RKC INSTRUMENT COM-ML-2 Manuale utente

Tipo
Manuale utente
IMR02E08-E3
RKC INSTRUMENT INC.
EtherNet/IP
Communication Converter
CO
M
-
M
L
Instruction Manual
[For SRZ]
*00577629*
All Rights Reserved, Copyright 2008, RKC INSTRUMENT INC.
NOTICE
EtherNet/IP is a trademark of ControlNet International Ltd. used under license by Open DeviceNet
Vendor Association, Inc. (ODVA).
ControlLogix and RSLogix are trademarks of Rockwell Automation. RSLinx is a registered trademark
of Rockwell Automation.
Modbus is a registered trademark of Schneider Electric.
The name of each programmable controller (PLC) means the products of each manufacturer.
Company names and product names used in this manual are the trademarks or registered
trademarks of the respective companies.
This manual assumes that the reader has a fundamental knowledge of the principles of
electricity, process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for explanation
purpose.
RKC is not responsible for any damage or injury that is caused as a result of using this
instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments
made by imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC
makes no warranty, expressed or implied, with respect to the accuracy of the information.
The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without
prior written approval from RKC.
IMR02E08-E3 i-1
Safety Precautions
Pictorial Symbols (safety symbols)
Various pictorial symbols are used in this manual to ensure safe use of the product, to protect
you and other people from harm, and to prevent damage to property. The symbols are
described below.
Be sure you thoroughly understand the meaning of the symbols before reading this manual.
:
This mark indicates precautions that must be
taken if there is danger of electric shock, fire,
etc., which could result in loss of life or injury.
:
This mark indicates that if these precautions
and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions
should be taken for safe usage.
To prevent injury to persons, damage to the instrument and the equipment, a
suitable external protection device shall be required.
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to the instrument and the equipment.
This instrument must be used in accordance with the specifications to prevent
fire or damage to the instrument and the equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc. to
avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction may
occur and warranty is void under these conditions.
IMR02E08-E3
i-2
This product is intended for use with industrial machines, test and measuring equipment.
(It is not designed for use with medical equipment and nuclear energy plant.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply,
source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock to operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired.
All wiring must be in accordance with local codes and regulations.
To prevent instrument damage as a result of failure, protect the power line and the input/output
lines from high currents with a suitable overcurrent protection device with adequate breaking
capacity such as a fuse, circuit breaker, etc.
A malfunction in this product may occasionally make control operations impossible or prevent
alarm outputs, resulting in a possible hazard. Take appropriate measures in the end use to
prevent hazards in the event of malfunction.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid electric
shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dissipation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration may occur. Use a soft, dry cloth to remove stains from the instrument.
Do not connect modular connectors to telephone line.
When disposing of each part used for this instrument, always follows the procedure for
disposing of industrial wastes stipulated by the respective local community.
For Proper Disposal
IMR02E08-E3
i-3
Symbols
Pictorial Symbols (safety symbols)
: This mark indicates important information on installation, handling
and operating procedures.
: This mark indicates supplemental information on installation,
handling and operating procedures.
: This mark indicates where additional information may be located.
Abbreviation symbols
These abbreviations are used in this manual:
Abbreviation
symbols
Name
Abbreviation
symbols
Name
PV Measured value TC (input) Thermocouple (input)
SV Set value RTD (input) Resistance temperature detector (input)
MV Manipulated output value V (input) Voltage (input)
AT Autotuning I (input) Current (input)
ST Startup tuning HBA Heater break alarm
OUT Output CT Current transformer
DI Digital input LBA Control loop break alarm
DO Digital output LBD LBA deadband
IMR02E08-E3
i-4
About This Manual
There are four manuals pertaining to this product. Please be sure to read all manuals specific to your
application requirements.
The following manuals can be downloaded from the official RKC website:
https://www.rkcinst.com/english/manual_load.htm.
Manual
Manual
Number
Remarks
EtherNet/IP Communication Converter
COM-ML [For SRZ] Installation Manual
IMR02E05-E This manual is enclosed with instrument.
This manual explains the mounting and wiring.
EtherNet/IP Communication Converter
COM-ML [For SRZ] Quick Operation Manual
IMR02E06-E This manual is enclosed with instrument.
This manual explains the communication setting
and the basic operation method.
EtherNet/IP Communication Converter
COM-ML [For SRZ] Host Communication Data List
IMR02E07-E This manual is enclosed with instrument.
This list is a compilation of the host communication
data items.
EtherNet/IP Communication Converter
COM-ML [For SRZ] Instruction Manual
IMR02E08-E3
This manual you are reading now.
This manual describes mounting, wiring,
communication setting, protocol, communication
data, troubleshooting and product specification.
Read this manual carefully before operating the instrument. Please place the manual in a
convenient location for easy reference.
IMR02E08-E3
i-5
Contents
Page
NOTICE
Safety Precautions ............................................................................................................................... i-1
Pictorial Symbols (safety symbols) .............................................................................................. i-1
WARNING ....................................................................................................................................... i-1
CAUTION ........................................................................................................................................ i-2
For Proper Disposal .............................................................................................................................. i-2
Symbols ................................................................................................................................................ i-3
Pictorial Symbols (safety symbols) .............................................................................................. i-3
Abbreviation symbols ................................................................................................................... i-3
About This Manual ................................................................................................................................ i-4
1. OUTLINE .............................................................................. 1
1.1 Checking the Product ..................................................................................... 2
1.2 Model Code .................................................................................................... 3
1.3 Parts Description ............................................................................................ 4
2. HANDLING PROCEDURES ................................................ 6
3. MOUNTING .......................................................................... 7
3.1 Mounting Cautions .......................................................................................... 7
3.2 Dimensions ..................................................................................................... 9
3.3 DIN Rail Mounting .......................................................................................... 9
3.4 Panel Mounting ............................................................................................. 11
4. WIRING .............................................................................. 12
4.1 Wiring Cautions ............................................................................................ 12
4.2 Terminal Configuration ................................................................................. 13
4.3 Connection to EtherNet/IP ............................................................................ 14
4.4 Connection to Host Computer ....................................................................... 16
4.4.1 When connected with RS-422A ............................................................................................... 16
4.4.2 When connected with RS-485 ................................................................................................. 18
4.4.3 Connections for loader communication ................................................................................... 20
IMR02E08-E3
i-6
Page
5. HOST COMMUNICATION SETTING ................................. 2 1
5.1 Address Setting ............................................................................................ 21
5.2 DIP Switch Setting ........................................................................................ 22
6. COMMUNICATION SETTING OF
SRZ FUNCTION MODULE ................ 23
6.1 Address Setting of the Function Modules ..................................................... 23
6.2 Temperature Control Channel of the SRZ Unit ............................................. 24
6.3 Digital Input/Output Channel of Z-DIO Module ............................................. 25
7. INITIAL COMMUNICATION DATA SETTING ................... 26
7.1 IP Address Setting ........................................................................................ 26
7.2 EtherNet/IP Communication Settings ........................................................... 29
7.3 Other Communication Data Settings ............................................................ 34
8. EtherNet/IP ......................................................................... 35
8.1 Outline of EtherNet/IP .................................................................................... 35
8.2 Communication Method ................................................................................. 37
9. COMMUNICATION DATA LIST ......................................... 38
9.1 Reference to Communication Data List ........................................................ 38
9.2 Communication Data of COM-ML ................................................................. 40
9.3 Communication Data of Z-TIO Module ......................................................... 43
9.4 Memory Area Data Address of Z-TIO Module ............................................... 66
9.5 Communication Data of Z-DIO Module ......................................................... 68
10. USAGE EXAMPLE ........................................................... 73
10.1 Handling Procedures ................................................................................... 73
10.2 System Configuration .................................................................................. 74
10.3 Use Instruments Settings ............................................................................ 75
10.4 Initial Communication Data Settings ........................................................... 75
10.5 Tool Settings ............................................................................................... 76
10.6 I/O Communication ..................................................................................... 84
10.7 Explicit Message Communication ............................................................... 87
IMR02E08-E3
i-7
Page
11. TROUBLESHOOTING ...................................................... 93
12. SPECIFICATIONS ............................................................ 98
13. OBJECT MODEL ............................................................ 102
13.1 CIP Common Object .................................................................................. 102
13.2 Application Object ...................................................................................... 106
APPENDIX. HOST COMMUNICATION PROTOCOL .......... 108
A.1 Communication Requirements .................................................................... 108
A.2 RKC Communication Protocol .................................................................... 110
A.2.1 Polling procedures ............................................................................................................... 110
A.2.2 Selecting procedures ........................................................................................................... 116
A.2.3 Communication data structure ............................................................................................. 121
A.3 Modbus Protocol ......................................................................................... 123
A.3.1 Message format ................................................................................................................... 123
A.3.2 Function code ...................................................................................................................... 124
A.3.3 Communication mode .......................................................................................................... 124
A.3.4 Slave responses .................................................................................................................. 125
A.3.5 Calculating CRC-16 ............................................................................................................. 126
A.3.6 Register read and write ....................................................................................................... 129
A.3.7 Data processing precautions ............................................................................................... 133
A.3.8 How to use memory area data ............................................................................................ 134
IMR02E08-E3
i-8
MEMO
IMR02E08-E3 1
1. OUTLINE
EtherNet/IP communication converter COM-ML [For SRZ] (hereafter called COM-ML) is communication
converter to connect the RKC module type controller SRZ to the EtherNet/IP.
This chapter describes features, package contents, model code, system configuration, etc.
EtherNet/IP is an implementation of CIP (Common Industrial Protocol) on Ethernet and TCP/IP.
COM-ML supports “I/O communication” and “Explicit message communication” for EtherNet/IP.
Scanner/adapter (multicast: 1 to N) communication is used in I/O communication.
Client/server (peer to peer: 1 to 1) communication is used in explicit message communication.
In scanner/adapter communication, COM-ML corresponds to the adapter. In client/server
communication, COM-ML corresponds to the server.
Up to 30 function modules (Z-TIO and Z-DIO) can be connected to one COM-ML with SRZ unit.
(However, the maximum joinable number of function modules of the same type is 16.)
SRZ Unit
Host computer
or
Operation panel
Z-TIO-A/B or Z-DIO-A module
(Up to 30 modules)
EtherNet/IP
or
Ethernet
RKC communication
Modbus
RS-485
RS-422A
EtherNet/IP communication converter
COM-ML
[Adapter or Server]
Programmable
controller
(PLC)
[Scanner or Client]
Host
computer
Network Hub
Ethernet
EtherNet/IP
For EtherNet/IP, see the website of ODVA (Open DeviceNet Vendor Association).
URL: https://www.odva.org/
1. OUTLINE
IMR02E08-E3
2
1.1 Checking the Product
Before using this product, check each of the following:
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, or terminal, etc.)
Check that all of the items delivered are complete. (See below)
Name Q’TY Remarks
COM-ML [For SRZ] Installation Manual (IMR02E05-E) 1 Enclosed with instrument
COM-ML [For SRZ] Quick Instruction Manual (IMR02E06-E) 1 Enclosed with instrument
COM-ML [For SRZ] Communication Data List (IMR02E07-E) 1 Enclosed with instrument
Joint connector cover KSRZ-517A 2 Enclosed with instrument
Power terminal cover KSRZ-518A 1 Enclosed with instrument
COM-ML [For SRZ] Instruction Manual (IMR02E08-E3) 1 This manual (sold separately)
This manual can be downloaded from
the official RKC website:
https://www.rkcinst.com/english/
manual_load.htm
If any of the products are missing, damaged, or if your manual is incomplete, please contact
RKC sales office or the agent.
EDS file
The EDS file is used for recognition of the COM-ML on EtherNet/IP in the configuration tool
(software for environment settings and creating programs); however, EtherNet/IP communication
is possible without using the EDS file.
If you require the EDS file, download it from the official RKC website.
https://www.rkcinst.com/english/manual_load.htm
Accessories (sold separately)
Name Q’TY Remarks
End plate DEP-01 2 Secures the SRZ on the DIN rail
Communication converter COM-K2-1 1 For loader communication
(Option: with loader communication cable)
Connection cable (W-BF-01-, : cable length) 1 For host communication
Modular connector and Spade lug terminal
Connection cable (W-BF-02-, : cable length) 1 For host communication
Modular connectors (at both ends)
Connection cable (W-BF-28-, : cable length) 1 For host communication
Modular connector and D-sub 9-pin connector
1. OUTLINE
IMR02E08-E3
3
1.2 Model Code
Check whether the delivered product is as specified by referring to the following model code list.
If the product is not identical to the specifications, please contact RKC sales office or the agent.
(1) Ethernet communication type
2: EtherNet/IP
(2) Host communication interface (COM. PORT)
4: RS-422A
5: RS-485
(3) Corresponding to the RKC controller
02: SRZ
COM- ML - 2 02
(1) (2) (3)
1. OUTLINE
IMR02E08-E3
4
1.3 Parts Description
COM-ML mainframe
Loade
r
communication
connecto
r
Indication lamp RX/TX
Indication lamp FAIL/RUN
Host communication
address setting switch
Communication
port
COM. PORT
Indication lamp NS
EtherNet/IP
communication
connecto
r
Left side view
DIP switch
Front view
Indication lamp LINK
Indication lamp MS
COM-ML
FAIL/RU N
LOADER
RX/T
X
COM.PORT
NS MS
LINK
EtherNet/IP
Base
Indication lamps
FAIL/ RUN [Green or Red] When normal: A green lamp is on (RUN)
During setting of default IP address setting: A green lamp flashes (RUN)
Self-diagnostic error (Recoverable fault): A green lamp flashes (FAIL)
Self-diagnostic error (Major fault): A red lamp is on (FAIL)
RX/TX [Green] During host communication data send and receive: A green lamp turns on
NS (Network status)
[Green or Red]
No power or no IP address: Turns off
Online, no connection established: A green lamp flashes
Online, connections established: A green lamp turns on
I/O connection is timeout: A red lamp flashes
A fatal communications error has occurred (Duplicate IP address):
A red lamp turns on
LINK (Link/Activity) [Green] No link, no activity: Turns off
Activity (During data send): A green lamp flashes
Link established: A green lamp turns on
MS (Module status)
[Green or Red]
No power: Turns off
Controlled by a Scanner in Run state: A green lamp turns on
Not configured, or Scanner in idle state: A green lamp flashes
Recoverable fault: A red lamp flashes
Major fault: A red lamp turns on
Communication port (modular connector) and communication connector
COM. PORT Use to connecting the Operation panel or Host computer. [RS-485 or RS-422A]
EtherNet/IP communication
connector
Use to connecting the EtherNet/IP.
Loader communication connector Use to connecting the communication converter and personal computer when
loader communication is performed.
Switch
Host communication address
setting switch
Sets unit address for host communication.
DIP switch
Sets the communication speed and communication protocol corresponding to
host communication.
Sets dip switch setting validity/invalidity.
Sets the default IP address settings.
1. OUTLINE
IMR02E08-E3
5
Base
Mounting holes (M3 screw)
Power supply
terminals
Joint connector
Mounting
bracket
Terminal 3, 4 and 5
Usage is prohibited.
Front Rear
Mounting holes (M3 screw)
Holes for screws to fix the base to a panel, etc.
Customer must provide the M3 screws.
Joint connector
Used to mechanically and electrically connect each module.
Power supply terminals
These are terminals to supply power to the COM-ML and joined function modules.
Terminal number Signal name
1 24 V DC (+)
2 24 V DC ()
Terminal 3, 4 and 5
These terminals cannot be used for the COM-ML. (Usage is prohibited.)
When the COM-ML is connected to a function module, do not use
terminals 3, 4 and 5 of the function module.
Mounting bracket
Used to fix the module on DIN rails and also to fix each module joined together.
6 IMR02E08-E3
2. HANDLING PROCEDURES
Conduct necessary setting before operation according to the procedure described below.
Mounting
Install the COM-ML.
See 3. MOUNTING (P. 7).
For controller (SRZ), see Z-TIO Instruction Manual
(IMS01T01-E) and Z-DIO Instruction Manual
(IMS01T03-E).
Host communication
settings
Wiring
Controller (SRZ) settings
IP address settings
The address, communication speed, communication protocol, data bi
t
configuration, and DIP switch setting validity/invalidity of hos
t
communication are set only when host communication is used in the
COM-ML.
See 5. HOST COMMUNICATION SETTINGS (P. 21).
Connect the COM-ML power wiring and the controller (SRZ) wiring,
and connect the COM-ML to the scanner (or client). Connect the
wiring for host communication or loader communication in the
COM-ML.
See 4. WIRING (P. 12)
For controller (SRZ), see Z-TIO Instruction Manual
(IMS01T01-E) and Z-DIO Instruction Manual
(IMS01T03-E).
Set the communication setting of controller (SRZ).
See 6. COMMUNICATIOM SETTING OF SRZ
FUNCTION MODULE (P. 23).
For controller (SRZ), see Z-TIO Instruction Manual
(IMS01T01-E) and Z-DIO Instruction Manual
(IMS01T03-E).
Set the IP address of COM-ML.
See 7.1 IP Address Settings (P. 26).
EtherNet/IP
communication settings
Configure initial settings for EtherNet/IP communication.
See 7.2 EtherNet/IP Communication Setting (P. 29).
See 10.5 Tool Settings (P. 76).
Other communication
data settings
Set the data for the COM-ML and controller (SRZ).
See 7.3 Other Communication Data Settings (P. 34).
See 9. COMMUNICATION DATA LIST (P. 38).
EtherNet/IP
communication
Execute I/O communication or explicit message communication.
See 10.6 I/O Communication (P. 84).
See 10.7 Explicit Message Communication (P. 87).
IMR02E08-E3 7
3. MOUNTING
This chapter describes installation environment, mounting cautions, dimensions and mounting procedures.
3.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions.
(IEC 61010-1) [POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions.
Allowable ambient temperature: 10 to +50 °C
Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX.W.C 29.3 g/m
3
dry air at 101.3 kPa)
Installation environment conditions: Indoor use
Altitude up to 2000 m
(3) Avoid the following conditions when selecting the mounting location:
Rapid changes in ambient temperature which may cause condensation.
Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam splashes.
Excessive dust, salt or iron particles.
Excessive induction noise, static electricity, magnetic fields or noise.
Direct air flow from an air conditioner.
Exposure to direct sunlight.
Excessive heat accumulation.
(4) Mount this instrument in the panel considering the following conditions:
Provide adequate ventilation space so that heat does not build up.
Do not mount this instrument directly above the equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors.)
If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or the
like. Cooled air should not blow directly on this instrument.
In order to improve safety and the immunity to withstand noise, mount this instrument as far away as
possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines: Separate at least 200 mm
Rotating machinery: Separate as far as possible
For correct functioning mount this instrument in a horizontal position.
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
3. MOUNTING
IMR02E08-E3
8
Space required between each module vertically
When the module is mounted on the panel, allow a
minimum of 50 mm at the top and bottom of the
module to attach the module to the mainframe.
Depth for modular cables mount type
module
Space for modular cables must be considered
when installing.
It is recommended to use a plastic cover on the connector on both sides of the mounted modules for
protection of connectors.
Joint connector cove
Be sure the COM-ML and SRZ function modules (Z-TIO and Z-DIO modules) are joined when
using them.
(5) In case this instrument is connected to a supply by means of a permanent connection, a switch or
circuit-breaker shall be included in the installation. This shall be in close proximity to the equipment
and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.
50 mm or more
COM
76.9 mm
Communication
cable
Approx.
50 mm
3. MOUNTING
IMR02E08-E3
9
3.2 Dimensions
76.9
30 6.7
100
5
4.7
(Unit: mm)
3.3 DIN Rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the module (A). Attach the hooks on the top of the
module to the DIN rail and push the lower section into place on the DIN rail (B).
2. Slide the mounting bracket up to secure the module to the DIN rail (C).
(B) Push
Mounting
bracket
DIN rail
(A) Pull down
(C) Locked
3. MOUNTING
IMR02E08-E3
10
Module joining procedures
1. Mount the function modules on the DIN rail. Slide the modules until the modules are closely joined
together and the joint connectors are securely connected.
(Front view of module mainframe)
Joint connector
Function module
COM-ML
2. Push in the mounting brackets to lock the modules
together and fix to the DIN rail.
After module joining, install a
plastic cover on the
connector on both sides of the mounted modules for
protection of connectors. (See P. 8)
To firmly fix the modules, use end plates (DEP-01)
sold separately on both sides of the mounted
modules.
Removing procedures
1. Turn the power OFF.
2. Remove the wiring.
3. Pull down a mounting bracket with a
blade screwdriver (A). Lift the module
from bottom, and take it off (B).
(A) Pull down
(B) Lift and take off
(Rear view of base)
Push in all of the mounting brackets.
Mounting
bracket
State where each
module is locked.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150

RKC INSTRUMENT COM-ML-2 Manuale utente

Tipo
Manuale utente

in altre lingue