Mitsubishi Heavy Industries SAF150E7 Manuale utente

Tipo
Manuale utente

Questo manuale è adatto anche per

SAF150E7
SAF250E7
SAF350E7
SAF500E7
SAF800E7
SAF1000E7
SAF500E7
USER’S MANUAL
VENTILATION AND HEAT EXCHANGE UNIT
(ENERGY RECOVERY VENTILATOR)
This air-conditioner complies with following directive.
Machinery 2006/42/EC
Low Voltage 2014/35/EU
EMC 2014/30/EU
RoHS 2011/65/EU
Ecodesign 2009/125/EC
Energy labelling 2010/30/EU
CE marking is applicable to the area of 50 Hz power supply.
Ce climatiseur est conforme aux directives suivantes.
Machines 2006/42/CE
Basse tension 2014/35/UE
CEM 2014/30/UE
RoHS 2011/65/UE
Écoconception 2009/125/CE
Label énergétique 2010/30/UE
La marque CE s'applique aux régions alimentées en courant de 50 Hz.
Diese Klimaanlage erfüllt die folgende Richtlinie.
Maschinen 2006/42/EC
Niederspannung 2014/35/EU
EMV 2014/30/EU
RoHS 2011/65/EU
Ökodesign 2009/125/EC
Energiekennzeichnung 2010/30/EU
Die CE-Marke gilt für Bereiche mit einer Netzstromversorgung von 50 Hz.
Questo condizionatore d'aria è conforme alla seguente direttiva.
Macchinario 2006/42/CE
Bassa tensione 2014/35/UE
EMC 2014/30/UE
RoHS 2011/65/UE
Ecodesign 2009/125/CE
Etichettatura energetica 2010/30/UE
Il marchio CE è applicabile alla fascia di alimentazione 50 Hz.
Este aire acondicionado cumple con la siguiente directiva.
Máquinas 2006/42/CE
Baja tensión 2014/35/UE
EMC 2014/30/UE
RoHS 2011/65/UE
Ecodiseño 2009/125/CE
Etiquetado energético 2010/30/UE
La indicación CE sólo corresponde al área de suministro eléctrico de 50 Hz.
MANUEL DE L’UTILISATEUR
CONDITIONNEUR D’AIR MONOBLOC ENCHASTRE A GAINES
(VENTILATEUR D’ÉCHANGE DE CHALEUR)
ANWENDERHANDBUCH
LUFT-LUFT-WÂRMETAUSCHER
(ENERGIEGEWINNUNGS-VENTILATOR)
ISTRUZIONI PER L’USO
SCAMBIATORE DI CALORE AIR-TO-AIR
(VENTILATORE A RECUPERO ENERGETICO)
MANUAL DEL PROPIETARIO
UNIDAD INTERCAMBIADORA DE CALOR DE AIRE A AIRE
(VENTILADOR CON RECUPERACIÓN DE ENERGÍA)
PCH012A010
ORIGINAL INSTRUCTIONS
PCH012A010.indb 1 2017/09/28 11:46:03
PCH012A010.indb 2 2017/09/26 21:15:53
PCH012A010.indb 1 2017/09/26 21:15:54
■If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to
avoid a hazard.
■This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance
in a safe way and understand the hazards involves.
■Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
■Make sure to disconnect the power plug before cleaning the product.
PCH012A010.indb 2 2017/09/26 21:15:54
PCH012A010.indb 3 2017/09/26 21:15:54
PCH012A010.indb 4 2017/09/26 21:15:54
SAF150E7
SAF250E7
SAF350E7
SAF500E7
SAF800E7
SAF1000E7
SAF150E7
Model No.
SAF350E7
SAF500E7
SAF800E7
SAF1000E7
970
A
1050
1090
1322
1322
467
B
804
904
884
1134
270
SAF250E7
882
599
270
C
317
317
388
388
Energy Recovery Ventilator Remocon
Energy Recovery Ventilator Remocon
PCH012A010.indb 5 2017/09/26 21:15:55
Operate the Energy Recovery Ventilator
Remocon with certainty.In particular,
suddenly turning the switch on and off will
not only cause improper operation of the
unit,but will also affect the relay inside the
switch,and may damage it.
PCH012A010.indb 6 2017/09/26 21:15:55
For detail,please refer to the“Energy Recovery Ventilator Remocon”manual.
PCH012A010.indb 7 2017/09/26 21:15:55
PCH012A010.indb 8 2017/09/26 21:15:55
Item
Model No.
SAF150E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 97-114 92-107 69-77 97-114 92-107 69-77
Air Volume (m
3
/h) 150 150 120 150 150 120
External Static Pressure
(Pa)
80 70 25 80 70 25
Noise (dB) 28.5-29.0 28.0-29.0 19.5-21.5 28.5-29.0 28.0-29.0 19.5-21.5
Temperature Exchange
Efency(%)
75 75 77
Dimensions(mm) Width 970 × Depth 467 × Height 270
Weight (kg) 25
Item
Model No.
SAF250E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 112-128 108-123 87-96 112-128 108-123 87-96
Air Volume (m
3
/h) 250 250 190 250 250 190
External Static Pressure
(Pa)
105 95 45 105 95 45
Noise (dB) 30.0-31.5 29.5-30.5 23.5-26.5 30.0-31.5 29.5-30.5 23.5-26.5
Temperature Exchange
Efency(%)
75 75 77
Dimensions(mm) Width 882 × Depth 599 × Height 270
Weight (kg) 29
Item
Model No.
SAF350E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 182-190 178-185 175-168 182-190 178-185 175-168
Air Volume (m
3
/h) 350 350 240 350 350 240
External Static Pressure
(Pa)
140 60 45 140 60 45
Noise (dB) 32.5-33.0 30.5-31.0 22.5-25.5 32.5-33.0 30.5-31.0 22.5-25.5
Temperature Exchange
Efency(%)
75 75 78
Dimensions(mm) Width 1050 × Depth 804 × Height 317
Weight (kg) 49
Specifications
9
PCH012A010.indb 9 2017/09/26 21:15:56
Item
Model No.
SAF500E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 263-289 204-225 165-185 263-289 204-225 165-185
Air Volume (m
3
/h) 500 500 440 500 500 440
External Static Pressure (Pa)
120 60 35 120 60 35
Noise (dB) 36.5-37.5 34.5-35.5 31.0-32.5 37.5-38.5 37.0-38.0 31.0-32.5
Temperature Exchange
Efency(%)
75 75 76
Dimensions(mm) Width 1090 × Depth 904 × Height 317
Weight (kg) 57
Item
Model No.
SAF800E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 387-418 360-378 293-295 387-418 360-378 293-295
Air Volume (m
3
/h) 800 800 630 800 800 630
External Static Pressure (Pa)
140 110 55 140 110 55
Noise (dB) 37.0-37.5 36.5-37.0 33.5-34.5 37.0-37.5 36.5-37.0 33.5-34.5
Temperature Exchange
Efency(%)
75 75 76
Dimensions(mm) Width 1322 × Depth 884 × Height 388
Weight (kg) 71
Item
Model No.
SAF1000E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 437-464 416-432 301-311 437-464 416-432 301-311
Air Volume (m
3
/h) 1000 1000 700 1000 1000 700
External Static Pressure (Pa)
105 80 75 105 80 75
Noise (dB) 37.5-38.5 37.0-37.5 33.5-34.5 39.5-40.5 39.0-39.5 35.5-36.5
Temperature Exchange
Efency(%)
75 75 79
Dimensions(mm) Width 1322 × Depth 1134 × Height 388
Weight (kg) 83
(Note) The ratings mentioned above shows the values under the external static pressure.
(Only the noise level shows the value under the external static pressure: 0Pa)
Noise Level shall be measured 1.5 m below the center of the unit. (It shall be measured at the
acoustic room.)
10
PCH012A010.indb 10 2017/09/26 21:15:56
EC DECLARATION OF CONFORMITY
MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.
16-5 Konan 2-chome, Minato-ku, Tokyo, 108-8215, Japan
declare under our sole responsibility that the apparatus referred to in this declaration conforms with the
following directives.
Description of apparatus: Heat Exchanger Unit
Model name: SAF Series
Relevant EU Directives :
Machinery Directive 2006/42/EC
Applied Standards :
EN 60335-1
Authorized representative in EU :
MITSUBISHI HEAVY INDUSTRIES AIR-CONDITIONING EUROPE, LTD.
7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
Note : About the detail of Conformity model, see EC DECLARATION OF CONFORMITY sheet
included in a package
PCH012A010.indb 3 2017/09/26 21:16:07
MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.
16-5 Konan 2-chome, Minato-ku, Tokyo, 108-8215, Japan
http://www.mhi.co.jp/aircon/
MITSUBISHI HEAVY INDUSTRIES AIR-CONDITIONING EUROPE, LTD.
7 Roundwood Avenue, Stockley Park, Uxbridge, Middlesex, UB11 1AX, United Kingdom
Tel: +44-20-7025-2750
Fax: +44-20-7025-2751
http://www.mhiae.com
PCH012A010.indb 4 2017/09/26 21:16:07
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14

Mitsubishi Heavy Industries SAF150E7 Manuale utente

Tipo
Manuale utente
Questo manuale è adatto anche per