
23 4 5 6
7
8
9
Fig.4
Exting Select Release
A B C D
On/Off HOLD Mode Manual
GND
Rel
1ST
Rel
2ST
OK1
+28V
OK2
+28V
OK3
+28V
Rele
Fire
O K1
O K2
O K3
On/Off Mode Manual
+ 28V - Exting Select HOLD Release
F D 5301
FS5200E
B A D C
1,5kÙButton for activate the extinguishing
Switcher Manual/Auto mode
Button for hold extinguishing
Circuit changer for disable extinguishing
7. Using the buttons
7.1. Mode selection:
Manua/Auto Turns the secret keyswitch in position Manual/Auto mode”. The LED is on (pos.3, fig.4);
• Manual Mode - Turns the secret keyswitch in position Manual”. The LED is on (pos.4, fig.4).
Fig.5
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

UniPOS FD5301 Manuale del proprietario

Tipo
Manuale del proprietario

in altre lingue