Item Model No. SAF500E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 263-289 204-225 165-185 263-289 204-225 165-185
Air Volume (m3/h) 500 500 440 500 500 440
External Static Pressure (Pa)
120 60 35 120 60 35
Noise (dB) 36.5-37.5 34.5-35.5 31.0-32.5 37.5-38.5 37.0-38.0 31.0-32.5
Temperature Exchange
Efency(%) 75 75 76 — — —
Dimensions(mm) Width 1090 × Depth 904 × Height 317
Weight (kg) 57
Item Model No. SAF800E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 387-418 360-378 293-295 387-418 360-378 293-295
Air Volume (m3/h) 800 800 630 800 800 630
External Static Pressure (Pa)
140 110 55 140 110 55
Noise (dB) 37.0-37.5 36.5-37.0 33.5-34.5 37.0-37.5 36.5-37.0 33.5-34.5
Temperature Exchange
Efency(%) 75 75 76 — — —
Dimensions(mm) Width 1322 × Depth 884 × Height 388
Weight (kg) 71
Item Model No. SAF1000E7
Power Source 220-240V~ 50Hz
Ventilation Mode Heat Exchange Ventilation Normal Ventilation
Notch (Extra high) High Low (Extra high) High Low
Input (W) 437-464 416-432 301-311 437-464 416-432 301-311
Air Volume (m3/h) 1000 1000 700 1000 1000 700
External Static Pressure (Pa)
105 80 75 105 80 75
Noise (dB) 37.5-38.5 37.0-37.5 33.5-34.5 39.5-40.5 39.0-39.5 35.5-36.5
Temperature Exchange
Efency(%) 75 75 79 — — —
Dimensions(mm) Width 1322 × Depth 1134 × Height 388
Weight (kg) 83
(Note) The ratings mentioned above shows the values under the external static pressure.
(Only the noise level shows the value under the external static pressure: 0Pa)
Noise Level shall be measured 1.5 m below the center of the unit. (It shall be measured at the
acoustic room.)
10
PCH012A010.indb 10 2017/09/26 21:15:56