MHSC VFC24L Install Manual

Categoria
Camini
Tipo
Install Manual

Questo manuale è adatto anche per

This is an unvented gas-red heater. It uses air
(oxygen) from the room in which it is installed.
Provisions for adequate combustion and venti-
lation air must be provided. Refer to Page 8.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future
reference.
Do not store or use gasoline or other
ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
– Do not try to light any appliance.
– Do not touch any electrical switch; do
not use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from
a neighbor's phone. Follow the gas
supplier's instructions.
– If you cannot reach your gas supplier,
call the re department.
Installation and service must be performed
by a qualied installer, service agency or
the gas supplier.
WARNING: If the information in this
manual is not followed exactly, a re or
explosion may result causing property
damage, personal injury or loss of life.
VFC Vent Free Fireplace System
Installation & Operating Instructions
Models: VFC24C, VFC24L, VFC32C & VFC32L
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
2
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
CONTENTS
Thank you and congratulations on your purchase of a Monessen Fireplace.
PLEASE READ THE INSTALLATION AND OPERATION INSTRUCTIONS
BEFORE USING THE APPLIANCE.
IMPORTANT: Read all instructions and warnings carefully before starting installation.
Failure to follow these instructions may result in a possible re hazard and will void the warranty.
Important Safety Information ...................................... 3
Codes ....................................................................... 4
Product Features .......................................................... 5
Operation ................................................................. 5
Gas Pressures ......................................................... 5
Gas Specications and Orice Sizes ....................... 5
Ignition Controls ....................................................... 5
Pilot .......................................................................... 5
Thermal Generator ................................................... 5
Cold Climate Option ................................................. 6
Fireplace And Framing Dimensions .......................... 7
Pre-Installation Information ......................................... 8
Getting Started ......................................................... 8
What You Will Need For Installation ......................... 8
Adequate Combustion and Ventilation Air ................ 8
Fireplace Installation .................................................... 9
Fireplace Location .................................................... 9
Clearances ............................................................. 10
Framing and Anchoring ...........................................11
Securing Heater to Floor or Hearth .........................11
Gas Line And Pressure .............................................. 12
Connecting the Gas Line ....................................... 12
Checking Gas Pressure Millivolt .......................... 12
Check Gas Pressure IPI ...................................... 13
Final Installation ......................................................... 13
Remove Screen ..................................................... 13
Install Canopy ........................................................ 13
Electrical Wiring – Millivolt ......................................... 14
Connect Optional Wall Switch or Thermostat ........ 14
Connect Remote Receiver ..................................... 15
Check System Operation ....................................... 15
Operating Instructions – Millivolt .............................. 16
For Your Safety Read Before Lighting ................... 16
What to do if You Smell Gas .................................. 16
Lighting Pilot For the First Time ............................. 16
Lighting Pilot .......................................................... 17
Lighting Burner ....................................................... 18
To Turn Off Gas ...................................................... 18
Electrical Installation – Ipi .......................................... 19
Electrical Wiring ..................................................... 19
Junction Box Wiring ............................................... 19
Wall Switch Installation .......................................... 20
IPI System Wiring Diagram .................................... 20
Operating Instructions – Ipi ........................................ 21
Operations and Indications .................................... 21
For Your Safety Read Before Lighting ................... 22
What to do if You Smell Gas .................................. 22
Operating Instructions ............................................ 22
To Turn Off Gas to Appliance ................................. 22
Electrical Wiring – Fan ................................................ 23
Log And Media Placement ......................................... 24
Cast Iron Grate Installation .................................... 24
Rock Wool Placement ............................................ 24
Log Placement (VFC24L/VFC32L Only) ................ 25
Glass Only Placement ........................................... 26
Flame Appearance ...................................................... 27
Pilot and Burner Flame Appearance ...................... 27
Checking the Pilot Flame ....................................... 27
Checking Burner Flame ......................................... 28
Operating Instructions ............................................ 28
Operating Instructions ............................................... 29
For Your Safety Read Before Lighting ................... 29
What to do if You Smell Gas .................................. 29
Millivolt/Thermostat Control Lighting Instructions .. 30
To Turn Off Gas to Heater ...................................... 30
Match Lighting Instructions .................................... 31
Blower Operation ................................................... 31
Cleaning And Servicing ............................................. 32
Annual Cleaning/Inspection ................................... 32
Periodic Cleaning ................................................... 32
Optional Accessories ................................................. 33
Forced Air Kit ......................................................... 33
Installing Optional Firebrick Panels ........................ 33
Installing Optional Porcelain Panels ...................... 34
Installing Optional Black Magic Panels .................. 34
Troubleshooting ......................................................... 35
Replacement Parts ..................................................... 38
VFC Firebox Parts ................................................. 38
VFC24 Millivolt Burner Parts .................................. 39
VFC24 IPI Burner Parts ......................................... 40
VFC32 Millivolt Burner Parts .................................. 41
VFC32 IPI Burner Parts ......................................... 42
Replacement Logs ................................................. 43
Warranty ...................................................................... 44
3
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
IMPORTANT SAFETY INFORMATION
INSTALLER
Please leave these instructions with the appliance.
OWNER
Please retain these instructions for future reference
.
WARNING:
Any change to this heater or its controls can be dangerous.
Improper installation or use of the heater can cause serious injury or death from re, burns,
explosion or carbon monoxide poisoning.
Do not allow fans to blow directly into the replace. Avoid any drafts that alter burner ame
patterns.
Do not use a blower insert, heat exchanger insert or other accessory, not approved for use with
this heater where applicable.
13. Avoid any drafts that alter burner ame patterns. Do not
allow fans to blow directly into replace. Do not place
a blower inside burn area of rebox. Ceiling fans may
create drafts that alter burner ame patterns. Sooting
and improper burning will occur.
14. CAUTION: Candles, incense, oil lamps, etc. produce
combustion byproducts including soot. Vent-free
appliances will not lter or clean soot produced by
these types of products. In addition, the smoke and/
or aromatics (scents) may be reburned in the vent-free
appliance which can produce odors. It is recommended
to minimize the use of candles, incense, etc. while the
vent-free appliance is in operation.
15. This is an unvented gas-fired heater. It uses air
(oxygen) from the room in which it is installed. Provi-
sions for adequate combustion and ventilation air must
be provided.
16. This heater shall not be installed in a room or space
unless the required volume of indoor combustion air is
provided by the method described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International
Fuel Gas Code or applicable local codes.
17. Keep room area clear and free from combustible mate-
rials, gasoline and other ammable vapors and liquids.
18. Unvented gas heaters are a supplemental zone heater.
They are not intended to be the primary heating appli-
ance.
19. Unvented gas heaters emit moisture into the living
area. In most homes of average construction, this
does not pose a problem. In houses of extremely
tight construction, additional mechanical ventilation is
recommended.
20. During manufacturing, fabricating and shipping, various
components of this appliance are treated with certain
oils, lms or bonding agents. These chemicals are not
harmful but may produce annoying smoke and smells
as they are burned off during the initial operation of the
appliance; possibly causing headaches or eye or lung
irritation. This is a normal and temporary occurrence.
1. Due to high temperatures, the appliance should be
located out of trafc and away from furniture and
draperies.
2. Children and adults should be alerted to the hazard
of high surface temperature and should stay away
to avoid burns or clothing ignition.
3. Young children should be carefully supervised when
they are in the same room with the appliance.
4. Do not place clothing or other ammable material
on or near the appliance.
5. Any safety screen or guard removed for servicing
an appliance, must be replaced prior to operating
the heater.
6. Installation and repair should be done by a qualied
service person.
7. To prevent malfunction and/or sooting, an unvented
gas heater should be cleaned before use and at
least annually by a professional service person.
More frequent cleaning may be required due to
excessive lint from carpeting, bedding materials,
etc. It is imperative that control compartments,
burners and circulating air passageways be kept
clean.
8. CARBON MONOXIDE POISONING: Early signs of
carbon monoxide poisoning are similar to the u with
headaches, dizziness and/or nausea. If you have these
signs, obtain fresh air immediately. Have the heater
serviced as it may not be operating properly.
9. The installation must conform with local codes or, in
the absence of local codes, with the National Fuel
Gas Code, ANSI Z223.l/NFPA54.
10. This unit complies with the latest edition of ANSI
Z21.11.2–2013, Unvented Heaters.
11. Do not install the heaters in a bathroom or bedroom.
12. Correct installation of the refractory cement logs,
proper location of the heater, and annual cleaning are
necessary to avoid potential problems with sooting.
Sooting, resulting from improper installation or opera-
tion, can settle on surfaces outside the replace. See
log placement instructions for proper installation.
4
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
IMPORTANT SAFETY INFORMATION
CODES
Adhere to all local codes or, in their absence, the latest edition of THE NATIONAL FUEL GAS CODE ANSI Z223.1 or
NFPA54 which can be obtained from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
or
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
The initial break-in operation should last six hours with
the burner at the highest setting. Provide maximum
ventilation by opening windows or doors to allow
odors to dissipate. Any odors remaining after this initial
break-in period will be slight and will disappear with
continued use.
21. Input ratings are shown in BTU per hour and are for
elevations up to 2,000 feet. For elevations above 2,000
feet, input ratings should be reduced 4 percent for each
1,000 feet above sea level. Refer to the National Fuel
Gas Code.
22. The appliance must be isolated from the gas supply
piping system by closing its equipment shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 psig
(3.5 kPa).
23. Do not use this room heater if any part has been under
water. Immediately call a qualied service technician
to inspect the room heater and to replace any part of
the control system and any gas control which has been
under water.
24. Never burn solid fuels in a replace where a unvented
room heater is installed.
25. Always have a replace screen in place when the
appliance is in operation and, unless other provisions
for combustion air are provided, the screen must have
an opening(s) for induction of combustion air.
THIS APPLIANCE MAY BE INSTALLED IN AN
AFTER-MARKET, PERMANENTLY LOCATED,
MANUFACTURED (MOBILE) HOME, WHERE
NOT PROHIBITED BY LOCAL CODES.
THIS APPLIANCE IS ONLY FOR USE WITH THE
TYPE OF GAS INDICATED ON THE RATING
PLATE. THIS APPLIANCE IS NOT CONVERT-
IBLE FOR USE WITH OTHER GASES.
Nous recommandons que nos
appareils de chauffage au gaz
soient installés et entretenus par
des professionnels qui ont été
accrédités aux È.U. par le National
Fireplace Institute ® (NFI) comme
étant des spécialistes du NFI en
matièred’appareils de chauffage
au gaz.
WARNING: Never connect unit to
private (non-utility) gas wells. This gas
is commonly known as wellhead gas.
WARNING: This product and the
fuels used to operate this product (liquid
propane or natural gas), and the products
of combustion of such fuels, can expose
you to chemicals including benzene, which
is known to the State of California to cause
cancer and reproductive harm. For more
information go to: www.P65Warnings.
ca.gov.
5
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
PRODUCT FEATURES
OPERATION
This unvented gas heater requires no outside venting
and burns cleanly with excellent heating efciency. As a
zero-clearance appliance, it can be installed against (or
recessed into) any wall that is accessible to a gas line.
Piezo Ignition
Fireplace
Screen
Control Knobs
Figure 1. VFC Shown with Control Access Door Open
On/Off Switch
GAS PRESSURES
Control Fuel Millivolt and IPI
Regulator Pressure Nat. 3.5" w.c.
Pilot Regulator Nat. 3.5" w.c.
Max. Inlet Pressure Nat. 10.5" w.c.
Min. Inlet Pressure Nat. 5.0" w.c.
Regulator Pressure LP 10.0" w.c.
Max. Inlet Pressure LP 13.0" w.c.
Min. Inlet Pressure LP 11.0" w.c.
GAS SPECIFICATIONS AND ORIFICE SIZES
NOTE: For LP models an external regulator is required
to reduce supply pressure to a maximum of 13" w.c.
MODEL FUEL CONTROL
MAX
BTU
MIN
BTU
ORIFICE
SIZE
VFC24CNV NAT MILLIVOLT 22,000 16,000 2.35mm
VFC24CPV LP MILLIVOLT 22,000 20,000 1.45mm
VFC24CNI NAT IPI 22,000 16,000 2.35mm
VFC24CPI LP IPI 22,000 20,000 1.45mm
VFC24LNV NAT MILLIVOLT 22,000 16,000 2.35mm
VFC24LPV LP MILLIVOLT 22,000 20,000 1.45mm
VFC24LNI NAT IPI 22,000 16,000 2.35mm
VFC24LPI LP IPI 22,000 20,000 1.45mm
VFC32CNV NAT MILLIVOLT 28,000 19,000 #38
VFC32CPV LP MILLIVOLT 27,000 22,000 #52
VFC32CNI NAT IPI 28,000 19,000 #38
VFC32CPI LP IPI 27,000 22,000 #52
VFC32LNV NAT MILLIVOLT 28,000 19,000 #38
VFC32LPV LP MILLIVOLT 27,000 22,000 #52
VFC32LNI NAT IPI 28,000 19,000 #38
VFC32LPI LP IPI 27,000 22,000 #52
IGNITION CONTROLS
Piezo ignitor allows ignition of the pilot without the use of
matches or batteries.
Millivolt and EcoLogic® 2.0 controls have four (4)
positions:
OFF - All gas to the gas logs is shut off at the
valve.
IGN - Valve position to light/maintain a standing
pilot.
ON - Valve position to turn ON/OFF log set with
remote switch/thermostat.
LOW/HI - Variable position to control ame height
(heat output).
PILOT
The gas log heater is tted with a specially designed safety
pilot light (ODS assembly) which senses the amount of
oxygen available in the room and shuts the gas log heater
off if the oxygen level begins to drop below a satisfactory
level. The pilot can only be re-lit when adequate fresh air
is available.
THERMAL GENERATOR
The millivolt gas log pilot is tted with a millivolt generator
to provide power for remote activation.
6
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
COLD CLIMATE OPTION (IPI Models Only)
NOTE: If you live in a cold climate, seal all cracks around
your appliance and wherever cold air could enter the room,
with noncombustible material. It is especially important to
insulate the outside chase cavity between the studs and
under the oor on which the appliance rests, if the oor is
above ground level.
Your replace is equipped with an intermittent pilot ignition
(IPI) control. An IPI control with a standing pilot option pro-
vides the dual benet of an economical and environmentally
responsible product and one which lights easily even in
the coldest climates. When in intermittent pilot mode (as
it comes from the factory), your pilot remains unlit until
needed, saving you fuel. Standing pilot mode, by com-
parison, is characterized by a continuously burning pilot.
The benet of a pilot which lights only when needed is fuel
savings. However, with no pilot burning in your replace,
units operating in colder climates may experience delayed
start up or lock out. Because colder air is heavier than
milder air and there is no pilot burning to maintain a warm
stable temperature in your rebox, establishing a draft to
aid ignition becomes difcult. This is perfectly normal but
can be somewhat frustrating.
To remedy this issue, your replace has been designed with
a cold climate pilot option, which, when active, maintains
a warmer temperature inside your rebox to make ignition
faster and more efcient. Operating your appliance in cold
climate (aka standing) pilot mode will prohibit the need for
multiple ignition attempts and will prevent the system from
delaying start up or locking out.
To activate the cold climate option, simply move the cold
climate toggle switch located on the right side of the black
control center to the “On” (left) position. (Figure 2) You can
operate your appliance in this mode regardless of whether
you are using a remote control, wall switch or thermostat.
Cold Climate
Switch
Master Switch
PRODUCT FEATURES
Figure 2. Cold Climate Option
7
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
O - Min. Rough Opening Width
Min. Rough
Opening
Depth
1/2”
or 5/8”
Min. Rough
Opening
Height
L
334051
VFS DBX dims
A
B
C
D
H
E
F
G
J
P
S
R
Q
S
I
N
M
K
FIREPLACE AND FRAMING DIMENSIONS
Figure 3. Fireplace and Framing Dimensions
Ref. VFC24 VFC32
A 2458" (625 mm) 32" (813 mm)
B2258" (575 mm) 2834" (730 mm)
C2612" (673 mm) 30" (762 mm)
D 19" (482 mm) 2534" (654 mm)
E 1614" (413 mm) 1912" (495 mm)
F412" (114 mm) 534" (146 mm)
G 478" (124 mm) 5" (127 mm)
H 1412" (368 mm) 1412" (368 mm)
I 1" (25 mm) 158" (41 mm)
J 1318" (333 mm) 1318" (333 mm)
K1138" (289 mm) 1138" (289 mm)
L 16" (406 mm) 1712" (445 mm)
M2234" (578 mm) 2834" (730 mm)
Framing Dimensions
N 2634" (680 mm) 3014" (768 mm)
O 2518" (638 mm) 3212" (826 mm)
P1338" (340 mm) 1338" (340 mm)
Q4478" (1140 mm) 58" (1478 mm)
R 24" (610 mm) 2914" (743 mm)
S 3212" (826 mm) 41" (1041 mm)
Model Pounds
VFC24LNV/CNV 72
VFC24LPV/CPV 72
VFC24LNI/CNI 56
VFC24LPI/CPI 56
VFC32LNV/CNV 55
VFC32LPV/CPV 58
VFC32LNI/CNI 78
VFC32LPI/CPI 78
8
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
GETTING STARTED
Make sure you have received all parts:
Check your packing list to verify that all listed parts have
been received. You should have the following:
Unvented gas heater
Installation/operating instruction
Four (4) black screws
Canopy and three (3) screws
Two (2) anchoring screws
Refractory cement logs or glass media
Carefully inspect the contents for shipping damage. If any
parts are missing or damaged, immediately inform the
dealer from whom you purchased the appliance. Do not
attempt to install any part of the appliance unless you
have all parts in good condition.
WHAT YOU WILL NEED FOR INSTALLATION:
You must have the following items available before pro-
ceeding with installation:
External regulator (for propane/LPG only)
Manual shutoff valve
Piping which complies with local codes
Sediment trap
Phillips head screwdriver
Tee joint
Pipe sealant approved for use with propane/LPG
Pipe wrench (resistant to sulfur compounds)
When planning the installation for the replace it is nec-
essary to determine where the unit is to be installed and
whether optional accessories are desired. Gas supply
piping should also be planned. The following steps repre-
sent the normal sequence of installation. Each installation
is unique, however, and might require a different sequence.
1. Position fireplace in desired location. Refer to the
Location of Fireplace and Clearances and Height
Requirements, and Firebox Framing sections found in
this manual.
PRE-INSTALLATION INFORMATION
Gloves are recommended when handling
refractory cement logs to prevent skin
irritation from loose bers. Logs are fragile
— handle with care.
WARNING: WARNING—Do not install the heater:
Where curtains, furniture, clothing, or
other ammable objects are less than
42" from the front of the heater.
In high trafc areas.
In windy or drafty areas.
WARNING: If the area in which the heater
is operated does not meet the required
volume for indoor combustion air, combustion
and ventilation air shall be provided by one of
the methods described in the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, the International
Fuel Gas Code or applicable local codes.
NOTE: Be sure all packing material has been removed
from underside the unit.
2. Install canopy and logs per instructions found in this
manual. The canopy MUST be installed for safe oper-
ation of the unit.
3. Field wire main power supply to units with fan kit. Refer
to the Electrical Section found in this manual. (Electrical
connections should only be performed by an experi-
enced, licensed certied tradesman).
4. Install optional ON/OFF kit on units with millivolt control.
Refer to the installation instructions included with the
kit and also refer to the Electrical Wiring section found
in this manual.
5. Plumb gas line. Refer to the Connecting the Gas sec-
tion found in this
manual. (Gas connections should only be performed
by an experienced,
licensed/certied tradesman).
6. Complete nish wall material and/or surround.
ADEQUATE COMBUSTION AND VENTILA-
TION AIR
This heater shall not be installed in a conned space or
unusually tight construction unless provisions are provided
for adequate combustion and ventilation air.
The National Fuel Gas Code, (ANSI Z223.1/NFPA54),
denes a conned space as a space whose volume is less
than 50 cubic feet per 1,000 BTU per hour (4.8m3 per kw)
of the aggregate input rating of all appliances installed in
that space, and an unconned space as a space whose
volume is not less than 50 cubic feet per 1,000 BTU per
hour (4.8 m3 per kw) of the aggregate input rating of all
appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed,
through openings not furnished with doors, are considered
a part of a conned space.
9
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
FIREPLACE INSTALLATION
FIREPLACE LOCATION
Carefully select the best location for installation of your
unvented replace. The following factors should be taken
into consideration.
Clearance to side wall, ceiling, woodwork and
window or other combustibles. Refer to Clearances
section. Minimum clearances to combustibles must
be maintained.
Location must not be affected by drafts caused by
kitchen exhaust fans, ceiling fans, return air registers
for forced air furnaces / air conditioners, windows or
doors.
Installation must provide adequate ventilation and
combustion air.
DO NOT INSTALL THESE MODELS IN A BED-
ROOM OR BATHROOM.
Location should be out of high trafc areas and
away from furniture and draperies due to heat
from rebox.
Never obstruct the front opening of the unvented
replace or restrict the ow of combustion and ven-
tilation air.
Minimize modications to existing construction. Refer
to Figure 5 below for location suggestions.
Do not install in the vicinity where gasoline or other
ammable liquids may be stored. The unvented re-
box must be kept clear and free from the combustible
materials.
FP2440
fireplace locations
W
H
Counter
Fireplace
Unusually tight construction is dened as construction
where:
a. walls and ceilings exposed to the outside atmosphere
have a continuous water vapor retarder with a rating of
1 perm (6 x 1011 kg per pa/sec-m2) or less with openings
gasketed or sealed, and
b. weather stripping has been added on openable windows
and doors, and
c. caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates
and oors, between wall-ceiling joints, between wall
panels, at penetrations for plumbing, electrical and gas
lines and other openings.
The following formula can be used to determine the maxi-
mum heater rating per the denition of unconned space:
BTU/Hr = (L1 + L2) Ft x (W) Ft x (H) Ft
50
Consider two connecting rooms with an open area
between, with the following dimensions:
L1 = 151/2 Ft., L2 = 12 Ft., W = 12 Ft., H = 8 Ft.
BTU/Hr = (151/2 + 12) x (12) x (8)
50
If there were a door between the two rooms the calculation
would be based only on the room with the heater.
BTU/Hr = (151/2) x (12) x (8)
50
Figure 4. Combustion Air Calculation Figure 5. Possible Fireplace Loca-
tions
10
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
FIREPLACE INSTALLATION
2¹⁄₂
12”
10”
19”
FP2508
VFS DBX mantel clearances
Canopy
FP2508
Figure 7. Mantel Clearances
WARNING: The dimensions shown
in Figures 6, 7 and 8 are minimum
clearances to maintain in installing this heater.
Left and right clearances are determined when
facing the front of the heater.
Follow these instructions carefully to ensure
safe installation. Failure to follow instructions
exactly can create a re hazard.
CLEARANCES
Ensure that minimum clearances shown in Figure 6 and
Figure 7 are maintained. Left and right clearances are
determined when facing the front of the rebox.
Follow these instructions carefully to ensure safe instal-
lation. Failure to follow these requirements may create a
re hazard.
Sidewall ClearancesThe clearance from the inside of
the appliance to any combustible adjacent wall should not
be less than 9" for the VFC24 and VFC32. Figure 6
Ceiling Clearance The ceiling must be at least 42" from
the top of the rebox opening. Figure 6
Back Wall Clearance The appliance may be placed
against a combustible back wall.
Floor Clearance The replace may be installed directly
on a combustible oor or a raised platform of an appropri-
ate height. Do not place replace on carpeting, vinyl, tile or
other soft oor coverings. It may, however, be placed on at
wood, plywood, particle board or other hard surfaces. Be
sure replace rests on a solid continuous oor or platform
with appropriate framing for support and so that no cold
air can enter from under the rebox.
Mantel clearances — The canopy supplied with the unit
must be installed. If a combustible mantel is installed. It
must meet the clearance requirements detailed in Figure 7
NOTE: The Monessen Barrington cabinet model series
BWC300, BWC400 and BWC500 are specially designed
to comply with all mantel temperature requirements. Any
custom-built mantel must comply with all clearance require-
ments shown in this instruction manual.
9"
Minimum
9"
Minimum
42" Minimum
FP2441
sidewall clg clear
Figure 6. Sidewall and Ceiling Clearances Figure 8. Mantel Leg Clear-
ances
45°
1”
2¹⁄₂
3”
5”
6”
1¹⁄₂
3¹⁄₂
4¹⁄₂
FP2692
mantel leg clearance
6”
7¹⁄₂
7¹⁄₂
9”
Finish Wall
Combustible
Material Area
11
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
FP2509
nailing flanges
Nail Sides
Through Nailing
Flanges
Figure 9. Vinyl Flooring Exception
FIREPLACE INSTALLATION
SECURING HEATER TO FLOOR OR
HEARTH
NOTE: Clearance requirements as detailed in the
Clearances section on of this manual, must be met before
securing the heater in place.
To prevent movement, the heater must be secured to the
oor or hearth.
1. Open the control access door and remove the screen.
2.
Secure the rebox with two anchoring screws (
316
" x 1
14
"
length) supplied with the replace system. Figure 11.
NOTE: If the unit is mounted on carpeting, tile or
combustible material without the hearth, a metal or wooden
base covering the entire width and depth of the base must
be installed.
Figure 10. Nailing Flanges
FRAMING AND ANCHORING
If unit is to be “built in”, replace framing can be built before
or after the appliance is set in place. BE SURE THAT ALL
PACKING MATERIAL HAS BEEN REMOVED FROM THE
UNDERSIDE OF THE UNIT PRIOR TO SETTING THE
FIREBOX IN PLACE. Construct replace framing following
Fireplace and Framing Dimensions. The framing headers
may rest directly on top of the rebox.
The replace may be installed directly on a combustible
oor or a raised platform of an appropriate height. Do
not place replace on carpeting, vinyl, tile or other soft
oor coverings. It may, however, be placed on at wood,
plywood, particle board or other hard surfaces. Be sure
replace rests on a solid continuous oor or platform with
appropriate framing for support and so that no cold air can
enter from under the rebox.
Anchor replace to the side framing members using nailing
anges.
1. Bend out the nailing anges located on each side of the
rebox.
2. Slide the rebox into prepared framing or position rebox
in its nal position and frame later.
3. Level the rebox by checking the top edge of the rebox.
Shim if necessary.
WARNING: The replace must be installed
giving full consideration to the clearance
and height requirements identified in this
manual.
Anchor Screws
316" x 114"
VINYL FLOORING
Vinyl Flooring is sensitive to heat. A 14 inch minimum
depth hearth extension is recommended when using vinyl
ooring up to the wall. See Figure 9.
NOTICE: Clearances that do not meet the minimum
guidelines could result in damage or buckling to the vinyl
ooring and is done at the installer's risk.
Hearth and Home Technologies does not recommend
adhesive based vinyl ooring due to thermal expansion.
Floating-style ooring can be used, but will reach tempera-
tures up tp 110°F in a room with ambient temperature of
70°F. Consult ooring specications to ensure compati-
bility.
4. Anchor rebox to the side framing members using 8d
nails or other suitable fasteners. Figure 10
5. The canopy must be installed for safe operation of the
heater. Refer to canopy installation details.
Vinyl Flooring
Firebox width min.
14 in. min.
Figure 11. Secure Fireplace to Floor or Hearth
FP2781
millivolt valve
Test Port
"OUT"
12
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
CONNECTING THE GAS LINE
NOTICE: A qualied gas appliance installer must connect
the heater to the gas supply. Consult all local codes.
GAS LINE & PRESSURE
FP2447
gas connection
3” Min.
To Fireplace
Pipe Coupling
Stainless
Flexible Tube
Pipe
Locations Pressure
Tapping Point Instal-
lation
Manual Shutoff
Valve
Gas Supply
Inlet
Figure 12. Gas
Connection
IMPORTANT: Loosen the pipe adapter on the ex tube
before installing to the system piping.
Always use an external regulator for all propane/LPG heat-
ers only, to reduce the supply tank pressure to a maximum
of 13" w.c. This is in addition to the internal regulator in the
heater valve.
To reach factory installed ex line, go through access door
on right or left side of rebox.
Figure 13. Access Holes
Manual Gas Shutoff
(Recommended Outlet
Positioned Vertical)
Stainless Flex Line
Access Door
for Gas Line
WARNING: Connecting directly to an
unregulated propane/LPG tank can
cause an explosion
WARNING: Use new black iron or
steel pipe. Internally tinned copper or
copper tubing can be used per National
Fuel Code, section 2.6.3, providing gas meets
hydrogen sulde limits, and where permitted by
local codes. Gas piping system must be sized to
provide minimum inlet pressure (Listed on Data
Plate) at the maximum ow rate (BTU/hr). Undue
pressure loss will occur if the pipe is too small.
A manual shutoff valve must be installed
upstream of the appliance. Union tee and
plugged 1/8" NPT pressure tapping point should
be installed upstream of the appliance. Figure 12
WARNING: CHECK GAS TYPE: The
gas supply must be the same as stated
on the heaters rating plate. If the gas
supply is different, DO NOT INSTALL THE
HEATER. Contact your dealer for the correct
model. Connecting to the wrong gas type may
result in property damage or personal injury.
The stainless ex line is on the right side facing the re-
place and can connect to either a 3/8 NPT female or 1/2
NPT male pipe. To connect from the opposite side, route
the pipe under the rear portion of the unit.
Test all gas joints from the gas meter to the heater valve for
leaks using a gas analyzer or soap and water solution after
completing connection. DO NOT USE AN OPEN FLAME.
Check the gas pressure with the appliance burning and
the control set to HIGH.
Open control access door on either side of unit to nd valve
and regulator referred to below. Figure 13
CHECKING GAS PRESSURE – MILLIVOLT
CONTROL
Figure 12
The valve regulator controls the burner pressure which
should be checked at the pressure test point.
Turn captured screw counter clockwise two or three turns
and then place tubing
to pressure gauge over
test point (Use test point
“OUT” closest to con-
trol knob). After taking
pressure reading, be
sure and turn captured
screw clockwise firmly
to re-seal. Do not over
torque. Check for gas
leaks.
Figure 14. Pressure Test Point Location Millivolt Control
13
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
CHECK GAS PRESSURE – IPI
1. Check gas type. The gas supply must be the same as
stated on the appliance’s rating decal. If the gas supply
is different from the replace, STOP! Do not install the
appliance. Contact your dealer immediately.
2. To facilitate easier installation, a 18" (610 mm) ex line
with manual shut-off valve has been provided with this
appliance. Install and attach 1/2" gas line onto shut-off
valve.
3. After completing gas line connection, purge air from
gas line and test all gas joints from the gas meter to the
replace for leaks. Use a solution of 50/50 water and
soap solution or a gas sniffer.
4. To check gas pressures at valve, turn captured screw
counter clockwise 2 or 3 turns and then place tubing to
pressure gauge over test point. Turn unit to high. Fig-
ure 14 After taking pressure reading, be sure and turn
captured screw clockwise rmly to reseal. Do not over
torque. Check test points for gas leaks.
Figure 15. IPI Valve
Pressure Inlet
Pilot Adjust-
ment Screw
Pressure
Outlet
FP3034
FINAL INSTALLATION
REMOVE SCREEN
NOTE: Fireplace screen must be removed to access log
box and to install canopy.
Figure 16
1. Remove bottom access panel.
2. Removing replace screen frame panel by pushing
screen frame panel up and out.
3. Remove log box, canopy and log support.
4. Remove and discard logs support and screws. Figure
16a.
INSTALL CANOPY
Figure 16a
1. Align the black canopy with the holes in the top frame
assembly.
2. Install the three (3) screws (in owner’s manual packag-
ing) which attach the canopy to the top frame assembly.
3. Tighten all screws. Make sure the canopy is level and
secure.
Canopy
WARNING: Do not operate the unit with-
out the screen frame panel and canopy
installed.
Screws
Fireplace
Screen
Canopy
WARNING: Do NOT use open ame
to check for gas leaks. Figure 16. Remove Fireplace Screen Panel
Figure 17. Install
Canopy
Figure 15a
Log Support
Screws
14
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
Figure 18. Wiring
Diagram
FP2112a
wiring diagram
8/09
Field Installed Optional
Wall Switch or
Remote Receiver
Switch
On/Off
Switch
On/Off
Switch
ODS Pilot
Valve
ODS
Pilot
Spade
Terminal
FP2112a
TH = 3
TP = 1
TP/TH = 2
The millivolt valve is a self-powered combination gas con-
trol THAT DOES NOT REQUIRE 110V AC TO OPERATE.
Refer to Figure 17 and installation instructions provided
with optional wall switch, thermostat or remote control for
wiring instructions. A maximum length of 15 feet of 18awg
two conductor wire is to be used for wall switch or ther-
mostat installations.
NOTE: Thermostats and switches must be suitable for
millivolt operation.
CONNECT OPTIONAL WALL SWITCH OR
THERMOSTAT
1. Use 18 awg, two-wire cable, 15 feet maximum length.
2. At one end of the cable, connect both wires to the wall
switch or thermostat. At the other end, connect one
wire to TP/TH and one wire to TH, or connect the wall
switch/thermostat to the two male (0.25") terminals on
the left side of the unit. The color of the wires does not
matter.
WARNING: Do NOT connect wall
switch to 110 V circuit.
WARNING: Label all wires prior to
disconnection when servicing controls.
Wiring errors can cause improper and
dangerous operation. Verify proper operation
after servicing.
ELECTRICAL WIRING — MILLIVOLT
15
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
Figure 19. Install Remote Receiver
Check
Test
To
Test
Connect Meter
Leads to
Terminals
Switch or
Thermostat
Contacts
Meter Reading
Should Be
AComplete
System 2 & 3 Closed Closed
BThermopile
Output 1 & 2 Open Open
CONNECT REMOTE RECEIVER
THESE INSTRUCTIONS SUPERCEDE THE SECTION
ENTITLED “HEARTH MOUNT” IN THE MILLIVOLT
HAND-HELD REMOTE INSTRUCTIONS SUPPLIED
WITH THE REMOTE.
Figure 18
1. Remove bottom control door.
2. Connect the remote connector wires located in the unit
to the remote receiver.
3. Stick Velcro® pads with self-adhesive backing to bottom
of remote receiver and to oor of compartment behind
access panel.
4. Attach remote receiver to rebox with Velcro® pads.
Control switch must face forward.
NOTE: Do not place remote in combustion chamber,
only the remote receiver.
CHECK SYSTEM OPERATION
The millivolt system and individual components may be
checked with a millivolt meter having a 0-1000 mV range.
Conduct each check shown in chart below by connection
meter test leads to terminals as indicated.
A. COMPLETE MILLIVOLT SYSTEM CHECK
(“A” Reading: Thermostat contacts CLOSED,
control knob “ON,” main burner should turn ON)
a. If the reading is more than 100 millivolts and the
automatic valve still does not come on, replace the
control.
b. If the closed circuit reading (“A” reading) is less than
100 millivolts, determine cause for low reading, pro-
ceed to Section B below.
B. Thermopile Output Reading Check
(“B” Reading: Thermostat contacts OPEN, main
burner OFF)
1. Check gas pressure to the unit. If gas pressure is
within minimum and maximum on data plate, then
check pilot voltage, 325 millivolts minimum. If the
minimum millivolt reading is not obtainable, replace
pilot.
ELECTRICAL WIRING — MILLIVOLT
Remote Receiver
16
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
OPERATING INSTRUCTIONS—MILLIVOLT
A. This appliance is equipped with a pilot which must be lit with built-in piezo ignitor while following these
instructions exactly.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the oor
because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS:
Turn off all gas to the appliance.
Open windows.
Do not attempt to light any appliance.
Do not touch any electric switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the re department.
C. Use only your hand to push in, or turn the gas control knob. Never use tools. If the knob will not push
in or turn by hand, don't try to repair it. Call a qualied service technician. Force or attempted repair
may result in a re or explosion.
D. Do not use this appliance if any part of it has been under water. Immediately call a qualied service
technician to inspect the appliance and to replace any part of the control system and any gas control
that has been under water.
FOR YOUR SAFETY READ BEFORE LIGHTING
LIGHTING PILOT FOR THE FIRST TIME
INITIAL LIGHTING
Purge air from the supply line as follows:
Open main shutoff valve.
Unscrew main pressure test point.
Leave inlet test screw open until gas comes in.
When gas is owing, tighten inlet screw immediately.
LEAK TESTING
1. Follow the pipe from the gas supply line connection to the gas valve. Check connection for leaks
with soap and water mixture.
2. Next check for gas leaks at the burner with soap and water mixture.
3. Check the pilot for gas leaks with soap and water mixture.
WARNING: If you do not follow these instruction exactly, a re or explosion may result
causing property damage, personal injury or loss of life.
WARNING: NEVER use open ame
to check for gas leaks.
17
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
OPERATING INSTRUCTIONS—MILLIVOLT
PILOT
O
F
F
P
I
L
O
T
O
N
FP1935
control knob pilot
Continued on next page
APPROVED LEAK TESTING METHOD
You may check for gas leaks with the following methods only:
Soap and water solution
An approved leak testing spray
Electronic sniffer
NOTE: Remove any excessive pipe compound from the connections. Excessive pipe compound
can set off electronic sniffers.
1. Depress and turn knob counterclockwise to pilot position.
2. Depress fully and hold pilot gas knob. Depress piezo igniter as many times as needed to ignite pilot.
Keep knob fully depressed for a few seconds. Release and check that pilot continues to burn.
If the pilot does not stay lit, repeat steps 1 and 2.
LIGHTING PILOT
Pilot Position
Check for gas leaks in each of the following locations:
Pipe from the gas supply line connection to the gas valve
Burner connections Field made joints / gas shutoff valve
Pilot Factory made joints
Each joint or connection All joints on valve and control body
LIGHTING PILOT FOR THE FIRST TIME
WARNING: NEVER use open ame
to check for gas leaks.
WARNING: If using a soap and water
solution to test for leaks, DO NOT
spray solution onto control body.
WARNING: The control has an interlock device that does not allow the lighting of the
replace up to the moment the safety device of the ame has not interrupted the gas
ow. After that period of time (when the magnet is closed), it is possible to start the
lighting operation.
The gas control knob is designed to be operated by hand. DO NOT use any tools during this
operation. Damaged knobs may result in serious injury.
18
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
PILOT
O
F
F
P
I
L
O
T
O
N
Wall Switch
LIGHTING BURNER
LIGHTING THE BURNER
Depress and turn the knob counterclockwise to the “ON” position.
It will take less than four (4) seconds for the burner to ignite.
MAIN BURNER SWITCH
This switch allows you to turn on and to turn off the main burner
without using the gas valve knob. is in the “ON” position to light the
main burner.
Depress and turn knob clockwise to “OFF” position.
TO TURN OFF GAS
Off Position
FP3033
wall switch
PILOT
O
F
F
P
I
L
O
T
O
N
FP1935
control knob pilot
O
F
F
P
I
L
O
T
O
N
PILOT
FP1937
control knob on
Pilot Position On Position
OPERATING INSTRUCTIONS – MILLIVOLT
19
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
ELECTRICAL WIRING
General
This replace is equipped with an IPI control valve which
operates on 6 volts. The 6 volt DC adapter plugs into the
replace junction box A/C power supply.
It is equipped with a battery back-up which will operate
the unit for approximately 48 hours in the event of a power
failure using on/off function only. Use of high/low function
will reduce battery life while in back-up mode..
Optional Accessories
This replace may be used with a wall switch, wall mounted
thermostat or IPI hand held remote control.
CAUTION
Label all wires before disconnecting when
servicing controls. Wiring errors can cause
improper and dangerous operation.
ELECTRICAL INSTALLATION — IPI
WARNING: Electrical connections should
only be performed by a qualied, licensed
electrician. Main power must be off
when connecting to main electrical power
supply or performing service. All wiring shall
be in compliance with all local, city and state
codes. The appliance, when installed, must be
electrically grounded in accordance with local
codes or in the absence of local codes, with
the National Electrical Code ANSI/NFPA 70
(latest edition) and Canadian Electrical Code,
CSA C22.1.
Figure 20. Junction Box Wiring Diagram
FP1912
Junction box wiring
8/08
Junction Box
Factory Supplied
Not Supplied
120V AC
60Hz
WARNING: Do NOT connect to a
110V circuit.
JUNCTION BOX WIRING
1. This should be done before framing the replace. Wire
the receptacle into an electrical circuit. Wire with mini-
mum 60° C wire in accordance with prevailing codes.
2. Remove the external junction box cover by removing
the screw from the side of the outside rebox wall.
Junction box was installed at the factory.
3. The junction box cover has a factory installed “romex”
style strain relief connector. After connecting the wires,
route the wire leads through this connector. Refer to
the wiring diagram in Figure 20.
20
VFC Vent Free Fireplace System
Monessen • VFC 24/32 Owner Manual • 20308011 • Rev J • 01/22
RED
RED
RED
RED
RED
BLACK
D/C POWER
GREEN
GROUND
BROWN
BLACK
BLACK
ORANGE
YELLOW
BLACK
BLACK
RED
CAUTION
Electrical connections should only be performed by a qualied, licensed electrician. Main
power supply must be turned off before connecting fans to the main electrical power supply
or performing service.
Figure 21. IPI System Wiring Diagram
IPI SYSTEM WIRING DIAGRAM
ELECTRICAL INSTALLATION – IPI
WALL SWITCH INSTALLATION
The wall switch wire connection is located off the wire
harness coming out of the IPI Control Board. The label is
wired 'wall switch'. Connect the low voltage switch wires to
the two (2) terminals labeled "wall switch" from the control
board. Run wire to desired location on wall. Up to 50 feet
of 18 gauge wire may be used if necessary. Attach wires
to wall switch. Mount the wall switch in a junction box and
screw on cover. Figure 21
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46

MHSC VFC24L Install Manual

Categoria
Camini
Tipo
Install Manual
Questo manuale è adatto anche per