Tecnoware 02.01.0042 Manuale utente

Tipo
Manuale utente
Stabilizer Servo-Assisted/SCR with µP Electronic Control
Stabilizzatore Servoassistito/SCR a Controllo Elettronico con µP
User’s manual
Manuale utente
Index
User’s Manual - English ........................................................................ 1
Safety Warnings ................................................................................. 1
1 Introduction ................................................................................. 2
2 General Characteristics ................................................................... 3
3 Receipt and site selection ................................................................ 4
4 External Description ....................................................................... 5
4.1 Front Panel ............................................................................ 5
4.2 Front Side and Rear Side ............................................................. 7
4.2.1 Single-Phase models....................................................................... 7
4.2.2 Three-Phase models ....................................................................... 8
4.3 Input/output Terminals .............................................................. 9
5 Electrical Installation ..................................................................... 10
5.1 Installation ............................................................................ 11
6 Functioning ................................................................................. 12
6.1 Turning ON and OFF ................................................................. 12
6.2 Load Control .......................................................................... 13
6.3 Manual Bypass ........................................................................ 13
7 Technical Characteristics ................................................................ 14
8 Maintenance................................................................................ 15
8.1 AVR Cleaning ......................................................................... 15
8.2 Operator Safety ...................................................................... 15
9 Service ...................................................................................... 15
Conformity to the European Directives ................................................... 16
Product Disposal ............................................................................... 16
Indice
Manuale Utente – Italiano ................................................................... 17
Avvisi di Sicurezza............................................................................ 17
1 Introduzione ............................................................................... 18
2 Caratteristiche Generali ................................................................ 19
3 Ricevimento e Collocazione ............................................................ 20
4 Descrizione Esterna ...................................................................... 21
4.1 Pannello Frontale .................................................................... 21
4.2 Fronte e Retro ........................................................................ 23
4.2.1 Modelli Monofase ......................................................................... 23
4.2.2 Modelli Trifase ............................................................................ 24
4.3 Morsettiera d’Ingresso/Uscita ...................................................... 25
5 Installazione Elettrica ................................................................... 26
5.1 Installazione .......................................................................... 27
6 Funzionamento ........................................................................... 28
6.1 Accensione e Spegnimento ......................................................... 28
6.2 Controllo del carico .................................................................. 29
6.3 Bypass Manuale ....................................................................... 29
7 Caratteristiche Tecniche ................................................................ 30
8 Manutenzione ............................................................................. 31
8.1 Pulizia del prodotto.................................................................. 31
8.2 Sicurezza dell’Operatore ........................................................... 31
9 Servizio Assistenza ....................................................................... 31
Conformità alle Direttive Europee ........................................................ 32
Smaltimento del Prodotto ................................................................... 32
ENGLISH
STABILIZER 1 User’s manual
User’s Manual - English
Safety Warnings
Read this manual carefully and completely before installing and using the TECNOWARE Stabilizer, which,
from here after, will also be referred to as AVR.
This manual should be kept close to the AVR and read before the AVR is installed and used.
The AVR must be used only by properly trained personnel. To ensure correct and safe operations, it is
necessary that operators and maintenance personnel observe the general safety Standards as well as the
specific instructions included in this manual.
Risk of electric shock: do not remove the cover. The AVR contains internal parts which are at a high
Voltage and are potentially dangerous, capable of causing injury or death by electric shock.
The electric installation has to be done by qualified personnel. Follow all the Safety Standards (CEI
Standards in Italy or IEEE elsewhere) for the Input/Output connections and for the right section of
Input/Output cables.
There are no internal parts in the AVR which are user serviceable. Any repair or maintenance work must
be performed exclusively by qualified technical personnel authorized by TECNOWARE. TECNOWARE
declines any responsibility if this warning is disregarded.
It is compulsory to ground the AVR according to Safety Standards.
Risk of electric shock at the Output lines when the AVR is ON or in Bypass Mode.
Risk of electric shock at the Output lines while the unit is connected to the AC utility line.
We recommend to use a dedicate AC Input/Output power line for the AVR.
Do not obstruct ventilation slots or holes and do not rest any object on top of the AVR.
Do not insert objects or pour liquids in the ventilation holes.
Install the AVR indoors, in a protected, clean and moisture-free environment.
Do not expose to the direct sun light.
Do not keep liquids, flammable gases or corrosive substances near the AVR.
ENGLISH
User’s manual 2 STABILIZER
1 Introduction
Principle of compensated AC Voltage Regulator
TECNOWARE Stabilizer is an AVR (AVR means Automatic Voltage Regulator): this product is the result of constant
technological research aimed at obtaining the best performance at the lowest cost.
This product is a compensated type AC voltage regulator.
It consists of MCU control unit, voltage regulator unit, servo-assisted motor, and input/output protection
components, etc. (see figure 1).
When the grid voltage is not stable, MCU control unit samples the output voltage, and according to the
requirement of setting accuracy, keeps the output voltage within the desired voltage range, by means of
adjustment of the voltage regulator unit.
AVR has a short response time, high efficiency, high reliability, can work continuously for a long time. It is
applicable for all kinds of instruments, meters, communications, home appliances and work site.
This manual is a guide that enables you to correctly install and use your AVR. This
manual includes important SAFETY instructions for the operator, for the AVR correct
installation, and gives useful advice on the product maintenance. For any type of
problem, please refer to this manual before calling the customer service.
Stabilizer is constantly being developed and improved: consequently, your unit may differ somewhat from the
description contained in this manual.
This manual includes the following models:
SINGLE-PHASE STABILIZERS
Code Power
FSTESM4K5M
4
.
5
K
VA
FSTESM7K5M
7
.
5
K
VA
FSTESM10KM
10
VA
FSTESM12KM
1
2
VA
FSTESM18KM
1
8
KVA
THREE-PHASE STABILIZERS
Code Power
FSTESM9KT
9 KVA
FSTESM18KT
18 KVA
FSTESM25KT
25 KVA
FSTESM50KT
50 KVA
FSTESC75KT
75 KVA
FSTESC100KT
100 KVA
In this manual Stabilizer will simply be referred to as AVR.
ENGLISH
STABILIZER 3 User’s manual
2 General Characteristics
AVR has all the advanced features which guarantee maximum reliability and safety:
Output Voltage regulation 1%
Protection from overload and short circuits
Automatic restart after Blackout, once AC utility power comes back on.
Graphic Display for visualization of the Input and Output Voltage measurements, output current value,
alarms, overload and fault condition.
Acoustic signals of various kinds indicating alarm situations
High efficiency
Maximum reliability
Smart design and easy to use
ENGLISH
User’s manual 4 STABILIZER
3 Receipt and site selection
Carefully remove the AVR from its packaging, and carry out a meticulous inspection. We recommend keeping the
original packaging in a secure place, in case you need to send the AVR for maintenance purposes. In case of
transport damage, notify the carrier and dealer immediately.
We recommend paying attention to the below points in order to choose a correct placement for your AVR:
The AVR is designed to operate in a protected environment (e.g. offices). We therefore recommend
installing it in a place with very little or no humidity, dust or smoke.
When the AVR is brought from a cold place to a warmer place, humidity in the air may cause condensation
in the AVR. In this case, allow AVR to stand for two hours in the warmer place before beginning with the
installation.
In all circumstances, see the “Technical Characteristics” chapter for environmental specifications and
check that the selected area meets these criteria.
During normal operation the AVR discharges a minimal amount of heat. So it is necessary to leave at least
20 cm of unobstructed space all around the AVR in order to keep it properly ventilated.
Do not obstruct ventilation holes.
Do not insert objects or pour liquids in the ventilation holes.
Do not rest any object on top of the AVR.
Do not keep liquids, flammable gases or corrosive substances near the unit.
Install the AVR on a properly tiled floor. Avoid the installation on a floor that is not tiled flat.
ENGLISH
STABILIZER 5 User’s manual
4 External Description
4.1 Front Panel
AVR informs the user about operating status, alarm conditions and measurements through a display on the front
panel.
Figure 1 – Front panel display FSTESM4K5M, FSTESM7K5M and FSTESM10KM
1. Normal
2. Delay Time
3. Over Voltage Protection
4. Low Voltage Protection
5. Protection (fault Mode)
6. Menu Push Button
7. Up Push Button
8. Down Push Button
9. Back Push Button
10. Output Current
11. Output Voltage
12. Input Voltage
1
2
3
4
5
6
7
8
9
10
11
1
2
ENGLISH
User’s manual 6 STABILIZER
Figure 2 – Front panel display FSTESM12KM and FSTESM18KM
Figure 3 – Front panel display FSTESM9KT - FSTESM18KT – FSTESM25KT – FSTESM50KT – FSTESC75KT –
FSTESC100KT
1. Menu Push Button
2. Up Push Button
3. Down Push Button
4. Back Push Button
5. Input Voltage
6. Output Voltage
7. Output Current
8. Status Mode
9. Volt Measure Push Button
10. Current Measure Push Button
1
2
3
4
5
6
7
9
10
8
1
2
3
4
5
6
7
8
ENGLISH
STABILIZER 7 User’s manual
4.2 Front Side and Rear Side
4.2.1 Single-Phase models
Figure 4 – Front and Rear side FSTESM4K5M, FSTESM7K5M and FSTESM10KM (1. Display, 2. Stabilizer Breaker,
3. Bypass Breaker, 4. Terminal Block Access Panel)
Figure 5 – Front side and rear side FSTESM12KM and FSTESM18KM (1. Display, 2. Stabilizer Breaker, 3. Bypass
Breaker, 4. Terminal Block Access Panel)
ENGLISH
User’s manual 8 STABILIZER
4.2.2 Three-Phase models
Figure 6 – Front side and rear side FSTESM9KT - FSTESM18KT – FSTESM25KT – FSTESM50KT (1. Display, 2.
Stabilizer Breaker, 3. Bypass Breaker, 4. Terminal Block Access Panel)
Figure 7 – Front side and left side FSTESC75KT – FSTESC100KT (1. Display, 2. Stabilizer Breaker, 3. Bypass
Breaker, 4. Terminal Block Access Panel)
ENGLISH
STABILIZER 9 User’s manual
4.3 Input/output Terminals
Figure 8 – INPUT/OUTPUT terminals for Single Phase Stabilizer
Figure 9 – INPUT/OUTPUT terminals for Three Phase Stabilizer
INPUT OUTPUT
L N L N
INPUT OUTPUT
L1 L2 L3 N L1 L2 L3 N
ENGLISH
User’s manual 10 STABILIZER
5 Electrical Installation
The electrical installation has to be done by qualified personnel. Follow all the Safety
Standards (CEI Standards in Italy or IEEE elsewhere) for the Input/Output connections
and for the right selection of Input/Output cables.
We recommend to use dedicate AC Input/Output power lines for the AVR.
For safety we recommend using external circuit breakers between Input mains and AVR
AC Input line and between AVR Output lines and the loads. The circuit breakers should
be qualified with leakage current protective function (leakage current < 30 mA).
Before starting the installation procedure, be sure that:
1. The AVR is “OFF” (check the Stabilizer Breaker is in OFF position).
2. The AC Input Voltage for the AVR has been removed.
The following table shows the recommended size (cross section) for Input, Output and Ground (GND) wires.
Single-Phase Models
Rated Power (KVA) 4,5 7,5 10 12 18
Input Cable (mm2) 4.0 4.0 6.0 10.0 14.0
Output Cable (mm2) 4.0 4.0 6.0 10.0 14.0
Ground Cable (mm2) 4.0 4.0 6.0 10.0 14.0
Three-Phase Models
Rated Power (KVA) 9 18 25 50 75 100
Input Cable (mm2) 2.5 4.0 6.0 14.0 18.0 40.0
Output Cable (mm2) 2.5 4.0 6.0 14.0 18.0 40.0
Ground Cable (mm2) 2.5 4.0 6.0 14.0 18.0 40.0
We recommend using only flexible TRI-RATED cables. Otherwise if you use rigid cables,
it will be difficult to move the AVR from initial positioning.
We recommend to use dedicate AC Input/Output power Lines for the AVR.
ENGLISH
STABILIZER 11 User’s manual
5.1 Installation
Connect the GROUND wire first when making wire connection. Disconnect the GROUND
wire last when making wire disconnection.
Make sure that the wires are connected tightly to the terminals.
We advise you to follow the steps below explained:
1. Single Phase models (see figures 4, 5 and 8)
1.1. Remove the metallic panel that covers the Input/Output terminals. The terminals are shown in figure 8.
All the cables have to reach the terminals from the rear side using the proper holes in the stabilizer rear
side.
1.2. Connect the AC INPUT line (LINE, NEUTRAL and GROUND), paying attention to the right polarity, in
accordance with figure 8, as explained below:
Connect INPUT GROUND wire to the GROUND terminal.
Connect INPUT LINE wire to the INPUT L terminal.
Connect INPUT NEUTRAL wire to the INPUT N terminal.
1.3. Connect the OUTPUT line (LINE, NEUTRAL and GROUND) as follow:
Connect OUTPUT GROUND wire to the GROUND terminal.
Connect OUTPUT LINE wire to the OUTPUT L terminal.
Connect OUTPUT NEUTRAL wire to the OUTPUT N terminal.
1.4. Reassemble the metallic panel that gives access to the Input/Output terminals.
1.5. Restore the AC Input mains Voltage to the AVR.
2. Three Phase models (see figures 6, 7 and 9).
2.1. Remove the metallic panel that covers the Input/Output terminals. The terminals are shown in figure 9.
All the cables have to reach the terminals from the rear side using the proper holes on the stabilizer. In
power models above 75KVA the terminals are behind the front door.
2.2. Connect the AC INPUT line (PHASE 1, PHASE 2, PHASE 3, NEUTRAL and GROUND), paying attention to
the right polarity, in accordance with figure 9, as explained below:
Connect GROUND wire to the GROUND terminal.
Connect PHASE 1 wire to the INPUT L1 terminal.
Connect PHASE 2 wire to the INPUT L2 terminal.
Connect PHASE 3 wire to the INPUT L3 terminal.
Connect NEUTRAL wire to the INPUT N terminal.
2.3. Connect the AC OUTPUT line (PHASE 1, PHASE 2, PHASE 3, NEUTRAL and GROUND), paying attention to
the right polarity, in accordance with figure 9, as explained below:
Connect GROUND wire to the GROUND terminal.
Connect PHASE 1 wire to the OUTPUT L1 terminal.
Connect PHASE 2 wire to the OUTPUT L2 terminal.
Connect PHASE 3 wire to the OUTPUT L3 terminal.
Connect NEUTRAL wire to the OUTPUT N terminal.
2.4. Reassemble the metallic panel that gives access to the Input/Output terminals.
2.5. Restore the AC Input mains Voltage to the AVR.
ENGLISH
User’s manual 12 STABILIZER
It is compulsory to ground the AVR according to the Safety Standards.
The case of the AVR is internally connected to the ground terminal (GND) of the IN/OUT
terminals, in order to guarantee safety to the user. To guarantee safety it is necessary
to be sure that the local electric plant is supplied with GROUND (in compliance with the
Safety Standards), and that a valid connection is guaranteed between the GROUND of
the AVR and the GROUND of the local electric plant.
Any interruption of the GROUND conductor is absolutely prohibited.
We recommend to use dedicate AC Input/Output power Lines for the AVR.
Risk of electric shock at the Output lines while the unit is connected to the AC utility
line.
Risk of electric shock: do not remove the cover. The AVR contains internal parts which
are at a high Voltage and are potentially dangerous, capable of causing injury or death
by electric shock.
There are no internal parts in the AVR which are user serviceable. Any repair or
maintenance work must be performed exclusively by qualified technical personnel
authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is
disregarded.
Disregard for these warnings may lead to a risk of electric shock to operators.
6 Functioning
6.1 Turning ON and OFF
All models have a main breaker called Stabilizer.
Let’s see carefully the consequences of the switching of Stabilizer breaker.
When the breaker is moved to the ON position, the AVR performs a test of about 5 seconds during which the Delay
led is active.
Then the AVR begins to work as a Stabilizer: the Output line is activated and all connected devices turn on.
Please check the following points:
1. The Normal led/indication is ON.
2. The Overload Protection led/indication must be OFF; otherwise it is necessary to remove part of the loads at
the Output line.
3. The AVR gives no indication of alarm or anomaly.
When the breaker is moved to the OFF position, the AVR stops to work as a stabilizer and switches off
immediately: the Output line is deactivated and all connected devices turn off.
ENGLISH
STABILIZER 13 User’s manual
6.2 Load Control
The AVR indicates the Output Load current value by the display on the front side.
When the Output load is higher than nominal value the AVR warns of Overload condition as follow explained:
the Overload Protection led/indication is ON.
a continuous acoustic alarm is ON.
The AVR has the capability to accept an Overload less than 125% for 30 seconds and then the AVR turns off.
If the Overload exceeds 125%, the AVR switches off immediately.
To turn on again the AVR after an overload shutdown, follow the steps below explained:
1. Disconnect the output loads that cause the Overload condition.
2. Move the Stabilizer breaker to the OFF position.
3. Move the Stabilizer breaker to the ON position.
Make sure that the AVR never indicates Overload condition.
Do not connect a load greater than rated value to the AVR (see POWER specifications in
the chapter “Technical Characteristics”), as this may damage the unit. In this case the
warranty is void.
6.3 Manual Bypass
There is another breaker called Bypass on the right of the Stabilizer breaker.
To enable Manual Bypass, the following steps must be taken:
1. Move the Stabilizer breaker to the OFF position.
2. Slide the metal lock on the Bypass breaker to the Stabilizer position.
3. Move the Bypass breaker to the ON position.
In Bypass mode, the AVR doesn’t work as a Stabilizer, but only as a Bypass between
Input and Output power lines.
To disable Manual Bypass and return to the normal operation of the AVR, follow the steps below explained:
1. Move the Bypass breaker to the OFF position.
2. Slide the metal lock on the Stabilizer breaker to the Bypass position.
3. Move the Stabilizer breaker to the ON position.
ENGLISH
User’s manual 14 STABILIZER
7 Technical Characteristics
Type AVR Model Input Voltage Output Voltage Frequency Output Power
Single-
Phase
FSTESM4K5M
160-270 Vac 220/230/240
(selectable) ±1% 50/60 Hz
4,5KVA
FSTESM7K5M 7,5 KVA
FSTESM10KM 10 KVA
FSTESM12KM 12 KVA
FSTESM18KM 18 KVA
Three-
Phase
FSTESM9KT
260-470 Vac 380/400/415
(selectable) ±1% 50/60 Hz
9 KVA
FSTESM18KT 18 KVA
FSTESM25KT 25 KVA
FSTESM50KT 50 KVA
FSTESC75KT 75 KVA
FSTESC100KT 100 KVA
Phase Three-Phase Single-Phase
Over Temperature If the temperature is high, the unit will shut down and alarm.
Delay Time 5 seconds
Manual Bypass YES
Overload Capability (100÷125)% for 30 sec with acoustic alarm; > 125% for 100 ms
Cooling Fan Cooling
Efficiency 98%
Noise ≤65 dB
Temperature 0°C to 45°C
Humidity 20% to 90%
Technical data may change without prior notice
ENGLISH
STABILIZER 15 User’s manual
8 Maintenance
8.1 AVR Cleaning
Before starting any cleaning operation, be sure that:
1. The Stabilizer breaker is “OFF”.
2. The AC Input Voltage for the AVR has been removed.
Use only a cloth dampened with water to clean the unit.
If AVR works in an environmental unusually dusty or dirty, remove the dirty from the ventilation holes.
Before restarting the AVR be sure it is completely dry. If any liquid gets inside the AVR, do not start the unit and
contact Technical Service immediately.
8.2 Operator Safety
Whenever the AVR is not responding anymore to original characteristics, the AVR must be made non-operative and
every usage not authorised must be avoided. After it will be necessary to refer to qualified technical personnel.
Original safety characteristics might not be if, for example, the AVR has visible damage or irregular operation.
9 Service
For any malfunction in operation or failure please contact the Technical Service and provide the following
information:
Model and serial number of the AVR, which can be found on the nameplate on the AVR.
Description of abnormal operation and alarm displayed on display.
Risk of electric shock: do not remove the cover. The AVR contains internal parts which
are at a high Voltage and are potentially dangerous, capable of causing injury or death
by electric shock.
There are no internal parts in the AVR which are user serviceable. Any repair or
maintenance work must be performed exclusively by qualified technical personnel
authorized by TECNOWARE.
TECNOWARE declines any responsibility if this warning is disregarded.
For any malfunction in operation or failure please contact:
TECNOWARE SERVICE
www.tecnoware.com
ENGLISH
User’s manual 16 STABILIZER
Conformity to the European Directives
TECNOWARE S.r.l. confirms that the product is comply with the requirements set out in: the Low Voltage (Safety) Directive
2014/35/EU and following amendments, the EMC (Electro-Magnetic Compatibility) Directive 2014/30/EU and following
amendments.
Produ
ct Disposal
The product cannot be disposed as an urban waste, but must be treated as a separate waste. Any
violation is indictable with financial sanctions as per in force regulations.
An incorrect waste disposal or an improper use of the same or of any parts can be damaging for the
environment and for human health.
A correct waste disposal of products having the dustbin symbol marked by a cross help to avoid
negative consequences to the environment and to human health.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40