CARLO GAVAZZI CPA3001LS1X Guida d'installazione

Tipo
Guida d'installazione

Questo manuale è adatto anche per

CARLO GAVAZZI Controls SpA
via Safforze, 8 - 32100 Belluno (BL) Italy
www.gavazziautomation.com
info: +39 0437 355811 / fax: +39 0437 355880
CPA050 CPA300

Code 8021885
CPA is a family of power analyzers for ac 1-phase or dc
      

The comprehensive set of measured variables allow this
       

Electrical specifi cation
System type 1-phase ac/dc
Power supply 9 to 30 Vdc
Consumption <1.3 W
Rated current
CPA050 50 Aac, 50 Adc
CPA300 300 Aac, 400 Adc
Rated voltage 800 Vac,1000 Vdc
Frequency 1-400 Hz or dc
Accuracy
Active energy +/- 1% RDG
Current/voltage <0.5% F.S
Environmental specifi cation
Operating temperature -15°C to 65°C
Storage temperature -40°C to 85°C
Relative humidity from 0 to 90% non-condensing
Environment Indoor use only
RS485 specifi cation
Protocol MODBUS RTU
Addresses 1-247
Data format 1 start bit, 8 data bit, NO/ODD/
EVEN parity (default NO parity)
Baud-rate 1200, 2400,4800, 9600, 19200,
38400, 57600, 115200 bps
Response delay 1-1000 ms
General specifi cation
Cable cross section area 1.5 mm
2
Screw tightening torque Max 0.25 Nm
Protection degree IP 20


Caratteristiche elettriche
Sistema Monofase ca/cc
Alimentazione da 9 a 30 Vcc
Consumo <1,3 W
Corrente nominale
CPA050 50 Aca, 50 Acc
CPA300 300 Aca, 400 Acc
Tensione nominale 800 Vca,1000 Vcc
Frequenza 1-400 Hz o cc
Precisione
Energia attiva +/- 1% RDG
Corrente/tensione <0,5% F.S.
Caratteristiche ambientali
Temperatura di esercizio da -15°C a 65°C
Temperatura di stoccaggio da -40°C a 85°C
Umidità relativa da 0 a 90% senza condensa
Ambiente solo uso interno
Caratteristiche RS485
Protocollo MODBUS RTU
Indirizzi 1-247
Formato dati 1 bit di start, 8 bit dati, NO/
ODD/parità EVEN (default
NO parità)
Baud-rate 1200, 2400,4800, 9600, 19200,
38400, 57600, 115200 bps
Ritardo alla risposta 1-1000 ms
Caratteristiche generali
Sezione del cavo 1,5 mm
2
Coppia di serragio viti Max 0,25 Nm
Grado di protezione IP 20
05
06
04
03
CPA050
CPA300
A
B
C
D
E F
A
B
C
D
E
F
• EN61000-6-4/2006+A1 2011
• EN64000-6-2/2005
• EN61010-1/2010
GENERAL WARNINGS
           
         



            
        


          


   


Element Component
A Hall sensor hole for current sensing
B
LED.
Hidden: power off
Steady: power on
Blinking: data communication on
C DIP switch for RS485 parameters set-up
D Screw terminals for voltage input connection
E Screw terminals for serial communication and power supply
F Hooks for DIN rail mounting


DIP switch DIP switch 1 DIP switch 2 Address Baudrate
ON OFF 1 9600
ON ON 1 38400
OFF OFF
settable via
communication
(default: 1)
settable via
communication
(default:9600)
PAY ATTENTION: the baudrate 1200, 2400, 4800, 19200, 57600, 115200 can be set only via
RS485 (see the section after) by means of UCS software.


by Carlo Gavazzi


Step Action
1
Set a baudrate by DIP switch to communicate to the RS485 and UCS tool. (See
the section before).
2 Install UCS software onto a PC.
3
Connect the CPA to the UCS tool via RS485 and set the address, baudrate or other
parameters by using UCS functions.
Note: the new parameters are stored into the CPA EEPROM memory.
4 Turn off the CPA and disconnect it from the PC.
5
Set both DIP switches to OFF.
6
Turn on the CPA.
The CPA will load the parameters set before via UCS and stored into its own
EEPROM.

Figure Description
03 ac input connection
04 dc input connection
05 Power Supply connection (from 9 to 30 Vdc)
06 RS485 connection
ENGLISH
02
01
AVVERTENZE GENERALI






ATTENZIONE: prima di accendere lo strumento assicurarsi che sia cablato













DIP switch DIP switch 1 DIP switch 2 Indirizzo Baudrate
ON OFF 1 9600
ON ON 1 38400
OFF OFF
impostabile via
com. seriale
(default: 1)
impostabile via
com. seriale
(default:9600)
ATTENZIONE: i baudrate 1200, 2400, 4800, 19200, 57600, 115200 sono impostabili solo
tramite RS485 (vedere la prossima sezione) mediante il software UCS.


fornito da Carlo Gavazzi


Passo Azione
1
Impostare un baudrate mediante DIP switch per comunicare con RS485 e UCS.
(Vedere sezione precedente).
2 Installare il software UCS sul PC.
3
Connettere il CPA al software UCS mediante RS485 e programmare indirizzo,
baudrate o altri parametri utilizzando le funzioni del software UCS.
Nota: i nuovi parametri sono memorizzati nella memoria EEPROM del CPA.
4 Spegnere il CPA e scollegarlo dal PC.
5
Impostare entrambi i DIP switch OFF.
6
Accendere il CPA.
Il CPA caricherà i parametri programmati precedentemente mediante UCS e
memorizzati nella EEPROM.

Figura Descrizione
03 Collegamento ingresso ca
04 Collegamento ingresso cc
05 Collegamento di alimentazione (da 9 a 30 V cc)
06 Collegamento RS485
ITALIANO
Elemento Componente
A Sensore di Hall per il rilevamento della corrente
B
LED.
Nascosto: nessuna alimentazione
Fisso: alimentazione presente
Lampeggiante: comunicazione dati in corso
C DIP switch per l’impostazione dei parametri della RS485
D Morsetti a vite per il collegamento degli ingressi di tensione
E
Morsetti a vite per il collegamento della comunicazione seriale e dell’ali-
mentazione.
F Ganci per il montaggio su guida DIN

Codice 8021885
   
       
         
      
      
      

ALLGEMEINE SICHERHEITSHINWEISE
       



        


   



       

          

 

Element Komponente
A Hall-Geber-Öff nung für Spannungsabtastung
B
LED.
Verborgen: Strom aus
Immer an: Strom an
Blinkt: Datenkommunikation an
C DIP switch für RS485 Parametereinstellung
D Schraubenklemmen für Anschluss Spannungseingang
E Schraubenklemmen für serielle Kommunikation und Stromversorgung
F Haken für DIN-Schienenmontage

             

DIP switch DIP switch 1 DIP switch 2 Adresse Baudrate
ON OFF 1 9600
ON ON 1 38400
OFF OFF


(default: 1)


(default:9600)
ACHTUNG: die Baudrate 1200, 2400, 4800, 19200, 57600, 115200 kann nur per RS485
(siehe folgenden Abschnitt) durch UCS Software eingestellt werden.


von Carlo Gavazzi


Schritt Action
1
Stellen Sie per DIP switch eine Baudrate ein, um mit dem RS485 und der UCS-
Software zu kommunizieren. (Siehe Abschnitt oben).
2 Installieren Sie die UCS-Software auf einem PC.
3
Verbinden Sie den CPA per RS485 mit der UCS-Software uns stellen Sie die
Adresse, Baudrate oder weitere Parameter mit den UCS-Funktionen ein.
Hinweis: die neuen Parameter werden in dem CPA EEPROM Speicher gespei-
chert.
4 Schalten Sie den CPA aus und trennen Sie ihn vom PC.
5
Stellen Sie beide DIP switches auf AUS.
6
Schalten Sie den CPA ein.
Der CPA lädt die zuvor per UCS und im eigenen EEPROM gespeicherten Parame-
ter.

Ab-
bildung
Beschreibung
03 Anschluss ac-Eingang
04 Anschluss dc-Eingang
05 Anschluss Spannungsversorgung (9 bis 30 Vdc)
06 RS485-Anschluss


Code 8021885

    
       
     
     


Elektrische Spezifi kation
Systemtyp 1-phasig ac/dc
Stromversorgung 9 bis 30 Vdc
Verbrauch <1,3 W
Nennstrom
CPA050 50 Aac, 50 Adc
CPA300 300 Aac, 400 Adc
Nennspannung 800 Vac,1000 Vdc
Frequenz 1-400 Hz oder dc
Genauigkeit
Wirkleistung +/- 1% RDG
Strom/Spannung <0,5% F.S
Umweltbedingungen
Betriebstemperatur -15°C bis 65°C
Lagertemperatur -40°C bis 85°C
Relative Luftfeuchtigkeit 0 bis 90% ohne Kondensation
Umfeld nur für Innenbereiche
RS485 Spezifi kation
Protokoll MODBUS RTU
Adressen 1-247
Datenformat 1 Startbit, 8 Datenbit, KEINE/
UNGERADE/GERADE Parität
(Default KEINE Parität)
Baudrate 1200, 2400,4800, 9600, 19200,
38400, 57600, 115200 bps
Reaktionsverzögerung 1-1000 ms
Allgemeine technische Daten
Kabelquerschnitt 1,5 mm
2
Schraubenanzugsmoment Max 0,25 Nm
Schutzart IP 20

Simbolo Descrizione
Indica che tutte le parti accessibili dell’oggetto, sono separate
dalle parti in tensione mediante un isolamento doppio o rinforzato
Pericolo alta tensione
Pericolo generico
Verso di inserimento del cavo
MANUTENZIONE E SMALTIMENTO
Responsabilità di smaltimento
Smaltire con raccolta diff erenziata tramite le strutture di raccolte indicate
dal governo o dagli enti pubblici locali. Il corretto smaltimento e il riciclag-
gio aiuteranno a prevenire conseguenze potenzialmente negative per
l’ambiente e per le persone.

Symbol Description
Indicates that all the accessible parts of the object are separated from the live
parts by means of double or reinforced insulation
High voltage hazard
Generic hazard
Insertion direction of the cable
MAINTENANCE AND DISPOSAL
Responsibility for disposal
The product must be disposed of at the relative recycling centers specifi ed
by the government or local public authorities. Correct disposal and
recycling will contribute to the prevention of potentially harmful conse-
quences to the environment and persons.

Symbol Beschreibung
Bedeutet, dass alle zugänglichen Teile des jeweiligen Gegenstands durch eine
doppelte oder verstärkte Isolierung von den unter Spannung stehenden Teilen
getrennt sind
Gefahr durch Hochspannung
Allgemeine Gefahr
Einsteck-Richtung des Kabels
WARTUNG UND ENTSORGUNG
Verantwortlichkeit für die Entsorgung
Es muss für getrennte Abfallentsorgung anhand der von der Regierung oder den
öff entliche Lokalbehörden benannten Sammelstrukturen gesorgt werden. Die
korrekte Entsorgung bzw. das Recycling tragen dazu bei, potentiell negative
Auswirkungen auf die Umwelt und die Personen zu vermeiden.
CARLO GAVAZZI Controls SpA
via Safforze, 8 - 32100 Belluno (BL) Italy
www.gavazziautomation.com
info: +39 0437 355811 / fax: +39 0437 355880
CPA050 CPA300



05
06
04
03
CPA050
CPA300
A
B
C
D
E F
A
B
C
D
E
F
FRANÇAIS
02
01

          
        



 

            










Élément Composant
A Orifi ce du capteur de hall pour la détection du courant
B
LED.
Masquée : hors tension
Allumée fi xe : sous tension.
Clignotante : communication de données en cours
C Commutateur DIP pour paramétrage de RS485
D Bornes à vis pour la connexion de la tension d'entrée
E Bornes à vis pour la communication série et la mise sous tension
F Crochets pour montage de rails DIN


Commutateur
DIP
Commutateur
DIP 1
Commutateur
DIP 2
Adresse Débit en Baud
ON OFF 1 9600
ON ON 1 38400
OFF OFF


défaut : 1)


défaut :9600)
ATTENTION: le débit en Baud 1200, 2400, 4800, 19200, 57600, 115200 peut se régler
uniquement via le RS485 (cf. chapitre suivant) au moyen du logiciel UCS.





Étape Action
1
Confi gurer un débit en Baud par commutateur DIP pour communiquer avec le
RS485 et l'UCS. (Voir le chapitre précédent).
2 Installer le logiciel UCS sur un ordinateur.
3
Connecter le CPA à l'UCS via le RS485 et saisir l'adresse, le débit en Baud ou
d'autres paramètres en utilisant les fonctions de l'UCS.
Remarque : les nouveaux paramètres sont enregistrés dans la mémoire EEPROM
du CPA.
4 Couper le CPA et le déconnecter de l'ordinateur.
5
Mettre les deux commutateurs DIP en marche (OFF).
6
Allumer le CPA.
Le CPA chargera les paramètres confi gurés au moyen de l'UCS et enregistrés
dans sa mémoire EEPROM.

Figure Description
03 Connexion d'entrée ca
04 Connexion d'entrée cc
05 Connexion d'alimentation électrique (de 9 à 30 V cc)
06 Connexion RS485

Code 8021885

         

       
      

Caractéristiques électriques
Type de système ca, cc monophasé
Alimentation V CC de 9 à 30
Consommation <1,3 W
Courant nominal
CPA050 50 Aca, 50 Acc
CPA300 300 Aca, 400 Acc
Tension nominale 800 Vca, 1000 Vcc
Fréquence 1-400 Hz ou cc
Précision
Énergie active +/- 1% RDG
Courant/tension <0,5 % F.S
Spécifi cations environnementales
Température de fonction-
nement
de -15°C à 65°C
Température de stockage de -40°C à 85°C
Humidité relative de 0 à 90% sans condensation
Environnement
Utilisation en intérieur uniquement
Caractéristiques RS485
Protocole MODBUS RTU
Adresses 1-247
Format de données
1 bit de départ, 8 bits de données,
AUCUNE parité/parité IMPAIRE/
PAIRE (par défaut AUCUNE parité)
Débit en Bauds 1200, 2400,4800, 9600, 19200,
38400, 57600, 115200 bps
Délai de réponse 1-1000 ms
Spécifi cations générales
Aire de section de câble 1,5 mm
2
Couple de serrage de vis Max 0,25 Nm
Degré de Protection IP 20

          


CUIDADO: cualquier cambio realizado por el interruptor DIP requiere desconectar la

          

         
          
electroimanes o masas de hierro     

        





Elemento Componente
A Orifi cio de sensor de efecto Hall para detección de corriente
B
LED.
Oculto: alimentación desconectada
Fijo: alimentación conectada
Destello: comunicación de datos conectada
C Confi guración de interruptor DIP para parámetros RS485
D Terminales de tornillo para conexión de entrada de tensión
E Terminales de tornillo para comunicación en serie alimentación
F Ganchos para montaje del carril DIN


Interruptor DIP Interruptor DIP 1 Interruptor DIP 2 Dirección Velocidad de
baudios
ON OFF 1 9600
ON ON 1 38400
OFF OFF
Confi gurable a
través de com.
serie (predetermi-
nado: 1)
Confi gurable a
través de com.
serie (predetermi-
nado:9600)
ATENCIÓN: la velocidad de baudios 1200, 2400, 4800, 19200, 57600, 115200 solo se pue-
de establecer a través de RS485 (ver la sección después) mediante software UCS.






Paso Acción
1
Establezca una velocidad de baudios mediante un interruptor DIP para comunicar-
se con RS485 y la herramienta UCS. (Ver la sección antes).
2 Instalar software UCS en un PC.
3
Conecte el CPA a la herramienta UCS mediante RS485 y establezca la dirección,
velocidad de baudios u otros parámetros mediante las funciones UCS.
Nota: los nuevos parámetros se almacenan en la memoria EEPROM del CPA.
4 Apagar el CPA y desconectarlo del PC.
5
Coloque ambos interruptores DIP en OFF.
6
Encender el CPA.
El CPA cargará los parámetros establecidos anteriormente a través del UCS y
almacenados en su propia EEPROM

Figura Descripción
03 Conexión de entrada de ca
04 Conexión de entrada de cd
05 Conexión de alimentación (de 9 a 30 VCC)
06 Conexión RS485
ESPAÑOL


        
           
           
        
       

Especifi caciones eléctricas
Tipo de sistema Monofásico ca/cd
Alimentación 9 a 30 Vcc
Consumo <1,3 W
Corriente nominal
CPA050 50 A ac, 50 Acc
CPA300 300 Aac, 400 Acc
Voltaje nominal 800 Vac,1000 Vcc
Frecuencia 1-400 Hz o cd
Precisión
Energía activa +/- 1 % RDG
Corriente/voltaje <0,5 % F.S
Especifi caciones ambientales
Temperatura de funcionamiento
de -15°C a 65°C
Temperatura de almacenamiento
de -40°C a 85°C
Humedad relativa de 0 a 90 % sin condensación
Ambiente Solo para uso en interior
Especifi cación de RS485
Protocolo MODBUS RTU
Direcciones 1-247
Formato de datos 1 bit de inicio, 8 bits de datos,
paridad ninguno/impar/par
(predeterminado sin paridad)
Tasa de baudios 1200, 2400,4800, 9600, 19200,
38400, 57600, 115200 bps
Retraso de respuesta 1-1000 ms
Especifi caciones generales
Área de sección cruzada del cable
1,5 mm
2
Par de apriete de los tornillos Máx. 0,25 Nm
Grado de protección IP 20

       
       

         

           

           

       




            


Element Komponent
A Hall-følehul til strømregulering
B
LED.
Skjult: Strøm ikke tilsluttet
Konstant tændt: Strøm tilsluttet
Blinker: Datakommunikation tændt
C Opsætning af DIP-omskifter til RS485-parametre
D Skrueterminaler til spændingsindgang
E Skrueterminaler til seriel kommunikation og strømforsyning
F Kroge til DIN-skinnemontering


DIP-omskifter DIP-omskifter 1 DIP-omskifter 2 Adresse Baudhastighed
ON OFF 1 9600
ON ON 1 38400
OFF OFF
Kan indstilles via
seriel kommuni-
kation (default: 1)
Kan indstilles via
seriel kommunika-
tion (default: 9600)
PAS PÅ: Baudrate 1200, 2400, 4800, 19200, 57600, 115200 kan kun indstilles via RS485
(se næste afsnit) vha. UCS-software.


som leveres af Carlo Gavazzi


Trin Handling
1
Indstil en baudrate med DIP-omskifteren for at kommunikere med RS485 og UCS-
værktøjet. (Se forrige afsnit).
2 Installer UCS-softwaren på en PC.
3
Tilslut CPA til UCS-værktøjet via RS485, og indstil adresse, baudrate eller andre
parametre vha. UCS-funktioner.
Bemærk: De nye parametre lagres i CPA's EEPROM-hukommelse.
4 Sluk CPA, og frakobl fra PC'en.
5
Indstil begge DIP-omskiftere til OFF (tændt).
6
Tænd CPA.
CPA indlæser de parametre, der blev angivet tidligere via UCS og lagret i dens
egen EEPROM.

Figur Beskrivelse
03 AC-indgangsforbindelse
04 DC-indgangsforbindelse
05 Strømforsyningsforbindelse (fra 9 til 30 Vdc)
06 RS485-forbindelse









Elektriske specifi kationer
Systemtype 1-faset AC/DC
Strømforsyning 9-30 Vdc
Forbrug <1,3 W
Mærkestrøm
CPA050 50 Aac, 50 Adc
CPA300 300 Aac, 400 Adc
Nominel spænding 800 Vac,1000 Vdc
Frekvens 1-400 Hz eller jævnstrøm
Nøjagtighed
Aktiv energi +/- 1% RDG
Strøm/spænding <0,5% F.S
Miljøteknisk specifi kation
Driftstemperatur -15°C til 65°C
Opbevaringstemperatur -40°C til 85°C
Relativ fugtighed
Fra 0-90 % ikke-kondenserende
Miljø Kun til indendørs brug
RS485-specifi kation
Protokol MODBUS RTU
Adresser 1-247
Dataformat 1 startbit, 8 databit, INGEN/
ULIGE/LIGE paritet (standard:
INGEN paritet)
Baudrate 1200, 2400,4800, 9600, 19200,
38400, 57600, 115200 bps
Svarforsinkelse 1-1000 ms
Generelle specifi kationer
Kabeltværsnitsareal 1,5 mm
2
Skruetilspændingsmoment Maks. 0,25 Nm
Beskyttesesgrad IP 20
• EN61000-6-4/2006+A1 2011
• EN64000-6-2/2005
• EN61010-1/2010

Símbolo Descripción
Indica que todas las partes accesibles del objeto están separadas de las partes
en tensión mediante un aislamiento doble o reforzado
Peligro alta tensión
Peligro genérico
Sentido de introducción del cable
MANTENIMIENTO Y ELIMINACIÓN
Responsabilidad de eliminación
Eliminar mediante recogida selectiva a través de las estructuras de
recogida indicadas por el gobierno o por los entes públicos locales. La
correcta eliminación y el reciclaje ayudarán a prevenir consecuencias
potencialmente negativas para el medioambiente y para las personas.

Symbole Description
Indique que toutes les pièces accessibles de l’objet, sont séparées des pièces
sous tension par une isolation double ou renforcée
Danger haute tension
Danger général
Sens d’introduction du câble
ENTRETIEN ET ÉLIMINATION
Responsabilité en matière d’élimination
Éliminer selon le tri sélectif avec les structures de récupération indiquées par l’État ou
par les organismes publics locaux. Bien éliminer et recycler aidera à prévenir des
conséquences potentiellement néfastes pour l’environnement et les personnes.

Symbol Beskrivelse
Angiver, at alle objektets tilgængelige dele er adskilt fra spændingsdele ved hjælp
af en dobbeltisolering eller forstærket isolering
Højspændingsfare
Generel fare
Side til isættelse af kabel
HÅNDTERING OG BORTSKAFFELSE
Ansvar vedrørende bortskaff else
Sorteres og bortskaff es på genbrugsplads, som angivet af stat eller
kommune. Den korrekte bortskaff else og genbrug er med til at forhindre
potentielt negative følger for miljøet og personer.
  • Page 1 1
  • Page 2 2

CARLO GAVAZZI CPA3001LS1X Guida d'installazione

Tipo
Guida d'installazione
Questo manuale è adatto anche per