MGE UPS Systems PULSAR EVOLUTION 3000 XL Manuale utente

Categoria
Gruppi di continuità (UPS)
Tipo
Manuale utente

Questo manuale è adatto anche per

3400711500/AA
MGE UPS SYSTEMS
Installation and user
manual
English
Français
Deutsch
Italiano
Español
Nederlands
Pulsar Evolution
2200/3000/3000 XL
N
O
T
HI
N
G
W
I
L
L
S
T
O
P
Y
O
U
N
OW
www.mgeups.com
34007115EN/AA - Page 1
Installation and user
manual
www.mgeups.com
N
O
T
H
I
N
G
W
I
L
L
S
T
O
P
Y
O
U
N
O
W
MGE UPS SYSTEMS
Pulsar Evolution
2200/3000/3000 XL
Page 2 - 34007115EN/AA
34007115EN/AA - Page 3
Introduction
Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar Evolution range has been designed with the utmost care. We recommend that you take the time to read this
manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar
Evolution a reference in environmental protection include:
the eco-design approach used in product development,
recycling of Pulsar Evolution at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar Evolution range,
we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
Page 4 - 34007115EN/AA
Foreword
Using this document
Important instructions that must always be followed.
Information, advice, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Information may be found in two ways, using:
the contents;
the index.
Pictograms
34007115EN/AA - Page 5
Contents
1. Presentation
1.1 Overall view ................................................................................................................................. 7
Tower position ................................................................................................................................. 7
Rack position .................................................................................................................................. 7
1.2 Back ............................................................................................................................................. 8
1.3 Control panel ................................................................................................................................. 9
2. Installation
2.1 Unpacking and parts check ....................................................................................................... 10
2.2 Upright installation (tower position) ......................................................................................... 11
2.3 Flat installation (rack position) .................................................................................................. 12
2.4 Connecting the protected equipment ....................................................................................... 13
2.5 Connection to the RS232 or USB communications port (optional)......................................... 14
2.6 Connection to the data-line protection port (optional) ............................................................. 14
2.7 Installation of the communications-card option ...................................................................... 15
3. Operation
3.1 Start-up ........................................................................................................................................ 16
3.2 Shift to booster or fader mode (during voltage variations in the AC-input power)..................... 16
3.3 Operation on battery power (following failure of AC-input power) ............................................. 17
Transfer to battery power .............................................................................................................. 17
Threshold for the low-battery warning...........................................................................................17
3.4 Personalisation (optional) ........................................................................................................... 18
Function ........................................................................................................................................ 18
ON / OFF conditions tab ............................................................................................................... 18
Battery tab..................................................................................................................................... 18
Voltage-thresholds tab .................................................................................................................. 19
Sensitivity tab ................................................................................................................................ 19
4. Maintenance
4.1 Trouble-shooting......................................................................................................................... 20
4.2 Replacement of the battery module .......................................................................................... 21
5. Environment ..................................................................................................................................... 23
Page 6 - 34007115EN/AA
Contents
6. Appendices
6.1 Technical data ............................................................................................................................. 24
Simplified diagram ........................................................................................................................ 24
Technical characteristics ............................................................................................................... 25
Examples of battery backup times ................................................................................................26
6.2 Glossary....................................................................................................................................... 27
6.3 Index............................................................................................................................................. 28
34007115EN/AA - Page 7
1. Presentation
1.1 Overall view
Tower position
Rack position
Evolution 2200
Evolution 3000
Evolution 3000 XL
Evolution 2200
Evolution 3000
Evolution 3000 XL
Dimensions in mm
(W x H x D)
438 x 87.9 x 640
(19") (2U)
Weight in kg
34
37
21
P U L S A R
Evolution
3 0 0 0
P U L S A R
Evolution
3 0 0 0
W
H
D
Page 8 - 34007115EN/AA
1 2
IN OUT
Ue/In/Eing 230V/16A Max
DATA LINE PROTECTION
AB
1
2
Us/Out/Ausg I max 13A
AB
TO BATTERY
CABINET
RS232
1 2
IN OUT
Ue/In/Eing 230V/10A Max
TO BATTERY
CABINET
DATA LINE PROTECTION
Us/Out/Ausg I max 10A
RS232
1. Presentation
1.2 Back
Pulsar Evolution 3000 / 3000 XL
Pulsar Evolution 2200
USB communications port.
RS232 communications port.
Connector for automatic detection of an
additional battery module.
Data-line protection.
Slot for communications-card option.
Connector for an additional battery
module.
Output circuit breakers.
Four outlets for direct connection of
protected equipment.
Two groups of two programmable
outlets (groups 1 and 2).
Input circuit-breaker.
Socket for connection to AC-power
source.
Battery module connectors (to the UPS
or to other battery modules).
Connectors for automatic detection of
additional battery modules.
Circuit breaker for battery ON/OFF and
protection.
1
2
3
4
5
6
7
9
8
10
11
12 14
EXB additional battery module 12
13
14
13 12
7
1234 115 1098
12
6
1234 115 109
8
12
6
34007115EN/AA - Page 9
12
%
%
1.3 Control panel
Bargraph indicating percent load at output.
Group 1 programmable outlets supplied with power.
Iluminated ON/OFF button for the outlets.
Group 2 programmable outlets supplied with power.
Operation on battery power.
15
16
17
20
19
23
22
18
21
1. Presentation
UPS fault.
Battery fault.
Overload.
Booster or fader mode.
Bargraph indicating the battery charge level.
0 to 25%.
26 to 50%.
51 to 75%.
76 to 100%.
Page 10 - 34007115EN/AA
2. Installation
2.1 Unpacking and parts check
Cord for connection to the AC-power source for 3000/3000 XL versions only (for the 2200 version, use the power cord
of the protected equipment).
Two cords for connection of the protected equipment.
RS232 communications cable.
USB communications cable.
Telescopic rails for mounting in 19" bay with mounting hardware.
Two securing systems for equipment power cords.
CD-ROM with the Solution-Pac and UPS Driver software.
Product documentation.
Two supports for the upright position.
27
28
29
25
24
25
26
27
28
26
24
29
31
32
31
32
30
30
P U L S A R
Evolution
3 0 0 0
34007115EN/AA - Page 11
2. Installation
2.2 Upright installation (tower position)
Connect the two supports for the upright position.
P U L S A R
Evolution
3 0 0 0
P U L S A R
Evolution
3 0 0 0
Page 12 - 34007115EN/AA
2. Installation
2.3 Flat installation (rack position)
Follow steps 1 to 6 for rack mounting of the UPS on the rails.
The rails and the necessary mounting hardware are supplied by MGE UPS SYSTEMS.
1
2
2
2
2
5
3
6
6
5
4
3
P U L S A R
Evolution
3 0 0 0
34007115EN/AA - Page 13
Ue/In/Eing 230V/10A Max
1 2
Us/Out/Ausg I max 10A
2.4 Connecting the protected equipment
Check that the indications on the rating plate on the back of the UPS correspond to your AC-power system and to
the actual electrical consumption of all the equipment to be connected to the UPS.
1 - Remove the power cord supplying the
equipment to be protected.
2 - Pulsar Evolution 2200: Connect the
power cord (1) just removed from the
equipment to the AC-power socket 11 and
then to the AC-power wall outlet.
- Pulsar Evolution 3000/3000 XL: Connect
the supplied power cord 24 (250 V, 16 A) to
the AC-power socket 11 and then to the
AC-power wall outlet.
3 - Connect the protected equipment to the
UPS using the two cords 25 . It is advised
to connect priority loads to the four standard
outlets 8 and any non-priority loads to the
four programmable outlets 9 (in groups of
two outlets).
If the UPS is connected to a
computer running MGE
communications software, it is
possible to program the
interruption of power to the
programmable outlets 9 during
operation on battery power, thus
reserving backup power for the
priority loads.
4 - Lock the connections using the securing
system 29 .
25
8
9
1
2
2. Installation
11
29
As soon as the UPS is energised, the battery begins charging. Eight hours are required to charge to the full rated
backup time.
Pulsar Evolution 3000 XL: At least one EXB additional battery module must be connected to the UPS because it does not
have internal batteries. See the EXB battery-module installation manual (Doc. no. 3400711600) for information on making
the connections.
(1) Make sure the cord has the following
characteristics: 250 V, 10 A, cross-sectional area 1
mm2, type HO5.
Page 14 - 34007115EN/AA
IN OUT
DATA LINE PROTECTION
TO BATTERY
CABINET
RS232
2. Installation
2.5 Connection to the RS232 or USB communications port (optional)
1 - Connect the RS232 26 or USB 27
communications cable to the serial port or
the USB port on the computer.
2 - Connect the other end of the
communications cable 26 or 27 to the
RS232 2 or USB 1 communications
port on the UPS.
The UPS can now communicate with all
MGE UPS SYSTEMS supervision, set-up or
safety software.
26
27
The RS232 and USB
communications ports cannot
operate simultaneously.
2.6 Connection to the data-line protection port (optional)
The data-line protection function on the UPS
eliminates overvoltages flowing on the
computer-network lines.
Simply connect the line to be protected to
the UPS using the data-line protection
connectors (IN and OUT) as indicated
opposite (RJ45 cables not supplied).
1
2
IN OUT
TO BATTERY
CABINET
DATA LINE PROTECTION
RS232
34007115EN/AA - Page 15
2. Installation
2.7 Installation of the communications-card option
1 - Remove the slot cover 5 secured by
two screws.
2 - Insert the card in the slot.
3 - Secure the cover with the two screws.
Slot for the communications-card
option.
5
IN OUT
TO BATTERY
CABINET
DATA LINE PROTECTION
RS232
It is not necessary to shut down the UPS to install the communications card.
Page 16 - 34007115EN/AA
12
%
%
3. Operation
3.1 Start-up
15
16
17
Press the ON / OFF button 15 .
The buzzer beeps and all the LEDs come ON.
The buzzer beeps twice during the self-test, then button 15 remains
ON, indicating that the outlets are supplied with power.
- AC power is present: Only button 15 is ON. The protected
equipment is supplied by the AC-power source.
- AC power is absent: Button 15 and LED 16 are ON. The protected
equipment is supplied by the UPS, operating on battery power.
All the connected equipment is supplied with power.
12
%
%
3.2 Shift to booster or fader mode
(during voltage variations in the AC-input power)
21
The booster and fader functions maintain the output voltage supplied by
the UPS within close tolerances around the rated value even if
significant voltage variations occur in the AC-input power. This avoids
calling on battery power.
The values defining the voltage range may be set using the UPS Driver
software.
During operation in booster or fader mode, LED 21 is ON, signalling a
significant voltage variation in the AC-input power.
If button 15 or LED 16 are not ON or if LED 17 is ON, there is a fault (see section 4.1).
Note: The battery is charged as soon as the UPS is connected to the AC-power source, even if button 15 is in the OFF
position.
34007115EN/AA - Page 17
12
%
%
12
%
%
3. Operation
3.3 Operation on battery power (following failure of AC-input power)
Transfer to battery power
The AC-input power is out of tolerances, LED 16 goes ON.
During operation on battery power, the buzzer beeps every ten seconds.
The equipment connected to the UPS is supplied by the battery.
Threshold for the low-battery warning
When the threshold is reached, the buzzer beeps every three seconds.
The low-battery warning threshold can be set by the user, with the “UPS
Driver” software.
There is very little remaining battery backup time. Close all
applications because UPS automatic shutdown is imminent.
When the battery reaches the end of its backup time, the UPS shuts
down and all the LEDs go OFF.
The equipment is no longer supplied with power.
16
The UPS automatically restarts when power returns.
If the UPS does not restart, check that the “automatic restart when power returns” function has not been disabled (see
section 3.4 Personalisation).
16
Page 18 - 34007115EN/AA
3. Operation
3.4 Personalisation (optional)
Function
Configurable function
Automatic restart
Cold start
Forced reboot
Energy saving
UPS ON / OFF via software
Default setting
Enabled
Enabled
Enabled
Disabled
Enabled
Personalisation parameters can be set and modified using the UPS Driver software installed on a computer that is
connected to the UPS (see section 2.5 Connection to the RS232 communications port).
Check that the RS232 26 communications cable is connected.
UPS Driver installation:
1 - Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running Windows.
2 - Open the Windows File manager or Explorer and select the CD-ROM drive.
3 - Double-click "\Emb\Evolutio\Config\Setup.exe".
Once UPS Driver has been installed, UPS parameters can be modified in a window containing a number of tabs, each
presenting a set of parameters :
Battery tab
Configurable function
Interval between automatic battery tests
Low-battery warning threshold
Configuration of additional battery modules
Protection against deep discharges
Default setting
Once a week
20% of the remaining battery
backup time
Display the number of standard
EXB modules connected
to the UPS
Enabled
Options
Every day
Once a month
No test
10 to 40% of the remaining battery
backup time
Back-up time for non-standard
batteries (for 3000XL only)
Disabled
Options
Disabled
Disabled
Disabled
Enabled
Disabled
ON / OFF conditions tab
34007115EN/AA - Page 19
3. Operation
Configurable function
Output voltage on battery power
Upper threshold for transfer to battery power
Fader-mode cut-in threshold
Booster-mode cut-in threshold
Lower threshold for transfer to battery power
Maximum input-voltage range
Default setting
230 V
294 V
265 V
184 V
160 V
Disabled
Options
200 V - 220 V - 240 V
271 to 294 V
244 to 265 V
184 to 207 V
160 to 180 V
Enabled (1)
Configurable function
UPS sensitivity level
Default setting
Normal
Options
High or low
Voltage-thresholds tab
Sensitivity tab
For more informations about these settings, refer to the Help function of the "UPS Driver" software.
(1) Lower threshold for transfer to battery power = 150 V
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172

MGE UPS Systems PULSAR EVOLUTION 3000 XL Manuale utente

Categoria
Gruppi di continuità (UPS)
Tipo
Manuale utente
Questo manuale è adatto anche per