Assembly and operating instructions
32 A Single Phase active power energy meter with Modbus interface, Pic. 1
Description
Energy meter with Modbus interface enables the reading of
all relevant data like consumption, current, voltage, power
(active and reactive) and cos phi.
Indicating elements
(Pic. 4)
unidirectional:
T total (kWh)
■
Indicates the total consumption
T part (kWh)
■
Indicates the partial consumption.
This value can be reset
P (kW)
■
Indicates the instantaneous power
2000 pulses/kWh
■
Pulsates according to the amount
of used power. Error indication
(line 1L/2L inverted) with pulse of
600/600 ms.
bidirectional:
T
(kWh)
■
Indicates the total consumption
T
(kWh)
■
Indicates the total feeding back
P (kW)
■
Indicates the instantaneous power
Current = consumption (pos.)
Current = feeding back (neg.)
2000 pulses/kWh
■
Pulsates according to the amount
of used power.
common:
U (V)
■
Indicates the voltage
I (A)
■
Indicates the current
Technical data
Connection
■
Pic. 2
diagram
Dimensions
■
Pic. 3
Accuracy class
■
B according to EN50470-3,
1 according to IEC62053-21
Reference, Maxi-
■
Iref = 5 A, Imax = 32 A, Ist = 20 mA
mum, initial current
operating voltage
■
230 VAC, 50 Hz
Tolerance −20%/+15%
Counting range
■
00 000,00…999 999,9 kWh
Connections
■
Conductor cross-section max. 6 mm
2
,
Main circuit screwdriver pozi no. 1, slot no. 1,
torque 1,2 Nm
Connections
■
Conductor cross-section max. 2,5 mm
2
,
Control circuit screwdriver pozi no. 0, slot no. 1,
torque 0,5 Nm
Operating
■
−25… +55°C (noncondensing
temperature according standard EN50470)
Environment
■
Mechanical M2
Electromagnetic E2
Notes before connecting
In order to avoid moisture in the meter due to condensate
build-up, acclimatise the meter at room temperature for
about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of re or the risk of
an electric shock.
Declaration of Conformity CE
We, Saia-Burgess Controls AG, CH 3280 Murten (Switzer-
land), herewith declare, on our own responsibility that
the products:
■
ALD1D5FD00A3A00
■
ALD1B5FD00A3A00
which this certicate refer to, are in accordance with the
directive 2004/22/EG (MID) and the following standards:
■
EN50470 parts 1 and 3 (electronic meter), of
October 2006.
ESD on equipment side: 13 kV.
Murten, 30.04.2013
Conformity Assessment Body:
METAS-Cert, Nr. 1259
CH-3003 Bern-Wabern
Signed: Urs Tanner, Site Quality Leader
English
Installation instructions
The energy meter can be attached to a 35 mm rail
(EN60715TH35).
The meter can be used only in installation cabinets.
Operation of the LCD display
See page with LCD menu navigation.
431951150G 03.2017 Subject to change without notice
Technical data Modbus
Bus system Modbus, RTU according to IDA specication
Transmission rate 4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Transmission mode Even parity: 8 data bits, 1 stop bit
Odd parity: 8 data bits, 1 stop bit
No parity: 8 data bits, 2 stop bits
Bus length (max.) 1200 m (without repeater)
Response time: Write: up to 60 ms
Read: up to 60 ms
■
The communication is ready 30 s after the power on
■
The use of energy meter in bus with intensive communication could reduce the performance of the bus
■
Refresh time for the data is 5 s. For this reason one energy meter should be not polled faster as 5 s
■
247
devices could be connected to the Modbus. With more than 128 devices, a repeater should be used
■
The interface don’t have a terminal resistor, this must be provided external
■
For a description of the used registers please look at the register page
Data transmission
■
Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized.
■
Up to 20 Registers can be read at a time.
■
The device supports broadcast messages.
■
In accordance with the Modbus protocol, a register R is numbered as R - 1 when transmitted.
■
The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)
Exception Responses
■
ILLEGAL FUNCTION [01]: The function code is not supported.
■
ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range
or more than 20 registers have been requested.
■
ILLEGAL DATA VALUE [03]: The value in the data eld is invalid for the referenced register.
Changing the Modbus address direct on device
■
In the menu, go for «U»
■
Push long ( ≥ 3 sec) ➞ «Adr»
■
Push short ➞ address +1, push long ➞ address +10
■
Once the desired address is selected wait, to validate, till the root menu to come back
English
Register
For double registers (4 – 5, 16 – 17, 28 – 29, 30 – 31) the high register is sent rst (big-Endian).
Partial counter (30 – 31) can be reset by writing 0 in both registers in the same message.
R Read Write Description Unit
1 X Firmware-Version Ex: 11 = FW 1.1
2 X Number of supported registers Will give 40
3 X Number of supported ags Will give 0
4–5 X Baudrate Ex: Baudrate High = 1 Baudrate Low = 49664
1 × 65536 + 49664 = 115 200 bps
6 X Not Used Will give 0
7 X Type / ASN function Will give «AL»
8 X Type / ASN function Will give «D1»
9 X Type / ASN function Will give #«D5» / *«B5»
10 X Type / ASN function Will give «FD»
11 X Type / ASN function Will give «00»
12 X Type / ASN function Non MID will give «A2»
MID will give «A3»
13 X Type / ASN function # Will give «A0»
14 X Type / ASN function # Will give «0»
15 X HW vers. Modif. Ex: 11 = HW 1.1
16–17 X Serial number Unique 32 bit serial number Low
18 X Serial number Unique 32 bit serial number High
19 X Not Used Will give 0
20 X Not Used Will give 0
21 X Not Used Will give 0
22 X Status 0 = no Problem
1 = problem with last communication request
23 X Response Timeout ms
24 X X
1)
Modbus Address Range 1–247
25 X Error register 0 : No error 1 : Error
26 X Not Used Will give 0
27 X # Not used
* Tari register
# Will give 0
* 0 : --> 4 : <--
28–29 X Counter Energy Total Tari 1
# WT1 total
*
WT *
10
–2
kWh (multiplier 0,01)
Ex: WT1 total High = 13 WT1 total Low = 60383
13 × 65536 + 60383 = 912351 = 9123.51 kWh
30–31 X X Counter Energy Partial Tari 1
# WT1 partial
WT *
10
–2
kWh (multiplier 0,01)
Ex: WT1 partial High = 13 WT1 partial Low = 60383
13 × 65536 + 60383 = 912351 = 9123.51 kWh
32 X Not Used Will give 0
33 X Not Used Will give 0
34 X Not Used Will give 0
35 X Not Used Will give 0
36 X URMS phase 1
Eective Voltage of Phase 1
V
Ex: 230 = 230 V
37 X IRMS phase 1
Eective Current of Phase 1
10
–1
A (multiplier 0,1)
Ex: 314 = 31.4 A
38 X Eective active Power of Phase 1
# PRMS phase 1
* positive: "Energy
”
*
negative: “Energy ”
10
–2
kW (multiplier 0,01)
Ex: 1545 = 15,45 kW
39 X QRMS phase 1
Eective reactive Power of Phase 1
10
–2
kvar (multiplier 0,01)
Ex: 1545 = 15,45 kvar
40 X cos phi phase 1 10
–2
(multiplier 0,01)
Ex: 67 = 0,67
1)
The Modbus Address register is not writable with a broadcast message.
# unidirectional * bidirectional
Unidirectional type ALD1D5FD
and bidirectional type ALD1B5FD