BEL LDC240 Guida d'installazione

Tipo
Guida d'installazione
LDC240-12
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.5 1.2 A; OUTPUT: 12 VDC, 15 A
LDC240-12P
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.5 1.2 A;
OUTPUT: 12 VDC, 15 A + ORing Circuit
LDC240-24
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.6 0.9 A; OUTPUT: 24 VDC, 10 A
LDC240-24P
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.6 0.9 A;
OUTPUT: 24 VDC, 10 A + ORing Circuit
LDC240-48
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.6 0.9 A; OUTPUT: 48 VDC, 5 A
LDC240-48P
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.6 0.9 A;
OUTPUT: 48 VDC, 5 A + ORing Circuit
LDC240-72
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.6 0.9 A; OUTPUT: 72 VDC, 3.3 A
LDC240-72P
INPUT: 120 240 VAC, 2.4 - 1.2 A, 50 - 60 Hz (UL certified) or 110 - 345 VDC, 2.6 0.9 A;
OUTPUT: 72 VDC, 3.3 A + ORing Circuit
MAIN
FEATURES
High efficiency
Ultra compact size
Active PFC for optimal efficiency
Overload 150%
Up to 70°C operating temperature with no derating
Constant current or Hiccup mode limitation, user settable
Wide range of output voltage
Easy parallelable for power increase
VOR DER INSTALLATION BITTE FOLGENDE
SICHERHEITSHINWEISE BEACHTEN!
LEGGERE ATTENTAMENTE PRIMA
DELL’INSTALLAZIONE!
A LIRE ATTENTIVEMENT AVANT
L’INSTALLATION!
Lesen Sie dieses Dokument vor der
Inbetriebnahme sorgfältig durch und bewahren Sie
es zum späteren Nachschlagen auf.
Die Nichtbeachtung dieser Anweisungen kann die
Funktion und Sicherheit der Geräte beeinträchtigen
und birgt Gefahren für Personen und Eigentum.
Die Geräte müssen von qualifiziertem Personal
unter Einhaltung der geltenden Normen und
Vorschriften installiert, betrieben, gewartet und
instand gehalten werden.
Öffnen Sie das Gerät nicht, es enthält keine
austauschbaren Komponenten, das Auslösen der
internen Sicherung (falls vorhanden) ist stets auf
tiefergehende Fehler im Schaltkreis zurück zu
führen.
Reparieren oder modifizieren Sie das Gerät nicht.
Sollte während des Betriebs eine Fehlfunktion oder
ein Defekt auftreten, schicken Sie das Gerät zur
Überprüfung ins Werk.
Bel übernimmt keine Haftung für die Folgen, die
sich aus dem Einsatz dieses Gerätes ergeben.
Prima dell’installazione, leggere attentamente
questo documento istruzioni e conservarle per
future consultazioni.
L’inosservanza delle presenti istruzioni può
compromettere le caratteristiche e la
sicurezza dell’apparecchio e causare pericolo
per le persone e le cose.
Il prodotto deve essere installato, utilizzato e
riparato da personale qualificato e nel rispetto
delle normative vigenti.
Non aprire il prodotto, esso non contiene
componenti sostituibili, il guasto del fusibile
interno (se previsto) è causato da un guasto
interno.
Non tentare di riparare o modificare il
prodotto, se durante il funzionamento si
verificano guasti o anomalie, inviarlo al
produttore per il controllo.
Bel non si assume nessuna responsabilità per
qualunque conseguenza derivante dall’uso di
questo materiale.
Lire ces instructions avant l'installation,
conserver ce manuel pour référence future.
Défaut de se conformer à ces instructions
peut affecter les caractéristiques et la sécurité
du dispositif, et causer du danger aux
personnes ou aux biens.
Les produits doivent être installés, exploités
et entretenus par du personnel qualifié et en
conformité avec les règlements.
N'ouvrez pas le produit, il ne contient aucune
pièce réparable, le déclenchement du fusible
interne (le cas échéant) est causé par un
défaut interne.
Ne pas essayer de réparer ou modifier le
produit ; si des défaillances se produisent
pendant le fonctionnement, retourner le
produit au fabricant pour inspection.
Bel n'assume aucune responsabilité des
conséquences éventuelles découlant de
l'utilisation des produits.
ACHTUNG
ATTENZIONE
AVVERTISSEMENT
GEFAHR VON VERBRENNUNGEN,
EXPLOSIONEN, FEUER, STROMSCHLAG,
PERSONENSCHÄDEN.
Führen Sie niemals Arbeiten an
spannungsführenden Teilen durch! Gefahr von
tödlichen Verletzungen! Das Gehäuse des Gerätes
kann heiß sein, lassen Sie Zeit zum Abkühlen des
Gerätes, bevor Sie es berühren.
Lassen Sie keine Flüssigkeiten oder Fremdkörper
in die Geräte eindringen.
Um Überschläge zu vermeiden, schließen Sie das
Gerät nicht an oder trennen Sie es nicht ohne
vorher die Eingangsspannung abgeschaltet zu
haben, und warten Sie die Entladung der internen
Kondensatoren ab (mindestens 1 Minute).
RISCHIO USTIONI, ESPLOSIONE,
INCENDIO, SCOSSA, LESIONI GRAVI.
Non effettuare mai operazioni sulle parti sotto
tensione! Pericolo di lesioni letali!
Il contenitore può scottare, lasciar quindi
raffreddare il dispositivo prima di toccarlo.
Non far entrare liquidi o oggetti estranei nel
dispositivo.
Per evitare scintille, non collegare o scollegare
l'apparecchiatura prima di avere tolto tensione
di ingresso e prima che sia avvenuta la
scarica dei condensatori interni (min. 1
minuto).
RISQUE DE BRULURES, EXPLOSION,
INCENDIE, ELECTROCUTION, DOMMAGE
AUX PERSONNES.
Ne jamais effectuer des opérations sur les
parties sous tension! Danger de mort!
Le boîtier peut produire des brûlures, le
laisser refroidir avant de toucher l'appareil. Ne
faire pas pénétrer des liquides ou des corps
étrangers dans l'appareil.
Pour éviter des étincelles, ne pas connecter
ou déconnecter l'équipement jusqu'à ce que
la tension d'entrée a été supprimée et avant
qu'il n'ait eut lieu la décharge des
condensateurs internes (minimum 1 minute).
BESTIMMUNGSGEMÄßER BETRIEB
USO PREVISTO
UTILISATION
Es handelt sich um galvanisch getrennte Geräte,
die für SELV- und PELV-Anwendungen geeignet
sind und für die Montage auf DIN-Schienen und die
Installation in einem Schutzgehäuse konzipiert
sind. Sie sind für den allgemeinen Gebrauch wie
z.B. in industriellen Steuer-, Kommunikations- und
Automatisierung-Anwendungen vorgesehen.
Verwenden Sie diese Geräte nicht in
Anwendungen, bei denen eine Fehlfunktion zu
Verletzungen oder zum Tod führen kann.
I dispositivi sono isolati, adatti per applicazioni
SELV e PELV, sono dotati di aggancio per il
montaggio su guida DIN all’interno di quadri
elettrici o contenitori di protezione, per
l’utilizzo con controllori industriali, unità di
comunicazione o apparecchi di misura.
Non utilizzare in applicazioni in cui un
eventuale guasto può comportare rischio di
lesioni o di morte.
Les produits sont isolés, appropriés pour les
circuits TBTS et TBTP et sont équipés d'un
crochet pour montage sur rail DIN dans des
armoires ou conteneurs de protection, pour
utilisation avec les contrôleurs industriels, des
modules de communication ou des unités de
mesure.
Ne pas utiliser ces dispositifs dans une
application où un dysfonctionnement pourrait
entraîner le risque des blessures ou de mort.
UMGEBUNGSBEDINGUNGEN
CARATTERISTICHE AMBIENTALI
CARACTÉRISTIQUES ENVIRONMENTALES
Installation in einer Umgebung mit
Verschmutzungsgrad 2.
Nicht in nassen Bereichen oder unter Feuchtigkeit
verwenden.
Das Gerät und die zugehörigen Batterien sind
entsprechend den lokalen Vorschriften zu recyceln
bzw. zu entsorgen.
Usare in ambienti con Grado di Inquinamento
2.
Non far funzionare l'apparecchio in un
ambiente umido o soggetto a formazione di
condensa. Riciclare il prodotto e le batterie
collegate, nel rispetto delle normative locali
vigenti.
Utiliser les produits dans des environnements
avec degré de pollution 2.
Ne pas employer l'appareil dans un
environnement humide ou soumis à la
condensation. Recycler les produits et les
batteries, conformément à la réglementation
locale.
Manufacturer
Bel Fuse Inc.
300 Executive Drive, Suite 300
West Orange, NJ 07052
USA
Asia-Pacific
+86 755 2988 5888
Europe, Middle East
+353 61 49 8941
North America
+1 866 513 2839
belfuse.com/power-solutions
© 2023 Bel Fuse Inc.
BCM.00406_AE
USER INSTRUCTIONS
1) DESCRIPTION
DIN rail mountable primary switched-mode power supply with 90 - 264 VAC (110 - 345 VDC) input, suitable for single phase mains line and DC line.
2) INSTALLATION
Use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where the device
is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).
The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping.
The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce
the load (see Fig.8)
3) CONNECTIONS
The device is equipped with screw terminal blocks. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input power and
waited for internal capacitors discharge (minimum 1 minute)
In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of:
60°C for ambient up to 45°C
75°C for ambient up to 60°C
90°C for ambient up to 70°C
Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5)
4) INPUT PROTECTION
The device input is provided with varistors against overvoltage. Input is provided with internal fuses 6.3AT /250 VAC, thus an external short circuit / overcurrent protection
must be provided by the end user (see Fig.6).
For operation on a single-phase system, a protection fuse on the phase must be provided.
Surge protection: it is strongly recommended to provide external surge arresters (SPD) according to local regulations.
5) AC INPUT CONNECTION
The device can be connected to single phase AC line with rated Vin 120 - 240 VAC (see Fig.7). Please connect the PE first.
6) DC INPUT CONNECTION
Connect L terminal to (+) positive pole, N terminal to (-) negative pole and terminal to GND. Rated voltage 110 345 VDC. The device is also suitable for photovoltaic
or wind turbine applications (see Fig.7).
7) OUTPUT CONNECTION
The device is suitable for SELV and PELV circuitry. Pay attention to LDC240-72 and LDC240-72P is not SELV.
Vout can be adjusted with a potentiometer to a wide range (see Fig.1)
Check Vout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed the nominal
power.
8) PARALLEL CONNECTION AND REDUNDANCY
Power supplies can be connected in parallel to increase power. For paralleling for power set the Ilim jumper to C.C. algorithm.
Vout must be set uniformly (±100 mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution.
Models with “P” suffix have an integrated ORing circuit.
For redundant connection, use the Models “P” or an external isolating device must be used (see accessory device).
9) OUTPUT PROTECTION
The device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT).
OL and SC: are controlled by a hiccup mode or a constant current (C.C.) mode protection with the following behaviour.
The Hiccup mode or C.C. mode are selectable with Jumper (see Fig.1)
OL behaviour in hiccup mode: Max. OL = 1.5 x In the output voltage remains constant at nominal voltage for 5s and after that time the device starts an ON/OFF cycle.
OL behaviour in C.C. mode: the maximum output current is limited at 1.1 x In if the load resistance is further decreased the output voltage starts to drop.
SC behaviour in hiccup mode: the device supplies 1.5 x In for 5 s, after that time it switches off for 10 s. The ON/OFF cycle is repeated continuously.
SC behaviour in C.C. mode: the device supplies 1.1 x In continuously into the short circuit without switching off
Output OV circuit protection: the output is protected against potential OV due to internal malfunction or coming from the load for
Vout Vnom x 1.2 1.3, depending on the model.
OT protection: turns off the device if the internal temperature exceeds a safe limit.
The device restarts automatically after cooling down. To recover to normal operation, reduce air temperature surrounding the power supply, increase cooling or reduce
load (see Fig.8).
10) FEEDING DC MOTORS
It is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it can trigger
overcurrent protection (see accessory device). For these applications the C.C. (Constant Current) mode of current limitation is recommended.
NOTE: motors can generate high conducted noise on the DC line. Therefore, it is not recommended to feed on the same line motors and equipment sensitive to noise.
11) OPERATION WITH BATTERY
When a battery is connected in parallel to the Output for backup purposes; the LDC240 must be set on C.C. mode to avoid battery over-charging (see accessory device).
Manufacturer
Bel Fuse Inc.
300 Executive Drive, Suite 300
West Orange, NJ 07052
USA
Asia-Pacific
+86 755 2988 5888
Europe, Middle East
+353 61 49 8941
North America
+1 866 513 2839
belfuse.com/power-solutions
© 2023 Bel Fuse Inc.
BCM.00406_AE
FIG.1 - CONNECTIONS
FIG.2 - DIMENSIONS
FIG.3 - DISTANCES
Just for reference
(1) AC/DC input
(2) DC output (load)
(3) Diagnostic Output
(dry contact, NC output OK)
(4) Green LED: Output OK
(5) Red LED: Overload
(6) Output voltage adjustment
(7) Selectable limitation mode
(Hiccup mode, C.C. mode)
Input AC Line:
L = Line
N = Neutral
= Earth ground
Input DC Line:
L = + Positive DC
N = - Negative DC
= Earth ground
Output:
+ = Positive DC
- = Negative DC
Dry contact = NC
Dimension
W
D
H
mm (inc)
40 (1.57)
110 (4.33)
115 (4.52)
Distance
A
B
mm (inc)
20 (0.8)
100 (3.9)
FIG.4 - MOUNTING / DISMOUNTING INSTRUCTIONS
For DIN rail fastening according to IEC 60715 TH35-7.5(-15)
Mounting as shown in figure, with input terminals on lower side, with suitable cooling and maintaining a proper distance between adjacent devices as specified in the
Installation Instruction of each family.
MOUNTING:
1. Tilt the unit slightly backwards.
2. Fit the unit over the top edge of the rail.
3. Slide it downward until it hits the stop.
4. Press against the bottom for locking.
1
2
3
4
DISMOUNTING:
1. Pull down the slide clamp lever
2. Tilt the unit upward
3. Unhook the unit from the rail
1 & 2
3
Manufacturer
Bel Fuse Inc.
300 Executive Drive, Suite 300
West Orange, NJ 07052
USA
Asia-Pacific
+86 755 2988 5888
Europe, Middle East
+353 61 49 8941
North America
+1 866 513 2839
belfuse.com/power-solutions
© 2023 Bel Fuse Inc.
BCM.00406_AE
FIG.5 - RECOMMENDED CONNECTING CABLE
Recommended Tightening torque
0.5 - 0.6 Nm
4.42 - 5.30 lbf in
Solid: 2.5 mm² / 12 AWG
Stranded:1.5 mm² / 12 AWG
L: 6.0 - 7.5 mm / 0.24 - 0.30 in
FIG.6 - INPUT PROTECTION
Fuse MCB 10 A C curve.
For USA and Canada, use the fuse type closest to the European equivalent type.
Surge protection: it is strongly recommended to provide external surge arresters (SPD) according to local regulations.
FIG.7 - INPUT CONNECTIONS
AC LINE
DC LINE
FIG.8 - ENVIRONMENT
OPERATING TEMPERATURE
DERATING
- 40°C to + 70°C
5 - 95% r.H. non condensing
UL Certified up to 70°C
No derating
NOTES:
Data may change without prior notice in order to improve the product.
Please refer to the latest version of LDC240 Series Datasheet or LDC240 Series Installation Instruction on our website:
belfuse.com/power-solutions
ACCESSORIES
LDX-D20 20 A Active ORing controller
LDX-D50 50 A Active ORing controller
LDX-U20 20 A High performance DC UPS
LDX-B20 150J Buffer Module
LDX-C120 Battery charger and DC UPS Module
LDX-L30 Sealed Lead acid Battery pack
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

BEL LDC240 Guida d'installazione

Tipo
Guida d'installazione