Magnum Energy MCP5538 Manuale del proprietario

Categoria
Adattatori di alimentazione
Tipo
Manuale del proprietario

Questo manuale è adatto anche per

MS Series
Pure Sine Wave
Inverter/Charger
Owners Manual
TM
Page i © 2009 Magnum Energy Inc.
Disclaimer of Liability
Since the use of this manual and the conditions or methods of installation, operation, use and
maintenance of the MS Series Inverter/Charger is beyond the control of Magnum Energy Inc.,
this company does not assume responsibility and expressly disclaims liability for loss, damage or
expense, whether direct, indirect, consequential or incidental, arising out of or anyway connected
with such installation, operation, use, or maintenance.
Due to continuous improvements and product updates, the images shown in this manual may not
exactly match the unit purchased.
Restrictions on Use
The MS Series Inverter/Charger shall not be used in connection with life support systems, life
saving or other medical equipment or devices. Using the MS Series Inverter/Charger with this
particular equipment is at your own risk.
Copyright Notice
Copyright © 2004, 2009 by Magnum Energy, Inc. All rights reserved. Permission to copy, dis-
tribute and/or modify this document is prohibited without express written permission by Magnum
Energy, Inc.
Contact Information
Magnum Energy, Inc.
2211 West Casino Rd.
Everett, WA 98204
Phone: 425-353-8833
Fax: 425-353-8390
Web: www.magnumenergy.com
Record the unit’s model and serial number in case you need to provide this
information in the future. It is much easier to record this information now,
instead of trying to gather it after the unit has been installed.
Model Number ___________________
Serial Number ___________________
Magnum Energy® is a registered trademark of Magnum Energy, Inc.
© 2009 Magnum Energy Inc.Page ii
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important safety instructions that must be followed during the installation
and operation of this product.
All electrical work must be performed in accordance with local, state and federal electrical codes.
Read all instructions and safety information contained in this manual before installing or using
this product.
This product is designed for indoor/compartment installation. It must not be exposed to rain,
snow, moisture or liquids of any type.
Use insulated tools to reduce the chance of electrical shock or accidental short circuits.
Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the inverter.
Always disconnect the batteries or energy source prior to installing or performing maintenance
on the inverter.
Live power may be present at more than one point since an inverter utilizes both batteries
and AC.
Always verify proper wiring prior to starting the inverter.
There are no user serviceable parts contained in this product.
This unit is provided with integral protection against overloads.
The input and output AC and DC circuits are isolated from the inverter chassis. The inverter
system grounding is the responsibility of the installer in accordance with the NEC/CEC, ABYC,
RVIA, and local codes.
Both AC and DC overcurrent protection must be provided as part of the installation.
Use Class 1 wiring methods for eld wiring connections to terminals of a Class 2 circuit.
Use only copper wires with a minimum temperature rating of 90°C.
Listed or labeled equipment shall be installed and used in accordance with any instructions
included in the listing or labeling.
Safety Symbols
To reduce the risk of electrical shock, re, or other safety hazard, the following safety symbols have
been placed throughout this manual to indicate dangerous and important safety instructions.
WARNING: This symbol indicates that failure to take a speci ed action could result in
physical harm to the user.
CAUTION: This symbol indicates that failure to take a speci ed action could result in
damage to the equipment.
Info: This symbol indicates information that emphasizes or supplements important
points of the main text.
Remedy: This symbol provides possible solutions for related issues.
SAVE THESE INSTRUCTIONS
Page iii © 2009 Magnum Energy Inc.
IMPORTANT BATTERY SAFETY INSTRUCTIONS
Be very careful when working around batteries, they can produce extremely high currents
if short-circuited. Read the battery supplier’s precautions before installing the inverter and
batteries.
Wear eye protection such as safety glasses when working with batteries.
Remove all jewelry such as rings, watches, bracelets, etc., when installing or performing
maintenance on the inverter.
Never work alone. Always have someone near you when working around batteries.
Use proper lifting techniques when working with batteries.
Never use old or untested batteries. Check each battery’s label for age, type and date code
to ensure all batteries are identical.
Batteries are sensitive to changes in temperature. Always install batteries in a stable
environment.
Install batteries in a well ventilated area. Batteries can produce explosive gasses. For
compartment or enclosure installations, always vent batteries to the outside.
Provide at least one inch of air space between batteries to provide optimum cooling.
Never smoke when in the vicinity of batteries.
To prevent a spark at the battery and reduce the chance of explosion, always connect the
cables to the batteries rst. Then connect the cables to the inverter.
Use insulated tools at all times.
Always verify proper polarity and voltage before connecting the batteries to the inverter.
To reduce the chance of re or explosion, do not short-circuit the batteries.
In the even of accidental exposure to battery acid, wash thoroughly with soap and water. In
the even of exposure to the eyes, ood them for at least 15 minutes with running water and
seek immediate medical attention.
Recycle old batteries.
SAVE THESE INSTRUCTIONS
© 2009 Magnum Energy Inc.Page iv
Table of Contents
1.0 Introduction ..................................................................................1
1.1 Features and Bene ts ................................................................................. 2
1.2 How an Inverter/Charger Works ................................................................... 5
1.3 Advantages of a Pure Sine Wave vs Modi ed Sine Wave Inverter ...................... 5
1.4 Appliances and Run Time ............................................................................ 6
2.0 Installation ...................................................................................7
2.1 Pre-Installation .......................................................................................... 7
2.2 Mounting the Inverter ...............................................................................10
2.3 Wiring the Inverter - General Requirements .................................................12
2.4 DC Wiring ................................................................................................13
2.5 AC Wiring ................................................................................................20
2.6 Grounding Inverters ..................................................................................30
2.7 Inverter Noti cation Requirements ..............................................................37
2.8 Final Inspection ........................................................................................37
2.9 Functional Test .........................................................................................38
3.0 Operation ....................................................................................39
3.1 Inverter Mode ..........................................................................................39
3.2 Standby Mode ..........................................................................................40
3.3 Battery Charging ......................................................................................40
3.4 Transfer Time ...........................................................................................42
3.5 Battery Temperature Sensor Operation ........................................................42
3.6 Protection Circuitry Operation .....................................................................43
3.7 Inverter Startup .......................................................................................44
3.8 Factory Default Values ...............................................................................45
4.0 Maintenance and Troubleshooting ...............................................46
4.1 Recommended Inverter and Battery Care .....................................................46
4.2 Storage for Mobile Installations...................................................................46
4.3 Troubleshooting ........................................................................................47
4.4 Resetting the Inverter ...............................................................................48
Appendix A - Speci cations and Optional Equipment ...........................49
A-1 Inverter/Charger Speci cations ..................................................................49
A-2 Inverter Ef ciency .....................................................................................50
A-3 AC Input Voltage to Output Charge Amps ........................................................... 50
A-4 Optional Equipment and Accessories............................................................51
Appendix B - Battery Information .......................................................52
B-1 Battery Location .......................................................................................52
B-2 Battery Types ...........................................................................................52
B-3 Battery Temperature .................................................................................52
B-4 Battery Bank Sizing ..................................................................................52
B-5 Battery Bank Sizing Worksheet ...................................................................53
B-6 Battery Wiring Con gurations .....................................................................54
Limited Warranty ................................................................................57
How to Receive Repair Service ............................................................57
Page v © 2009 Magnum Energy Inc.
List of Figures
Figure 1-1, Power Switch, Status LED and Accessory Connection Ports .................................................3
Figure 1-2, Electrical Connection Points ...........................................................................................3
Figure 1-3, Left Side Features ........................................................................................................4
Figure 2-1, Simpli ed Installation Diagram for Permanent Installations ................................................8
Figure 2-2, Approved Mounting Positions ....................................................................................... 10
Figure 2-3, MS Series Dimensions ................................................................................................. 11
Figure 2-4, DC and Battery Temperature Sensor Wiring ................................................................... 14
Figure 2-5, Battery Hardware Installation ......................................................................................16
Figure 2-6, Inverter DC Hardware Installation ................................................................................ 16
Figure 2-7, Battery Temperature Sensor ........................................................................................ 18
Figure 2-8, MS Series Inverter/Charger - AC Wiring ....................................................................... 21
Figure 2-9, MS Series Inverter/Charger - AC Wiring (Access Panel) .................................................. 21
Figure 2-10, AC Terminal Block ..................................................................................................... 22
Figure 2-11, AC Wiring for Single In - Single Out (30 A) Con gurations ............................................. 25
Figure 2-12, AC Wiring for Single In - Single Out (60 A) Con gurations ............................................. 26
Figure 2-13, AC Wiring for Single In - Dual Out Con gurations ......................................................... 27
Figure 2-14, AC Wiring for Dual In - Single Out Con gurations ......................................................... 28
Figure 2-15, AC Wiring for Dual In - Dual Out Con gurations ............................................................ 29
Figure 2-16, Grounding System for MS Series ................................................................................ 30
Figure 2-17, Multiple Connections to DC Ground Rod (Method 1) ....................................................... 31
Figure 2-18, Multiple Connections to DC Ground Rod (Method 2) ....................................................... 32
Figure 2-19, Single Connection to DC Ground Rod (Method 3) .......................................................... 32
Figure 2-20, Neutral-to-Ground Connection (Inverter Mode) ............................................................. 35
Figure 2-21, Neutral-to-Ground Connection (Standby Mode) ............................................................. 35
Figure 2-22, Disconnecting the Ground-to-Neutral connection ........................................................... 36
Figure 2-23, Large ground wire connected to MS Series ................................................................... 36
Figure 2-24, Warning Label .......................................................................................................... 37
Figure 2-25, AC Voltage Checks .................................................................................................... 38
Figure 3-1, Power Flow - Inverter Mode .........................................................................................39
Figure 3-2, Power Flow - Standby Mode ......................................................................................... 40
Figure 3-3, Automatic 4-Stage Charging Graph ............................................................................... 41
Figure 3-4, BTS Temperature to Charge Voltage Change .................................................................. 42
Figure 3-5, Power Switch and Status Indicator ................................................................................ 44
Figure 4-1, Performing an Inverter Reset .......................................................................................48
Figure 4-2, MS Series Ef ciency Chart ........................................................................................... 50
Figure 4-3, MS Series Output Charger Current Chart ....................................................................... 50
Figure B-1, Series Battery Wiring .................................................................................................. 54
Figure B-2, Parallel Battery Wiring ................................................................................................ 54
Figure B-3, Series-Parallel Battery Wiring....................................................................................... 54
Figure B-4, Battery Bank Wiring Examples (12-volt) ........................................................................ 55
Figure B-5, Battery Bank Wiring Examples (24-volt) ........................................................................ 56
List of Tables
Table 1-1, Typical Appliance Power Consumption ...............................................................................6
Table 2-1, Recommended DC Wire/Overcurrent Device for Rated Use ................................................ 15
Table 2-2, DC Wire Size For Increased Distance .............................................................................. 16
Table 2-3, AC Input/Output Wiring Con gurations ........................................................................... 24
Table 2-4, AC Grounding Electrode Conductor Sizing ....................................................................... 31
Table 2-5, Equipment Grounding Conductor Sizing .......................................................................... 33
Table 3-1, Inverter Battery Turn On/Off Levels ................................................................................ 43
Table 3-2, Inverter/Charger Default Values .................................................................................... 45
Table 4-1, Basic Troubleshooting ................................................................................................... 47
Page 1
© 2009 Magnum Energy Inc.
Introduction
1.0 Introduction
Congratulations on your purchase of the MS Series inverter/charger from Magnum Energy. The
MS Series is a “pure” sine wave inverter designed especially for rugged mobile applications, home
backup power and stand-alone applications. Powerful, yet simple to use, this inverter/charger
will provide you with years of trouble-free performance you have come to expect from Magnum
Energy.
Installation is easy. Simply connect the inverter’s output to your distribution circuits or electrical
panel; connect your utility or AC generator power to the inverter’s easy-to-reach terminal block;
connect the batteries, and then switch it on for power.
With the optional accessories listed below you can control and monitor many other Magnum
Devices.
The MS Series Inverter/Charger includes the following:
2000, 2800, or 4000 Watt Models in a small footprint - less weight and area needed for
installation
Pure Sine Wave Output
Automatic PFC (Power Factor Corrected) multi-stage battery charging
RS485 standard communication protocol
Remote and Network ports (easy connection for optional accessories)
ON/OFF Inverter-mounted switch with LED indicator
60 Amp AC Transfer available (using Dual IN/Dual OUT wiring)
Large AC access and terminal block [wire size: 14 to 6 AWG (2.1 to 13.3 mm2) CU]
DC terminal covers with 360 degree connection
Field Serviceable for quali ed personnel - tested repair kits available
Smooth, aesthetically pleasing design
ETL listed to UL/cUL STDs 458, 1741 and CSA STD 22.2 107.01-01 for safety.
Automatic battery temperature compensation (using battery temperature sensor) - for
optimum charging even during extreme temperature changes
Over-current, over-temperature, and high/low battery voltage protection
The following accessories are also available for use with the MS Series inverter/charger:
ME-RC (Remote Control Display) - communicates with the inverter to: 1. Easily operate
and monitor your inverter and charger from a remote location; 2. Con gure the inverter’s
adjustable settings and maintain these settings with nonvolatile memory; 3. Provide text
display to help with troubleshooting inverter faults.
ME-AGS-N (Automatic Generator Start Module - Network version) - communicates with
the inverter to automatically start/stop your connected generator.
ME-BMK (Battery Monitor Kit) - communicates with the inverter to provides precise DC
voltage/current measurements and information on the battery’s State of Charge (SOC).
ME-CB (Conduit Box) - provides 1/2” - 2” knockouts for connecting AC and DC conduit
runs to the inverter.
ME-SBC (Smart Battery Combiner) - monitors and keeps a second battery charged using
a portion of the current that is charging a main battery.
© 2009 Magnum Energy IncPage 2
Introduction
1.1 Features and Bene ts
The MS Series inverter/charger is designed to allow easy access to wiring, circuit breakers, controls
and for viewing the LED (Light Emitting Diode) status indicator. Its die cast base plate with one
piece aluminum cover ensures maximum durability with minimum weight, as well as cooler more
ef cient operation.
The front of the MS Series is equipped with the following features (see gures 1-1 and 1-2):
(1) Power Switch - a momentary push-button switch that alternately turns the inverter
ON or OFF.
(2) Status LED Indicator - this green LED illuminates to provide information on the
inverter or charger operation.
(3) Stack Connection Port (red label) - a RJ11 port that allows series-stacking and
accepts the optional RSAs (Remote Switch Adapters) which allows remote on/off switch
operation.
Info: The series-stacking capability, which allows two units to provide 120/240 VAC
output is only available on the MS4024 Series Inverter/Charger.
(4) Magnum Net Connection Port (green label) - a RJ11 port that accepts optional
Network capable accessories (i.e., Auto Gen Start or Battery Monitor).
(5) Remote Connection Port (blue label) - a RJ11 port that allows the optional remote
control display to be connected.
(6) BTS Connection Port (yellow label) - a RJ11 port that accepts the remote Battery
Temperature Sensor (BTS) accessory.
(7) Mounting Flange - used to secure the inverter to a shelf or wall.
(8) AC Entry/Exit Connections - two 3/4” knockouts provided with cable-clamp strain
reliefs to allow and hold the AC input and output eld wiring.
(9) Intake Air Vents - ventilation openings to pull in air to help keep the inverter cool
for peak performance.
(10) Positive DC Terminal - provides 360 degree connection point for the positive (+)
cable from the battery bank; provided with a 5/16-18 stainless Kep nut1 on a 5/16-18 bolt
to hold the battery cable to the DC terminal which uses.
(11) Negative DC Terminal - provides 360 degree connection point for the negative (-)
cable from the battery bank; provided with a 5/16-18 stainless Kep nut1 on a 5/16-18 bolt
to hold the battery cable to the DC terminal.
(12) DC Equipment Ground Terminal - this connection is used to tie the exposed
chassis of the inverter to the DC grounding system. This terminal accepts one CU/AL
conductor from #14 to # 2 AWG (21. to 33.6 mm2)
Note 1 - Hex nut with external tooth lock washer
Page 3
© 2009 Magnum Energy Inc.
Introduction
Figure 1-1, Power Switch, Status LED and Accessory Connection Ports
Figure 1-2, Electrical Connection Points
AC Entry/Exit
Connections
Mounting
Flange
(7)
(8)
Power ON/OFF Switch(1)
Status LED
(Charging/Inverting)
(2)
Stacking/Accessories Port
(red label)
(3)
Remote Port
(blue label)
(5)
Battery Temp Sensor Port
(yellow label)
(6)
Magnum Net Port
(green label)
(4)
Intake Air Vents
(and on right side)
(9)
DC Equipment Ground
Terminal
(12)
Positive (+)
DC Cover
(Positive
DC Terminal
underneath)
Negative (–)
DC Cover
(Negative
DC Terminal
underneath)
(11)
(10)
© 2009 Magnum Energy IncPage 4
Introduction
Figure 1-3, Left Side Features
The left side of the MS Series is equipped with the following features (see to gure 1-3):
(13) Exhaust Air Vent - ventilation openings that allow heated air to be removed by the
internal cooling fan.
(14) Model/Serial Number Label - includes model/serial number information, date of
manufacture and inverter and charger speci cations. See Appendix A for more information
and to nd the available models.
(15) AC Wiring Access Cover - provides access to the internal AC wiring terminal block.
This terminal block is used to hardwire all inverter AC input and output wiring connections.
Remove the two screws to access the AC wiring terminal block.
(16) Input circuit breaker - this circuit breaker protects the unit’s internal charger
wiring and pass-thru relay while in the standby mode. This circuit breaker will pop out
when it opens, press in to reset. This input circuit breaker is not branch-circuit rated,
therefore branch-circuit rated breakers must be installed in the inverter’s input wiring.
(17) Output circuit breakers - these circuit breakers are branch-rated and are only
provided on the MS2012-15B and MS2012-20B models. They allow the inverter AC loads
to be connected directly to the inverter’s output without requiring an inverter subpanel.
These circuit breakers pop out when they open, press in to reset. They can also be
manually pulled to disconnect the inverter’s loads.
Info: The output breakers (CB1 and CB2) are only available on models MS2012-15B
and MS2012-20B.
CAUTION: Inverter models without the output Circuit breakers (CB1 and CB2) must
have branch-circuit rated breakers installed in the inverter’s output wiring.
CAUTION: The inverter’s internal AC transfer relay is rated for 30 amps per leg (30
amps for AC HOT 1 and 30 amps for AC HOT 2) or 60 amps total. The pass-thru current
must be no greater than 30 amps per leg or damage to the relays may occur.
Exhaust
Air Vent
(and on
Right Side)
(13)
(14)
(15)
Model/Serial Number Label
(17)
Output Circuit Breakers* Input Circuit Breaker
(16)
(*Only available on certain models)
AC Wiring Access Cover
Page 5
© 2009 Magnum Energy Inc.
Introduction
1.2 How an Inverter/Charger Works
There are two modes of operation associated with this inverter/charger:
Inverter Mode:
When the inverter is properly connected to batteries and turned on, the Direct Current
(DC) from the batteries is transformed into a pure sine wave Alternating Current (AC).
This AC is similar to the voltage provided by your utility and is used to power the electrical
appliances (i.e. AC loads) connected to the inverter’s output.
Standby Mode:
When an external source of AC power (i.e. utility power or generator) is connected and
quali ed on the inverter’s AC input, it operates in the Standby Mode. In the Standby
Mode, the unit operates as a Battery Charger to convert the incoming AC power into DC
power to recharge the batteries; and at the same time, automatically closes an internal
AC Transfer Relay to pass the incoming AC power directly to inverter’s output to continue
powering the connected electrical appliances.
1.2.1 Inverter Applications for Permanent Installations
An inverter can be used for backup power in a permanent location that normally uses utility power
such as a home or of ce. When the utility power is available, the inverter keeps the batteries
charged. When the utility power fails, the inverter comes on automatically to supply AC power to
your home or of ce during the power failure. For a home or business, reliable backup power is
used to prevent lost computer data or to maintain lights and keep food fresh in the refrigerator/
freezer.
In some areas, where utility power is not available, this inverter can be used in an stand-alone
renewable power system. The inverter allows AC electrical appliances to be run from the storage
battery bank. When the battery bank becomes discharged, either renewable DC sources (solar,
wind or hydro power) can be used to recharge the batteries or a generator can be connected to
the inverter to power the system while the batteries recharge.
1.2.2 Inverter Applications for Mobile Installations
Inverters can also be used to provide power in mobile situations, such as in an RV, truck or boat.
In these applications, the inverter provides power to the AC loads using the energy stored in the
batteries and recharges the batteries when shore power or onboard generator is available.
1.3 Advantages of a Pure Sine Wave vs Modi ed Sine Wave Inverter
Today’s inverters come in two basic output waveforms: modi ed sine wave (which is actually a
modi ed square wave) and pure sine wave. Modi ed sine wave inverters approximate a pure sine
waveform and will run most appliances and electronics without any problems. These inverters are
less expensive and, therefore, offer a viable alternative to more expensive pure sine inverters.
The output of a pure sine wave inverter is equal to or, in many cases, better than the utility power
used in your home. Virtually any electronic device will operate from a pure sine wave inverter.
Motors run cooler, microwaves usually cook faster and clocks keep better time just to name a few
examples. Without compromising quality or performance, the MagnaSine provides you with all of
the advantages of a pure sine wave inverter at a much lower cost than many on the market.
The MS Series is built on the same platform as our popular ME and RD Series modi ed sine wave
inverters allowing for an easy upgrade from the original ME or RD Series installation. This standard
platform also helps reduce cost by using standard parts/accessories across many models. All
Magnum accessories such as the Remote Control (ME-RC), Automatic Generator Start - Networked
(ME-AGS-N), Battery Monitor Kit (ME-BMK), and network accessories can be used on all ME, RD,
and MS Series inverters.
© 2009 Magnum Energy IncPage 6
Introduction
1.4 Appliances and Run Time
The MS Series inverter/charger can power a wide range of household appliances including small
motors, hair dryers, clocks and other electrical devices. As with any appliance using batteries for
power, there is a certain length of time that it can run - this is called “run time.” Actual run time
depends on several variables including the size and the type of appliance, the type of batteries
installed in your application, as well as the battery’s capacity and age. Other factors such as the
battery’s state of charge and temperature can also affect the length of time your appliances can
run.
Appliances such as TVs, VCRs, stereos, computers, coffee pots, incandescent lights and toasters
can all be successfully powered by your inverter. Larger electrical appliances, however, such as
stoves, water heaters, etc., can quickly drain your batteries and are not recommended for this
application.
All electrical appliances are rated by the amount of power they consume. The rating is printed
on the product’s nameplate label, usually located on its chassis near the AC power cord. Even
though it is dif cult to calculate exactly how long an inverter will run a particular appliance, the
best advice is trial and error. Your MS Series inverter has a built-in safeguard that automatically
protects your batteries from over discharge.
Info: For optimum performance, a minimum battery bank of 200 AH is recommended
for moderate loads (<1000W) and greater than 400 AH for heavy loads (1000W).
Table 1-1, Typical Appliance Power Consumption
Device Load Device Load
Blender 400W Coffee Maker 1200W
Computer 300W Color TV 150W
Drill 500W Hair Dryer 1000W
Hot Plate 1800W Iron 1000W
Light (Flo) 10W Light (Inc) 100W
Microwave 1000W Refrigerator 500W
Page 7
© 2009 Magnum Energy Inc.
Installation
2.0 Installation
Info: Installations should be performed by quali ed personnel, such as a licensed
or certi ed electrician. It is the installer’s responsibility to determine which safety
codes apply and to ensure that all applicable installation requirements are followed.
Applicable installation codes vary depending on the speci c location and application of
the installation.
CAUTION: Review the “Important Product Safety Information” on page ii and the
“Important Battery Safety Instructions” on page iii before any installation.
CAUTION: The inverter is heavy. Use proper lifting techniques during installation to
prevent personal injury.
The simpli ed system diagram shown in Figure 2-1 should be reviewed to assist you in planning
and designing your installation. This drawing is not intended to over-ride or restrict any national
or local electrical codes. This drawing should not be the determining factor as to whether the
installation is compliant, that is the responsibility of the electrician and the on-site inspector.
2.1 Pre-Installation
Before installing the inverter, read the entire installation section to determine how you are going
to install your MS inverter/charger. The more thorough you plan in the beginning, the better your
inverter needs will be met.
2.1.1 Unpacking and Inspection
Carefully remove the MS Series inverter/charger from its shipping container and inspect all contents.
Verify the following items are included:
The MS Inverter/Charger
Red and black DC terminal covers with Phillips screws
AC access cover with two Phillips screws
Two 5/16” Kep nuts (installed on the DC terminals).
Battery Temperature Sensor
Warning Label
MS Series Owner’s Manual
If items appear to be missing or damaged, contact your authorized Magnum Energy dealer or
Magnum Energy. If at all possible, keep your shipping box. It will help protect your inverter from
damage if it ever needs to be returned for service. Save your proof-of-purchase as a record of
your ownership; it will also be needed if the unit should require in-warranty service.
Record the unit’s model and serial number in the front of this manual in case you need to provide
this information in the future. It is much easier to record this information now, instead of trying
to gather it after the unit has been installed.
2.1.2 Required Tools and Materials
Hardware/Materials
Conduit, strain-reliefs and appropriate ttings 1/4” mounting bolts and lock washers
Electrical tape Wire ties
Tools
Miscellaneous screwdrivers Pliers Wire strippers
Drill and drill bits Pencil or Marker Multimeter
Level 1/2” wrench
© 2009 Magnum Energy IncPage 8
Installation
Figure 2-1, Simpli ed Installation Diagram for Permanent Installations
Battery Bank
120/240VAC
power to
inverter
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
240
VAC 120
VAC
120
VAC
DC
Overcurrent
protection
(Breaker or
Fuse/switch)
MS Series
Inverter/
Charger
Main Panel Sub-Panel
120VAC Inverter power
(or 120/240VAC pass-thru power)
to Sub-panel
SELECT
TECH
AG S M ETER SET UPSHO REINVERTER
CHARG ER
INV
CHG
FA U LT
PWR
ON/ OFF
ON/ OFF
ME-RC50
Remote Control
(Magnum Option)
ME-BMK
Battery Monitor
with shunt
(Magnum
Option)
DC
Shunt
AC
Transfer
Switch
Generator Power
120/240VAC Output
Utility Power
120/240VAC Output
Flu x
Capa cito r Genera tor
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
BTS
ON
OFF
ON
OFF
30 A
30A
ME-SBC
Smart Battery
Combiner
(Magnum
Option)
ME-AGS-N
Auto Gen Start
Controller
(Magnum
Option)
Page 9
© 2009 Magnum Energy Inc.
Installation
2.1.3 Locating the Inverter
Only install the inverter in a location that meets the following requirements:
Clean and Dry - The inverter should not be installed in an area that allows dust, fumes, insects or
rodents to enter or block the inverter’s ventilation openings. This area also must be free from any
risk of condensation, water or any other liquid that can enter or fall on the inverter. The inverter
uses stainless steel fasteners, plated copper buss-bars, a power-coated aluminum base and the
internal circuit boards are conformal coated all done to help ght the harmful effects of corrosive
environments. However, the inverter’s life is uncertain if used in these type of environments, and
inverter failure under these conditions is not covered under warranty.
Info: If the inverter is installed in an area where moisture may occur, we recommend
putting silicone dielectric grease compound into the electrical ports (items 3 to 6 as
shown in gure 1-1). Before installing the cables or if leaving any ports open, squirt a
liberal amount into each port. Silicone dielectric compound makes an effective moisture
and corrosive barrier to help protect and prevent corrosion to the RJ11 connections.
Cool - The inverter should be protected from direct sun exposure or equipment that produces
extreme heat. The ambient temperature around the inverter must not exceed 77°F (25°C) to
meet power speci cations.
Ventilation - In order for the inverter to provide full output power and avoid over temperature
fault conditions; do not cover or block the inverters ventilation openings or install this inverter in
an area with limited air ow. The inverter uses two fans to provide forced air cooling, these fans
pull in air through the intake vents (see item 9 in gure 1-2) and blow out air through the exhaust
vents (see item 13 in gure 1-3). Allow at the minimum, an airspace clearance of 6” at the intake
and exhaust vents and 3” everywhere else to provide adequate ventilation.
If installed in an enclosure, a fresh air intake opening must be provided directly to the front side
(intake vents) of the inverter and an exhaust opening on the back side (exhaust vents) of the
inverter. This allows cool air from the outside to ow into the inverter and heated air to exit the
inverter and out of the enclosure. When mounted in an enclosed compartment, air ow must be
100 cfm in order to maintain no more than a 68°F (20°C) rise in compartment temperature.
CAUTION: Do not mount this inverter in a zero clearance compartment, cover or
obstruct the ventilation openings - overheating may result.
Safe - Keep any ammable/combustible material (i.e., paper, cloth, plastic, etc.) that may be
ignited by heat, sparks or ames at a minimum distance of 2 feet away from the inverter. Do not
install this inverter in any area that contains extremely ammable liquids like gasoline or propane,
or in locations that require ignition-protected devices.
WARNING: The MS Series inverter/charger is not ignition protected and may not be
located in an engine compartment with gasoline-fueled engines under any circumstance.
Close to the battery bank - As with any inverter, it should be located as close to the batteries as
possible. Long DC wires tend to loose ef ciency and reduce the overall performance of an inverter.
However, the unit should not be installed in the same compartment as the batteries or mounted
where it will be exposed to gases produced by the batteries. These gases are corrosive and will
damage the inverter; also if these gases are not ventilated and if allowed to collect, they could ignite
and cause an explosion.
Accessible - Do not block access to the inverter’s remote control and accessory ports as well
as the inverter’s controls and status indicator. Also allow enough room to access the AC and DC
wiring terminals and connections, as they will need to be checked and tighten periodically. See
gure 2-3 for the MS Series inverter/charger dimensions.
Away from sensitive electronic equipment - High powered inverters can generate levels of RFI
(Radio Frequency Interference). Locate any electronic equipment susceptible to radio frequency
and electromagnetic interference as far away from the inverter as possible.
© 2009 Magnum Energy IncPage 10
Installation
30
30
2.2 Mounting the Inverter
The inverter base can reach a temperature up to 90°C (194°F), and it is recommended that it should
be mounted on a noncombustible surface*. This surface and the mounting hardware must also be
capable of supporting at least twice the weight of the inverter. To meet regulatory requirements,
the MS Series must be mounted in one of the following positions; as shown in gure 2-2:
above or under a horizontal surface (shelf or table),
or on a vertical surface (wall) with the DC terminals to the right.
CAUTION: If the inverter is mounted in a way that the DC terminal ventilation openings
are oriented on the bottom, the ME-CB enclosure must be used. This enclosure prevents
burning material from falling out the bottom and also allows suf cient ventilation to
prevent the inverter from overheating under normal operating conditions.
After determining the mounting position, refer to the physical dimensions as shown in gure 2-3 or
use the base of the inverter as a template to mark your mounting screw locations. After marking
the mounting screw locations, mount the unit with appropriate mounting hardware.
* Noncombustible surface - A surface made of material that will not ignite, burn, support combustion, or release ammable
vapors when subjected to re or heat as per the ASTM E136 standard. For the most part, these are materials that are
largely comprised of inorganic materials such as stone, steel, iron, brick, tile concrete, slate and glass. Common building
materials such as gypsum board as well as any paint, wall coverings, and certainly wood will not pass.
Figure 2-2, Approved Mounting Positions
Shelf or Table Mounted
(unit below)
Shelf or Table Mounted
(unit above)
Wall Mounted
(DC terminal to the right
Wall Mounted (DC terminals on bottom*)
*When the inverter is mounted in this position, the ME-CB
conduit box must be installed.
Page 11
© 2009 Magnum Energy Inc.
Installation
Figure 2-3, MS Series Dimensions
12 5/8"
12"
4 7/8"
2"
4 7/8"
Keyhole
slots (x4)
and
mounting
holes (x4)
accept
up to
9/32"
screw/
bolt
13 3/4"
8"
6 5/8"
© 2009 Magnum Energy IncPage 12
Installation
2.3 Wiring the Inverter - General Requirements
This section also describes the requirements and recommendations for wiring the MS Series
inverter/charger. Before wiring the MS Series inverter/charger, read all instructions.
All wiring should meet all local codes and standards and be performed by quali ed
personnel such as a licensed electrician.
The NEC (National Electric Code, ANSI/NFPA 70) for the United States and the CEC (Canadian
Electrical Code) for Canada provide the standards for safely wiring residential and commercial
installations. The NEC/CEC lists the requirement for wire sizes, overcurrent protection and
installation methods and requirements.
Inverter/charger systems involve power from multiple sources (inverter, generator, utility, batteries,
solar arrays, etc.) which make the wiring more hazardous and challenging.
The input and output AC and DC circuits are isolated from the inverter chassis. The inverter system
grounding is the responsibility of the installer in accordance with the NEC.
WARNING: Ensure all sources of DC power (i.e., batteries, solar, wind or hydro) and
AC power (utility power or AC generator) are de-energized (i.e., breakers opened,
fuses removed) before proceeding - to prevent accidental shock.
2.3.1 Protecting Wire - Conduit Box
The AC and DC wires into and out of the inverter must be protected as required by code. This
can be done by using jacketed wires or by feeding the wires through conduit. Magnum provides
a DC conduit box (part number ME-CB) that can be purchased to allow conduit to be connected
to the inverter for both the AC and DC conductors.
Info: If using the ME-CB conduit box and the AC wires are individual conductors (i.e.,
not jacketed), the strain reliefs can be removed and replaced with 3/4” grommets.
2.3.2 Wiring Requirements
All conductors that are at risk to physical damage must be protected by conduit, tape, or
placed in a raceway.
Always check for existing electrical, plumbing or other areas of potential damage prior to
making cuts in structural surfaces or walls.
Do not mix AC and DC wiring in the same conduit or panel unless speci cally approved/
designed for both AC and DC wiring. Where DC wiring must cross AC or vice-versa, try to
make the wires at the crossing point 90° to one another.
Both AC and DC overcurrent protection must be provided as part of the installation.
The inverter requires a reliable negative and ground return path directly to the battery.
Use only copper wires with a minimum temperature rating of 90°C.
2.3.3 Wire Routing
Before connecting any wires, determine all wire routes to and from the inverter. Typical routing
scenarios are:
AC input wiring from the main AC panel to the inverter
AC input wiring from a generator (optional) to the inverter
DC input wiring from the batteries to the inverter
AC output wiring from the inverter to the AC sub-panel or to dedicated circuits
Battery Temperature Sensor cable from the inverter to the batteries
Remote Control cable (optional) to the inverter
Ground wiring to and from the inverter
2.3.4 Torque Requirements
Torque all AC wiring connections to 16 in lbf (1.8 N-m). Torque DC cable connections from
10 to 12 ft lbf (13.6 to 16.3 N-m).
Page 13
© 2009 Magnum Energy Inc.
Installation
2.4 DC Wiring
This section describes the inverter’s required DC wire sizes and the recommended disconnect/
overcurrent protection and how to make the DC connections to the inverter and the
battery bank.
Refer to gure 2-4 when connecting the DC wires.
WARNING: Even though DC voltage is “low voltage”, signi cant hazards may be
present, particularly from short circuits of the battery system.
CAUTION: The inverter is NOT reverse polarity protected which means that if the
negative and positive battery voltage is connected backwards to the inverter, the
inverter will likely be damaged. You should verify the correct voltage polarity using a
voltmeter BEFORE connecting the DC wires.
CAUTION: Before wiring the DC cables, review the safety information at the beginning
of this manual and the following to ensure a safe and long-lived system.
Info: DO NOT connect the battery cables to the inverter until all wiring is complete and
the correct DC voltage and polarity has been veri ed.
When the inverter is installed in a Photovoltaic System, the NEC requires that the DC circuit
conductors and overcurrent devices to the inverter be sized to carry not less than 125% of
the inverter’s maximum current rating.
The DC positive and negative cables connected to the inverter from the battery bank should
be tied together with wire ties or electrical tape approximately every 6 inches. This helps
improves the surge capability and reduces the effects of inductance, which improves the
inverter waveform and reduces the wear of the inverter’s lter capacitors.
Crimped and sealed copper ring terminal lugs with a 5/16” hole should be used to connect the
DC wires to the inverter’s DC terminals.
The battery bank voltage MUST match the DC voltage required by the inverter (i.e., 24-volt
battery bank for a 24-volt inverter) or the inverter may be damaged.
To ensure the maximum performance from the inverter, all connections from the battery bank
to the inverter should be minimized, the exception is the DC overcurrent disconnect in the
positive line and a shunt in the negative line. Any other additional connection will contribute
to additional voltage drops and these extra connections points may loosen during use.
All wiring to the battery terminals should be checked periodically (once a month) for proper
tightness. The torque requirement for the DC terminals is between 10 to 12 ft lbf (13.6
to 16.3 N-m). If you don’t have a torque wrench, ensure all DC terminals are tight and
cannot move.
Be aware that overtightening or misthreading the nuts on the DC terminals can cause the
bolts to strip and snap/break off.
Make sure cables have a smooth bend radius and do not become kinked. Place long cable
runs in conduit and follow existing wire runs where possible.
A brief spark or arc may occur when connecting the battery cables to the inverter DC terminals;
this is normal and due to the inverter’s internal capacitors being charged.
Color code the DC cables/wires with colored tape or heat shrink tubing: RED for positive (+);
WHITE for negative (-); and GREEN for DC ground to avoid polarity problems.
© 2009 Magnum Energy IncPage 14
Installation
DC Overcurrent
Protection
(Circuit Breaker
or Fuse/switch)
DC Ground
Bus-bar
DC
Shunt
Battery Bank
DC Circuit
Breaker Box
DC Negative
To DC Ground
Jumper
DC Grounding point
[Vehicle chassis, Electrode
Conductor (i.e. ground rod)]
MS Series
Inverter/Charger
ME-CB
Conduit Box
Battery Temp Sensor Cable
Inverters DC Negative Cable
Inverter’s DC Positive Cable
Inverter’s DC Equipment
Ground Wire
wall
mounted
view
front view
Figure 2-4, DC and Battery Temperature Sensor Wiring
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Magnum Energy MCP5538 Manuale del proprietario

Categoria
Adattatori di alimentazione
Tipo
Manuale del proprietario
Questo manuale è adatto anche per

in altre lingue