Installation
Installation Requirements
This product is designed for use on flat surfaces of Type 1, Type 4X (Indoor
Use Only), Type 13 Enclosure or IP65F.
Be aware of the following when building this product into an end-use product:
• The rear face of this product is not approved as an enclosure. When building this
product into an end-use product, be sure to use an enclosure that satisfies
standards as the end-use product’s overall enclosure.
• Install this product in an enclosure with mechanical rigidity.
• This product is not designed for outdoor use. UL certification obtained is for
indoor use only.
• Install and operate this product with its front panel facing outward.
NOTE :
• IP65F is not part of the UL certification.
• The necessary torque to fasten the screw of the enclosed installation fasteners is
0.35 N•m (3.1 lb-in).
Check that the installation wall or cabinet surface is flat, in good condition
and has no jagged edges. Metal reinforcing strips may be attached to the
inside of the wall, near the panel cutout, to increase its rigidity.
Decide on the thickness of the enclosure wall, based on the level of strength
required: 1.5...6 mm (0.06...0.24 in).
Even if the installation wall thickness is within the recommended range for
the panel cutout dimensions, depending on wall’s material, size, and
installation location of this product and other devices, the installation wall
could warp. To prevent warping, the installation surface may need to be
strengthened.