Comfee 2,6kW Portable Air Conditioner Manuale utente

Tipo
Manuale utente
Thank you for purchasing our Portable Air Conditioner.
Portable Air Conditioner
(Local Air Conditioner)
Instruction Manual
Before using your air conditioner, please read this instruction
manual carefully and keep it for future reference.
READ AND SAVE THESE INSTRUCTIONS!
EN
Contents
Safety Precautions
Cautions
Warnings(for using R290/R32 refrigerant only)
Preparations
Installation
Operation
Maintenance
Faults Diagnosis
Design and Compliance Notes
Sociable Remark
2
3
4
8
9
12
15
16
17
18
-------------
-----------------
-----------------
-------------------
-----------------
---------------
---------------
-------------------
------
-----
1
EN
Safety Precautions
-Installation must be performed according to the installation instructions. Improper installation
can cause water leakage, electrical shock, or fire.
-Use only the included accessories and parts, and specified tools for the installation. Using
non-standard parts can cause water leakage, electrical shock, fire, and injury or property damage.
-Make sure that the outlet you are using is grounded and has the appropriate voltage. The
power cord is equipped with a three-prong grounding plug to protect against shock. Voltage
information can be found on the nameplate of the unit.
-Your unit must be used in a properly grounded wall receptacle. If the wall receptacle you
intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker
(the fuse or circuit breaker needed is determined by the maximum current of the unit. The
maximum current is indicated on the nameplate located on unit), have a qualified electrician
install the proper receptacle.
-Install the unit on a flat, sturdy surface. Failure to do so could result in damage or excessive
noise and vibration.
-The unit must be kept free from obstruction to ensure proper function and to mitigate safety hazards.
-DO NOT modify the length of the power cord or use an extension cord to power the unit.
-DO NOT share a single outlet with other electrical appliances. Improper power supply can
cause fire or electrical shock.
-DO NOT install your air conditioner in a wet room such as a bathroom or laundry room. Too
much exposure to water can cause electrical components to short circuit.
-DO NOT install the unit in a location that may be exposed to combustible gas, as this could cause fire.
-The unit has wheels to facilitate moving. Make sure not to use the wheels on thick carpet or to roll
over objects, as these could cause tipping.
-DO NOT operate a unit that it has been dropped or damaged.
-The appliance with electric heater shall have at least 1 meter space to the combustible materials.
-Do not touch the unit with wet or damp hands or when barefoot.
-If the air conditioner is knocked over during use, turn off the unit and unplug it from the main power
supply immediately. Visually inspect the unit to ensure there is no damage. If you suspect the unit
has been damaged, contact a technician or customer service for assistance.
-In a thunderstorm, the power must be cut off to avoid damage to the machine due to lightning.
-Your air conditioner should be used in such a way that it is protected from moisture. e.g.
condensation, splashed water, etc. Do not place or store your air conditioner where it can fall or be
pulled into water or any other liquid. Unplug immediately if it occurs.
-All wiring must be performed strictly in accordance with the wiring diagram located inside of the unit.
-The unit's circuit board(PCB) is designed with a fuse to provide overcurrent protection. The
specifications of the fuse are printed on the circuit board, such as: T 3.15A/250V, etc.
WARNING: To prevent death or injury to the user or other people and property damage,
the following instructions must be followed. Incorrect operation due to ignoring of
instructions may cause death, harm or damage.
This symbol indicates that ignoring instructions may cause death or serious injury.
2
EN
Cautions
-This appliance can be used by children aged from 8 years and above and person with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in a safe way
and understand the hazards involved. Children shall not play with the appliance. Cleaning
and user maintenance shall not be made by children without supervision. (be applicable for
the European Countries)
-This appliance is not intended for use by persons (including childern) with reduced physical,
sensory or mental capabilities or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a person responsible for
their safety. (be applicable for other countries except the European Countries )
-Children should be supervised to ensure that they do not play with the appliance.
Children
must be supervised around the unit at all times.
-If the supply cord is damaged, it must be replaced by the manufacturer,its service agent or
similarly qualified persons in order to avoid a hazard.
-Prior to cleaning or other maintenance, the appliance must be disconnected from the supply mains.
-Do not remove any fixed covers. Never use this appliance if it is not working properly, or if it
has been dropped or damaged.
-Do not run cord under carpeting. Do not cover cord with throw rugs, runners, or similar
coverings. Do not route cord under furniture or appliances. Arrange cord away from traffic
area and where it will not be tripped over.
-Do not operate unit with a damaged cord, plug, power fuse or circuit breaker. Discard unit or
return to an authorized service facility for examination and/or repair.
-To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed
control device.
-The appliance shall be installed in accordance with national wiring regulations.
-Contact the authorised service technician for repair or maintenance of this unit.
-Contact the authorised installer for installation of this unit.
-Do not cover or obstruct the inlet or outlet grilles.
-Do not use this product for functions other than those described in this instruction manual.
-Before cleaning, turn off the power and unplug the unit.
-Disconnect the power if strange sounds, smell, or smoke comes from it.
-Do not press the buttons on the control panel with anything other than your fingers.
-Do not remove any fixed covers. Never use this appliance if it is not working properly, or if it
has been dropped or damaged.
-Do not operate or stop the unit by inserting or pulling out the power cord plug.
-Do not use hazardous chemicals to clean or come into contact with the unit. Do not use the
unit in the presence of inflammable substances or vapour such as alcohol, insecticides, petrol,etc.
-Always transport your air conditioner in a vertical position and stand on a stable, level surface
during use.
-Always contact a qualified person to carry out repairs. If the damaged power supply cord must be
replaced with a new power supply cord obtained from the product manufacturer and not repaired.
-Hold the plug by the head of the power plug when taking it out.
-Turn off the product when not in use.
Cautions
3
EN
4
WARNING
CAUTION
CAUTION
CAUTION
Caution: Risk of fire/
flammable materials
(Required for R32/R290 units only)
IMPORTANT NOTE: Read this manual carefully before installing or
operating your new air conditioning unit. Make sure to save this
manual for future reference.
Explanation of symbols displayed on the unit(For the unit adopts R32/R290 Refrigerant only):
This symbol shows that this appliance used a flammable refrigerant. If the
refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.
This symbol shows that the operation manual should be read carefully.
This symbol shows that a service personnel should be handling this
equipment with reference to the installation manual.
This symbol shows that information is available such as the operating
manual or installation manual.
EN
Warnings(for using R290/R32 refrigerant only)
-Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
-The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an
operating gas appliance or an operating electric heater).
-Do not pierce or burn.
-Be aware that the refrigerants may not contain an odour.
-Appliance 5000 Btu/h should be installed, operated and stored in a room with a floor area larger than 5 m .
2
-Compliance with national gas regulations shall be observed.
-Keep ventilation openings clear of obstruction.
-The appliance shall be stored so as to prevent mechanical damage from occurring.
-A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room
area as specified for operation.
-Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate
from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in
accordance with an industry recognised assessment specification.
-Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring
the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use
of flammable refrigerants.
5
Warnings(for using R290/R32 refrigerant only)
1.Transport of equipment containing flammable refrigerants
See transport regulations
2.Marking of equipment using signs
See local regulations
3.Disposal of equipment using flammable refrigerants
See national regulations.
4.Storage of equipment/appliances
The storage of equipment should be in accordance with the
manufacturer's instructions.
5.Storage of packed (unsold) equipment
Storage package protection should be constructed such
that mechanical damage to the equipment inside the
package will not cause a leak of the refrigerant charge.
The maximum number of pieces of equipment permitted to
be stored together will be determined by local regulations.
6.Information on servicing
1)Checks to the area
Prior to beginning work on systems containing flammable
refrigerants, safety checks are necessary to ensure that the
risk of ignition is minimised. For repair to the refrigerating
system, the following precautions shall be complied with
prior to conducting work on the system.
2)Work procedure
Work shall be undertaken under a controlled procedure so
as to minimise the risk of a flammable gas or vapour being
present while the work is being performed.
3)General work area
All maintenance staff and others working in the local area
shall be instructed on the nature of work being carried out.
Work in confined spaces shall be avoided. The area
around the workspace shall be sectioned off. Ensure that
the conditions within the area have been made safe by
control of flammable material.
4)Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant
detector prior to and during work, to ensure the technician
is aware of potentially flammable atmospheres. Ensure
that the leak detection equipment being used is suitable
for use with flammable refrigerants,
i.e. non-sparking, adequately sealed or intrinsically safe.
5)Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration
equipment or any associated parts, appropriate fire
extinguishing equipment shall be available to hand. Have
a dry powder or CO2 fire extinguisher adjacent to the
charging area.
6)No ignition sources
No person carrying out work in relation to a refrigeration
system which involves exposing any pipe work that
contains or has contained
flammable refrigerant shall use any sources of ignition in
such a manner that it may lead to the risk of fire or
explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site
of installation, repairing, removing and disposal, during
which flammable refrigerant can possibly be released to the
surrounding space. Prior to work taking place, the area
around the equipment is to be surveyed to make sure that
there are no flammable hazards or ignition risks. No
Smoking signs shall be displayed.
7)Ventilated area
Ensure that the area is in the open or that it is adequately
ventilated before breaking into the system or conducting
any hot work. A degree of ventilation shall continue during
the period that the work is carried out. The ventilation
should safely disperse any released refrigerant and
preferably expel it externally into the atmosphere.
8)Checks to the refrigeration equipment
Where electrical components are being changed, they shall
be fit for the purpose and to the correct specification. At all
times the manufacturer's maintenance and service
guidelines shall be followed. If in doubt consult the
manufacturer's technical department for assistance. The
following checks shall be applied to installations using
flammable refrigerants:
The charge size is in accordance with the room size within
which the refrigerant containing parts are installed;
The ventilation machinery and outlets are operating
adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the
secondary circuit shall be checked for the presence of
refrigerant; Marking to the equipment continues to be
visible and legible. Markings and signs that are illegible
shall be corrected;
Refrigeration pipe or components are installed in a
position where they are unlikely to be exposed to any
substance which may corrode refrigerant containing
components, unless the components are constructed of
materials which are inherently resistant to being corroded
or are suitably protected against being so corroded.
9)Checks to electrical devices
Repair and maintenance to electrical components shall
include initial safety checks and component inspection
procedures. If a fault exists that could compromise safety,
then no electrical supply shall be connected to the circuit
until it is satisfactorily dealt with. If the fault cannot be
corrected immediately but it is necessary to continue
operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so
all parties are advised.
Initial safety checks shall include:
That capacitors are discharged: this shall be done in a
safe manner to avoid possibility of sparking;
That there no live electrical components and wiring are
EN
exposed while charging, recovering or purging the system;
That there is continuity of earth bonding.
7.Repairs to sealed components
1)During repairs to sealed components, all electrical
supplies shall be disconnected from the equipment being
worked upon prior to any removal of sealed covers, etc. If it
isabsolutely necessary to have an electrical supply to
equipment during servicing, then a permanently operating
form of leak detection shall be located at the most critical
point to warn of a potentially hazardous situation.
2)Particular attention shall be paid to the following to ensure
that by working on electrical components, the casing is not
altered in such a way that the level of protection is affected.
This shall include damage to cables, excessive number of
connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded
such that they no longer serve the purpose of preventing the
ingress of flammable atmospheres. Replacement parts shall
be in accordance with the manufacturer's specifications.
NOTE: The use of silicon sealant may inhibit the
effectiveness of some types of leak detection
equipment. Intrinsically safe components do not have to
be isolated prior to working on them.
8.Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance
loads to the circuit without ensuring that this will not
exceed the permissible voltage and current permitted for
the equipment in use. Intrinsically safe components are
the only types that can be worked on while live in the
presence of a flammable atmosphere. The test apparatus
shall be at the correct rating. Replace components only
with parts specified by the manufacturer. Other parts may
result in the ignition of refrigerant in the atmosphere from
a leak.
9.Cabling
Check that cabling will not be subject to wear, corrosion,
excessive pressure, vibration, sharp edges or any other
adverse environmental effects. The check shall also take
into account the effects of aging or continual vibration
from sources such as compressors or fans.
10.Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition
be used in the searching for or detection of refrigerant
leaks. A halide torch (or any other detector using a naked
flame) shall not be used.
11.Leak detection methods
he following leak detection methods are deemed
acceptable for systems containing flammable refrigerants.
Electronic leak detectors shall be used to detect flammable
refrigerants, but the sensitivity may not be adequate, or
Warnings(for using R290/R32 refrigerant only)
may need re-calibration. (Detection equipment shall be
calibrated in a refrigerant-free area.) Ensure that the
detector is not a potential source of ignition and is suitable
for the refrigerant used. Leak detection equipment shall be
set at a percentage of the LFL of the refrigerant and shall be
calibrated to the refrigerant employed and the appropriate
percentage of gas (25 % maximum) is confirmed. Leak
detection fluids are suitable for use with most refrigerants
but the use of detergents containing chlorine shall be
avoided as the chlorine may react with the refrigerant and
corrode the copper pipe-work. If a leak is suspected, all
naked flames shall be removed/ extinguished. If a leakage
of refrigerant is found which requires brazing, all of the
refrigerant shall be recovered from the system, or isolated
(by means of shut off valves) in a part of the system remote
from the leak. Oxygen free nitrogen (OFN) shall then be
purged through the system both before and during the
brazing process.
12.Removal and evacuation
When breaking into the refrigerant circuit to make repairs
or for any other purpose conventional procedures shall be
used. However, it is important that best practice is followed
since flammability is a consideration. The following
procedure shall be adhered to:
Remove refrigerant;
Purge the circuit with inert gas;
Evacuate;
Purge again with inert gas;
Open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct
recovery cylinders. The system shall be flushed with OFN
to render the unit safe. This process may need to be
repeated several times. Compressed air or oxygen shall
not be used for this task.
Flushing shall be achieved by breaking the vacuum in the
system with OFN and continuing to fill until the working
pressure is achieved, then venting to atmosphere, and
finally pulling down to a vacuum. This process shall be
repeated until no refrigerant is within the system. When
the final OFN charge is used, the system shall be vented
down to atmospheric pressure to enable work to take
place. This operation is absolutely vital if brazing
operations on the pipe-work are to take place.
Ensure that the outlet for the vacuum pump is not close to
any ignition sources and there is ventilation available.
13.Charging procedures
In addition to conventional charging procedures, the
following requirements shall be followed.
Ensure that contamination of different refrigerants does
not occur when using charging equipment. Hoses or lines
shall be as short as possible to minimise the amount of
refrigerant contained in them.
Cylinders shall be kept upright.
Ensure that the refrigeration system is earthed prior to
charging the system with refrigerant.
Label the system when charging is complete (if not already).
6
EN
Warnings(for using R290/R32 refrigerant only)
Extreme care shall be taken not to overfill the refrigeration
system. Prior to recharging the system it shall be pressure
tested with OFN. The system shall be leak tested on
completion of charging but prior to commissioning. A follow
up leak test shall be carried out prior to leaving the site.
14.Decommissioning
Before carrying out this procedure, it is essential that the
technician is completely familiar with the equipment and all
its detail. It is recommended good practice that all
refrigerants are recovered safely. Prior to the task being
carried out, an oil and refrigerant sample shall be taken in
case analysis is required prior to re-use of reclaimed
refrigerant. It is essential that electrical power is available
before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
Mechanical handling equipment is available, if required, for
handling refrigerant cylinders;
All personal protective equipment is available and being
used correctly; The recovery process is supervised at all
times by a competent person;
Recovery equipment and cylinders conform to the
appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that
refrigerant can be removed from various parts of the
system.
f) Make sure that cylinder is situated on the scales before
recovery takes place.
g) Start the recovery machine and operate in accordance
with manufacturer's instructions.
h) Do not overfill cylinders. (No more than 80 % volume
liquid charge).
i) Do not exceed the maximum working pressure of the
cylinder, even temporarily.
j) When the cylinders have been filled correctly and the
process completed, make sure that the cylinders and the
equipment are removed from site promptly and all
isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another
refrigeration system unless it has been cleaned and
checked.
15.Labelling
Equipment shall be labelled stating that it has been
de-commissioned and emptied of refrigerant. The label
shall be dated and signed. Ensure that there are labels
on the equipment stating the equipment contains
flammable refrigerant.
16.Recovery
When removing refrigerant from a system, either for
servicing or decommissioning, it is recommended good
practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed.
Ensure that the correct number of cylinders for holding the
total system charge is available. All cylinders to be used are
designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure relief
valve and associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if possible,
cooled before recovery occurs.
The recovery equipment shall be in good working order with
a set of instructions concerning the equipment that is at hand
and shall be suitable for the recovery of flammable
refrigerants. In addition, a set of calibrated weighing scales
shall be available and in good working order. Hoses shall
be complete with leak-free disconnect couplings and in good
condition. Before using the recovery machine, check that it
is in satisfactory working order, has been properly
maintained and that any associated electrical components
are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant
supplier in the correct recovery cylinder, and the relevant
Waste Transfer Note arranged. Do not mix refrigerants in
recovery units and especially not in cylinders. If compressors
or compressor oils are to be removed, ensure that they
have been evacuated to an acceptable level to make
certain that flammable refrigerant does not remain within
the lubricant. The evacuation process shall be carried out
prior to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be employed
to accelerate this process. When oil is drained from a
system, it shall be carried out safely.
Note About Fluorinated Gasses
-Fluorinated greenhouse gases are contained in
hermetically sealed equipment. For specific information
on the type, the amount and the CO
2
equivalent in tonnes
of the fluorinated greenhouse gas(on some models),
please refer to the relevant label on the unit itself.
-Installation, service, maintenance and repair of this unit
must be performed by a certified technician.
-Product uninstallation and recycling must be performed
by a certified technician.
7
EN
Preparation
8
control panel
handle
(both sides)
horizontal louver control
lever(adjust manually)
vertical louver control
lever(adjust manually)
panel
Caster
bottom tray
drain outlet
air filter
(behind the grille)
upper air intake
air outlet
lower air intake
drain outlet
NOTE: PHA can not be
adjusted.
NOTE: PHA can not be
adjusted.
rearfront
EN
Accessories
Check your window size and choose the fit window slider.
Installation
Choosing The Right Location
Recommend Installation
Your installation location should meet the following requirements:
-Make sure that you install your unit on an even surface to
minimize noise and vibration.
-The unit must be installed near a grounded plug, and the
Collection Tray Drain (found on the back of the unit) must be
accessible.
-The unit should be located at least 30cm (12”) from the nearest
wall to ensure proper air conditioning.
-DO NOT cover the Intakes, Outlets or Remote Signal Receptor
of the unit, as this could cause damage to the unit.
NOTE:
All the illustrations in the manual are for explanation
purpose only. Your machine may be slightly different.
The actual shape shall prevail.
The unit can be controlled by the unit control panel
alone or with the remote controller. This manual does
not include Remote Controller Operations, see the
<<Remote Controll Illustration>> packed with the unit
for details.
When there are wide differences between
“INSTRUCTION MANUAL” and “Remote controll
Illustration” on function description, the description on
“INSTRUCTION MANUAL ” shall prevail.
Tools Needed
-Medium Philips screwdriver; -Tape measure or ruler; -Knife or scissors; -Saw (optional, to shorten window
adaptor for narrow windows)
9
50cm
19.7inch
EN
Installation
10
Window Installation Kit
Press the exhaust hose into the window slider adaptor
and unit adaptor, clamp automatically by elastic buckles
of the adaptors.
Step One: Preparing the Exhaust Hose assembly
Step Two: Install the Exhaust hose assembly to the unit
Press into Press into
Step Three: Preparing the Adjustable Window Slider
1. Depending on the size of your window, adjust the size of the
window slider.
2. If the length of the window requires two window sliders, use the bolt
to fasten the window sliders once they are adjusted to the proper
length.
3. For some models, if the length of the window requires three window
sliders(optional), use two bolts to fasten the window sliders once they
are adjusted to proper length.
Window slider A Window slider B
Bolt
Part Description
1 pc
1 pc
1 pc
1 pc
1 pc
1 pc
1 pc
1 pc
2 pc
1 pc
1 pc
2 pc
1 set
1 set
Unit Adaptor
Window Slider Adaptor
Window Slider A
Window Slider B
Exhaust Hose
Bolt
Foam Seal A (Adhesive)
Foam Seal B (Adhesive)
Foam Seal C (Non-adhesive)
Security Bracket and Screw
Drain Hose
Quantity Part Description Quantity
Remote Controller
and Battery
4 set
Wall Exhaust Adaptor A
(only for wall installation)
Wall Exhaust Adaptor B(with cap)
(only for wall installation)
Screw and anchor
(only for wall installation)
NOTE: Items with are optional. Slight variations in design may occur.
*
*
*
*
*
*
*
Unit adaptor Window slider
adaptor
Exhaust hose Exhaust hose
assembly
Push the Exhaust hose into the airoutlet opening of the unit along the
arrow direction.
EN
Installation
11
3.Cut the non-adhesive foam seal C strip to match the width of the
window. Insert the seal between the glass and the window frame to
prevent air and insects from getting into the room.
4.If desired, install the security bracket with 2 screws as shown.
2 Screws
Security Bracket
Foam seal B
(Adhesive type-shorter)
Foam seal A
(Adhesive type)
Window slider A
Window slider B
(if required)
Foam seal C
(Non-adhesive type) Foam seal C
(Non-adhesive type)
2 Screws
Security
Bracket
Type 2: Wall Installation(optional)
1.Cut a 125mm (4.9inch) hole into the wall for the Wall
Exhaust Adaptor B. 2.Secure the Wall Exhaust Adaptor B
to the wall using the four Anchors and Screws provided in
the kit. 3.Connect the Exhaust Hose Assembly(with Wall
Exhaust Adaptor A) to the Wall Exhaust Adaptor B.
Note: Cover the hole using the
adaptor cap when not in use.
Note: To ensure proper function, DO NOT overextend or
bend the hose. Make sure that there is no obstacle around
the air outlet of the exhaust hose (in the range of 500mm)
in order to the exhaust system works properly. All the
illustrations in this manual are for explanation purpose only.
Your air conditioner may be slightly different. The actual
shape shall prevail.
max 120cm or 47 inch
min 30cm or 12 inch
Expansion anchor
position
Adaptor cap
Wall Exhaust
Adaptor B
Note: Once the Exhaust Hose assembly and Adjustable Window Slider
are prepared, choose from one of the following installation methods.
1.Cut the adhesive foam seal A and B strips to the
proper lengths, and attach them to the window sash
and frame as shown.
or
or
or
or
or
2.Insert the window slider assembly into the window opening.
Type 1: Hung Window or Sliding Window Installation(optional)
Foam seal B
(Adhesive type-shorter)
Foam seal A
(Adhesive type)
Window slider A
Window slider B
(if required)
5.Insert the window slider adaptor into the hole of the window slider.
EN
Note: For the usage of the ventilation grille/ damper bought
from the market, please refer to following signs to ensure
sufficient air flow volume:
Operation
12
Control panel
EN
Operation
13
MODE button
Selects the appropriate operating mode.
Each time you press the button, a mode
is selected in a sequence that goes from
COOL, FAN and DRY .The mode indicator
light illuminates under the different mode
setting.
NOTE: On above modes, the unit operates
the auto fan speed automatically. You can
set fan speed only by the remote controller
on COOL and FAN modes.
Used to adjust (increasing/decreasing)
temperature settings in 1°C/2°F(or 1°F)
increments in a range of 17°C/62°F to
30°C/88°F (or 86°F).
NOTE: The control is capable of displaying
temperature in degrees Fahrenheit or
degrees Celsius. To convert from one to
the other, press and hold the Up and Down
buttons at the same time for 3 seconds.
Power button
Power switch on/off.
Power
indicator light
Timer mode
indicator
light (set only by
remote controller)
Up (+) and Down (-) buttons
LED display
Shows the set temperature while on cool mode.
While on DRY and FAN modes, it shows the
room temperature.
Shows Error codes:
E1-Room temperature sensor error.
E2-Evaporator temperature sensor error.
E4-Display panel communication error.
EC-Refrigerant leakage detection malfunction
(on some models).
Shows protection code:
P1-Bottom tray is full--Connect the drain hose
and drain the collected water away.If protection
repeats,call for service.
Note: When one of the above malfunctions
occurs, turn off the unit, and check for any
obstructions. Restart the unit, if the malfunction is
still present, turn off the unit and unplug the
power cord. Contact the manufacturer or its
service agents or a similar qualified person for
service.
Operation Instructions
COOL operation
-Press the "MODE" button until the "COOL" indicator light
comes on.
-Press the ADJUST buttons "+" or "-" to select your desired
room temperature. The temperature can be set within a
range of 17°C~30°C/62°F~88°F(or 86°F).
-Press the "FAN SPEED" button on the remote cotroller to
choose the fan speed.
FAN operation
-Press the "MODE" button until the"FAN " indicator light
comes on.
-Press the "FAN SPEED" button on the remote cotrollerto
choose the fan speed. The temperature can not be
adjusted.
-Do not put the duct to window.
DRY operation
-Press the "MODE" button until the "DRY" indicator light
comes on.
-Under this mode, you cannot select a fan speed or adjust
the temperature. The fan motor operates at LOW speed.
-Keep windows and doors closed for the best dehumidifying
effect.
-Do not put the duct to window.
Exhaust hose installation
The exhaust hose and adaptor must be installed or
removed in accordance with the usage mode.
For COOL mode must be installed exhaust hose.
For FAN or DRY mode must be removed exhaust
hose.
EN
Operation
Other features
FOLLOW ME/TEMP SENSING feature(optional)
NOTE:This feature can be activated from the remote
control ONLY. The remote control serves as a remote
thermostat allowing for the precise temperature control
at its location. To activate the Follow Me/Temp Sensing
feature, point the remote control towards the unit and
press the Follow Me/Temp Sensing button. The remote
control will send this signal to the air conditioner until
press the Follow Me/Temp Sensing button again. If the
unit does not receive the Follow Me/Temp Sensing signal
during any 7 minutes interval, the unit will exit the
Follow Me/Temp Sensing mode.
NOTE: This feature is unavailabe under FAN or DRY
mode.
AUTO-RESTART
If the unit breaks off unexpectedly due to the power cut,it
will restart with the previous function setting automatically
when the power resumes.
WAIT 3 MINUTES BEFORE RESUMING OPERATION
After the unit has stopped, it can not be restarted
operation in the first 3 minutes. This is to protect the unit.
Operation will automatically start after 3 minutes.
14
SLEEP/ECO operation
This feature can be activated from the remote control
ONLY. To activate SLEEP feature, the set temperature
will increase by 1°C/2°F(or 1°F) in 30 minutes. The set
temperature will then increase by another 1°C/2°F
(or 1°F) after an additional 30 minutes. This new
temperature will be maintained for 7 hours before it returns to
the originally selected temperature. This ends the Sleep mode
and the unit will continue to operate as originally programmed.
NOTE: This feature is unavailabe under FAN or DRY mode.
AIR FLOW DIRECTION ADJUSTMENT
Adjust the air flow direction manually:
-The louver can be set to the desired position manually.
-Do not place any heavy objects or other loads on the
louver, doing so will cause damage to the unit.
-Ensure the louver is fully opened under heating
operation.
-Keep the louver fully opened during operation.
Bottom drain
plug
EN
Water drainage
-During dehumidifying modes, remove the drain
plug from the back of the unit
and p
lace the open
end of the hose directly over
the drain area in your
basement floor.
Continuous
drain hose
Remove the
drain plug
NOTE: Make sure the hose is secure so there are
no leaks. Direct the hose toward the drain, making
sure that there are no kinks that will stop the warter
flowing. Place the end of the hose into the drain and
make sure the end of the hose is down to let the
water flow smoothly. When the continuous drain
hose is not used, ensure that the drain plug and
knob are installed firmly to prevent leakage.
-When the water level of the bottom tray reaches a
predetermined level, the unit beeps 8 times, the
digital display area shows "P1" . At this time
the air conditioning/dehumidification process will
immediately stop. However, the fan motor will
continue to operate(this is normal). Carefully move
the unit to a drain location, remove the bottom
drain plug and let the water drain away. Reinstall
the bottom drain plug and restart the machine until
the "P1" symbol disappears. If the error repeats,
call for service.
NOTE: Be sure to reinstall the bottom drain plug
firmly to revent leakage before using the unit.
Maintenance
-Always unplug the unit before cleaning or servicing.
-DO NOT use flammable liquids or chemicals to clean the unit.
-DO NOT wash the unit under running water. Doing so
causes electrical danger.
-DO NOT operate the machine if the power supply was damaged
during cleaning. A damaged power cord must be replaced with a
new cord from the manufacturer.
Clean the Air Filter
WARNING:
15
Maintenance Tips
Clean the Unit
Store the unit when not in use
-Be sure to clean the air filter every 2 weeks for optimal performance.
-The water collection tray should be drained immediately after P1
error occurs, and before storage to prevent mold.
-In households with animals, you will have to periodically wipe down
the grill to prevent blocked airflow due to animal hair.
Clean the unit using a damp, lint-free cloth and mild
detergent. Dry the unit with a dry, lint-free cloth.
-Run the appliance on FAN mode for 12 hours in a warm room to dry
it and prevent mold.
-Turn off the appliance and unplug it.
-Clean the air filter according to the instructions in the previous
section. Reinstall the clean, dry filter before storing.
-Remove the batteries from the remote control.
-Drain the unit’s water collection tray according to the instructions in
the following section.
Be sure to store the unit in a cool, dark place. Exposure to direct
sunshine or extreme heat can shorten the lifespan of the unit.
CAUTION
DO NOT operate the unit without filter because dirt
and lint will clog it and reduce performance.
Remove the air filter
Air filter
(take out)
NOTE: The cabinet and front may be dusted with an oil-free
cloth or washed with a cloth dampened in a solution of
warm water and mildliquid dishwashing detergent. Rinse
thoroughly and wipe dry. Never use harsh cleansers, wax
or polish on the cabinet front. Be sure to wring excess
water from the cloth before wiping around the controls.
Excess water in or around the controls may cause
damage to the unit.
EN
16
Please check the machine according to the following form before asking for maintenance:
Faults Diagnosis
Problem Possible Cause
P1 Error Code
In COOL mode: room
temperature is lower than
the set temperature
The air filter is blocked with
dust or animal hair
The unit is low on
refrigerant
Temperature setting is too
high
The windows and doors in
the room are open
The room area is too large
Troubleshooting
Reset the temperature
Unit does not turn
on when pressing
ON/OFF button
Unit does not cool
well
The unit is noisy
and vibrates too
much
The unit makes a
gurgling sound
Exhaust hose is not
connected or is blocked
The Water Collection Tray is full.
Turn off the unit, drain the water
from the Water Collection Tray
and restart the unit.
There are heat sources
inside the room
Turn off the unit and clean the
filter according to instructions
Call a service technician to inspect
the unit and top off refrigerant
Decrease the set temperature
Make sure all windows and doors
are closed
Double-check the cooling area
Turn off the unit, disconnect the
hose, check for blockage and
reconnect the hose
Remove the heat sources if
possible
The ground is not level Place the unit on a flat, level
surface
The air filter is blocked with
dust or animal hair
Turn off the unit and clean the
filter according to instructions
This sound is caused by the
flow of refrigerant inside
the unit
This is normal
EN
17
Design and Compliance Notes
Design Notice
The design and specifications are subject to change without prior notice for
product improvement. Consult with the sales agency or manufacturer for details.
Any updates to the manual will be uploaded to the service website, please check
for the latest version.
Unit Temperature Range
Cool 17-35°C (62-95°F)
Dry 13-35°C (55-95°F)
Mode Temperature Range
Energy Rating Information
The Energy Rating for this unit is based on an installation using an un-extended exhaust duct without window
slider adaptor or wall exhaust adaptor A (as shown in the Installation section of this manual). At the same time,
the unit must be operate on the COOL MODE and HIGH FAN SPEED by remote controller.
EN
Sociable Remark
When using this unit in the European countries, the following information must be followed:
DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste
separately for special treatment is necessary.
It is prohibited to dispose of this appliance in domestic household waste.
For disposal, there are several possibilities:
A) The municipality has established collection systems, where electronic waste can be disposed of at
least free of charge to the user.
B) When buying a new product, the retailer will take back the old product at least free of charge.
C) The manufacture will take back the old appliance for disposal at least free of charge to the user.
D) As old products contain valuable resources, they can be sold to scrap metal dealers.
Wild disposal of waste in forests and landscapes endangers your health when hazardous substances
leak into the ground-water and find their way into the food chain.
18
EN
Email
Midea Europe GmbH
Ludwig-Erhard-Straße 14
65760 Eschborn
Tel 06196-9020 0
Midea Italia S.r.l. a socio unico
Viale Luigi Bodio 29/37
20158 Milano (MI)
Italia
Condizionatore portatile
(Condizionatore locale)
Manuale di istruzioni
Ti ringraziamo per aver acquistato il nostro condizionatore portatile.
Prima di mettere in funzione il condizionatore, si prega di leggere attentamente il manuale di istru-
zioni e conservarlo per futura referenza.
LEGGI E CONSERVA IL MANUALE DI ISTRUZIONI!
IT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

Comfee 2,6kW Portable Air Conditioner Manuale utente

Tipo
Manuale utente