Eaton
®
BladeUPS
®
User’s Guide
(Preassembled and Standard Systems)
For use with Eaton BladeUPS 12 kVA to 60 kVA (N+1) systems
Class A EMC Statements
FCC Part 15
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,
may cause harmful interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference, in which case the user will be required to correct the interference at his
own expense.
ICES-003
This Class A Interference Causing Equipment meets all requirements of the Canadian Interference Causing
Equipment Regulations ICES-003.
Cet appareil numérique de la classe A respecte toutes les exigences du Reglement sur le matériel brouilleur du
Canada.
EN 62040-2
Some configurations are classified under EN 62040-2 as “Class-A UPS for Unrestricted Sales Distribution.” For
these configurations, the following applies:
WARNING
This is a Class A-UPS Product. In a domestic environment, this product may cause radio
interference, in which case the user may be required to take additional measures.
Eaton is are registered trademarks Eaton Corporation or its subsidiaries and affiliates. Phillips and Pozidriv are
a registered trademarks of Phillips Screw Company. National Electrical Code and NEC are registered
trademarks of National Fire Protection Association, Inc. All other trademarks are properties of their respective
companies.
©Copyright 2007–2012 Eaton Corporation, Raleigh NC, USA. All rights reserved. No part of this document may
be reproduced in any way without the express written approval of Eaton Corporation.
Requesting a Declaration of Conformity
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:
l
Harmonized Standards: IEC 61000-3-12
l
EU Directives:
73/23/EEC, Council Directive on equipment designed for use within certain voltage limits
93/68/EEC, Amending Directive 73/23/EEC
89/336/EEC, Council Directive relating to electromagnetic compatibility
92/31/EEC, Amending Directive 89/336/EEC relating to EMC
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC
Declaration of Conformity, contact:
Eaton Power Quality Oy
Koskelontie 13
FIN-02920 Espoo
Finland
Phone: +358-9-452 661
Fax: +358-9-452 665 68\
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk
of electric shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's
manual for additional information, such as important operating and
maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS
batteries in the trash. This product contains sealed, lead-acid batteries and
must be disposed of properly. For more information, contact your local
recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or
electronic equipment (WEEE) in the trash. For proper disposal, contact your
local recycling/reuse or hazardous waste center.
Table of Contents
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164291649—Rev 7 i
Table of Contents
1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2 SAFETY WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 PREASSEMBLED SYSTEM INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Tools Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Floor Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Moving the System and Battery Pallets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Installing the Ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Unloading the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Preassembled System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Preparing the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Installing the Input and Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installing the UPS Internal Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
EBM Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Checking the EBM Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Rack Setup for the EBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
EBM Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Parallel System Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
4 STANDARD SYSTEM INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Tools Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Unpacking the Cabinet. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Parallel System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Preparing the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Installing the Input and Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
EBM Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Checking the EBM Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Rack Setup for the EBM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
UPS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Checking the UPS Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Rack Setup for the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Installing the UPS Internal Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
EBM Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Standalone UPS Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Parallel UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
New Multiple Parallel UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Single Parallel-Ready UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
UPS Installation into an Existing Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Standalone UPS Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Parallel System Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
5 OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Control Panel Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Changing the Language. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Table of Contents
ii Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164291649—Rev 7
Display Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
User Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Standby Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
UPS Startup and Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Starting a Standalone UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
Starting a Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Starting the UPS on Internal Bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Standalone UPS Shutdown. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Individual Paralleled UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Parallel System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
Transferring the UPS Between Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Setting Power Strategy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Configuring Battery Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Configuring the UPS for EBMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Configuring the UPS for Customer-Supplied External Batteries . . . . . . . . . . . . . . . . . . . . . . . . 99
Setting the Battery Low Alarm Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Running Automatic Battery Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
6 COMMUNICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Installing Communication Options and Control Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
DB-9 Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
X-Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Control Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Relay Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Programmable Signal Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Remote Emergency Power-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Installing REPO for a Standalone UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Installing REPO for a Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Parallel Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Mode Transfers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Redundant Signal Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Auto-Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
7 UPS MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
UPS and Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Storing the UPS and Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
When to Replace Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Replacing Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
How to Replace EBMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
How to Replace UPS Internal Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Testing New Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Replacing the Electronics Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Replacing a UPS in a Parallel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Table of Contents
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164291649—Rev 7 iii
Recycling the Used Battery or UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Updating the UPS Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
8 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
9 WARRANTY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Eaton
®
UPS Model: BladeUPS
®
(Global) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Table of Contents
iv Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164291649—Rev 7
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 1
Chapter 1 Introduction
The Eaton
®
BladeUPS
®
module is an uninterruptible power system (UPS) that protects your sensitive electronic
equipment from the most common power problems, including power failures, power sags, power surges,
brownouts, and line noise.
Power outages can occur when you least expect it, and power quality can be erratic. These power problems
have the potential to corrupt critical data, destroy unsaved work sessions, and damage hardware—causing
hours of lost productivity and expensive repairs.
With the BladeUPS module, you can safely eliminate the effects of power disturbances and guard the integrity
of your equipment. The BladeUPS module is designed for critical applications such as ultra high-density blade
servers in a data center environment. Figure 1 shows the BladeUPS module with an optional Extended Battery
Module (EBM).
Figure 1. The BladeUPS Module with Optional EBM
Providing outstanding performance and reliability, the BladeUPS module’s unique benefits include the
following:
l
High-density three-phase input, three-phase output UPS.
l
Scalability to 60 kW (redundant N+1 configuration) by connecting up to five additional parallel UPSs. A
standalone UPS converts to a parallel UPS by changing the line cord. Each UPS in the parallel system
connects to a BladeUPS Bar pre-installed in the rear of an Eaton rack. Racks can be configured for bottom or
top entry.
A Powerware Hot Sync
®
Controller Area Network (CAN) Bridge Card in each paralleled UPS provides
connectivity for system metering and operational mode control. In a parallel system that is not fully loaded,
the system will shift load to UPSs with the strongest batteries to maximize runtime when on battery. Parallel
systems can be configured for capacity or redundancy.
l
6U height that fits any standard 19-inch rack.
Introduction
2 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7
l
Normal operating mode that minimizes heat generation by operating typically at >98% efficiency. The UPS
filters incoming AC power and provides consistent power to your equipment without draining the battery.
l
For utility line input that exceeds normal operating range, automatic transfer to an online, double-conversion,
high-frequency UPS design with pure sine wave output and power-factor correction.
l
ABM
®
technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life.
l
Hot-swappable electronics module and batteries that simplify maintenance by allowing you to replace them
safely without powering down the critical load.
l
Emergency shutdown control through the remote emergency power-off (REPO) port.
l
One standard communication option with a DB-9 serial port.
l
Firmware that is service upgradable through the DB-9 communication port.
l
Backed by worldwide agency approvals.
The following accessories for the BladeUPS module are available:
l
Maintenance Bypass Module (MBM) to safely service the UPS without disrupting power.
l
BladeUPS 12i model only. External Battery Interconnect to connect a customer-supplied external battery to
the UPS for extended runtime.
l
EBM for extended runtime, with up to four EBMs per UPS. A 0.9m (3 ft) battery extension cable is available.
l
X-Slot
®
cards with enhanced communication capabilities for network connectivity with monitoring and
control.
The BladeUPS Bar for parallel systems, mounted in the rear of an Eaton rack, provides the required input and
output connections for the paralleled UPSs and has a single system-rated input connection. Figure 2 shows an
example of a BladeUPS parallel system.
The BladeUPS system can be installed with Eaton remote power panels and rack-mounted power distribution
systems (see Figure 2).
Introduction
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 3
Figure 2. Example of a BladeUPS Parallel System
Note the following guidelines when configuring your BladeUPS standalone module or parallel system:
l
The UPS accommodates a maximum of four EBMs.
l
The EBM(s) for a standalone UPS can be mounted directly below the UPS or, with rack side panels removed,
in an adjacent rack to the left of the rack containing the UPS.
l
The EBMs for a parallel system can be mounted in an adjacent rack to the left of the rack containing the UPS
(rack side panels removed).
l
When configured with EBMs, each UPS in a parallel system must have the same number of EBMs installed.
l
Some load equipment may require phase rotation or phase relationship coordination to ensure proper
operation. Review your equipment manufacturer’s power requirement documents to ensure that your
connected equipment operates correctly.
Figure 56 on page 66 shows an example of a standalone UPS with EBMs. Figure 57 on page 67 and Figure 58
on page 68 show examples of a parallel system with EBMs.
BladeUPS Module
BladeUPS Module
Bottom Entry
Wireway
BladeUPS Bar
BladeUPS Module
Introduction
4 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 5
Chapter 2 Safety Warnings
IMPORTANT SAFETY INSTRUCTIONS — SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the UPS and batteries. Read all instructions before operating the equipment and
save this manual for future reference.
DANGER
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside
the UPS.
WARNING
l
This UPS contains its own energy source (batteries). The UPS output may carry live voltage
even when the UPS is not connected to an AC supply.
l
To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants. Ambient temperature must
not exceed 40°C (104°C). Do not operate near water or excessive humidity (95% maximum).
l
To reduce the risk of fire, connect only to a circuit provided with branch circuit overcurrent
protection in accordance with the National Electrical Code
®
(NEC
®
), ANSI/NFPA 70. See page 68
(standalone UPS) or page 71 (parallel system).
l
Output overcurrent protection and disconnect switch must be provided by others.
l
To comply with international standards and wiring regulations, the sum of the leakage current of
the UPS and the total equipment connected to the output of this UPS must not have an earth
leakage current greater than 3.5 milliamperes.
CAUTION
l
Batteries can present a risk of electrical shock or burn from high short-circuit current. Observe
proper precautions. Servicing should be performed by qualified service personnel
knowledgeable of batteries and required precautions. Keep unauthorized personnel away from
batteries.
l
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
l
Never dispose of batteries in a fire. Batteries may explode when exposed to flame.
Safety Warnings
6 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7
Sikkerhedsanvisninger
VIGTIGE SIKKERHEDSANVISNINGER — GEM DISSE ANVISNINGER
Denne manual indeholder vigtige instruktioner, som skal følges under installation og
vedligeholdelse af UPS’en og batterierne. Læs venligst alle instruktioner inden betjening af
udstyret og gem denne manual mhp. fremtidige opslag.
FARE
Denne UPS indeholder LIVSFARLIG HØJSPÆNDING. Alle reparationer og vedligeholdelse bør kun
udføres af en AUTORISERET SERVICETEKNIKER. Ingen af UPS’ens indvendige dele kan repareres
af brugeren.
ADVARSEL!
l
Denne UPS indeholder sin egen energikilde (batterier). Udgangsstikket på UPS’en kan endog
være strømførende, når UPS’en ikke er koblet til en vekselstrømsforsyning.
l
Installér denne UPS i et temperatur- og fugtighedskontrolleret indendørsmiljø, frit for ledende
forureningsstoffer for at formindske risikoen for brand og elektrisk stød. Rumtemperaturen må
ikke overstige 40°C. UPS’en bør ikke betjenes nær vand eller høj fugtighed (maksimalt 95%).
l
For at reducere risikoen for brand må tilkobling kun ske til et kredsløb forsynet med 100 ampere
maks. linieforgrenings overbelastningsbeskyttelse i overensstemmelse med National Electrical
Code, ANSI/NFPA 70. Se efter side 70 eller side 46.
l
Udgangsoverbelastningsbeskyttelsen og afbryderkontakten skal leveres af andre.
l
I overensstemmelse med internationale normer og bestemmelser for el-installation må det
udstyr, der er forbundet til udgangen af denne UPS, tilsammen ikke overskride en
jordafdelingsspænding på mere end 3,5 milliampere.
ADVARSEL
l
Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj kortslutningsstrøm.
Overhold gældende forsigtighedsregler. Servicering skal udføres af kvalificeret servicepersonale
med kendskab til batterier og gældende forsigtighedsregler. Hold uautoriseret personale væk fra
batterierne.
l
Korrekt bortskaffelse af batterier er påkrævet. Overhold gældende lokale regler for
bortskaffelsesprocedurer.
l
Skaf dig aldrig af med batterierne ved at brænde dem. Batterierne kan eksplodere ved åben ild.
Belangrijke Veiligheidsinstructies
BELANGRIJKE VEILIGHEIDSINSTRUCTIES — BEWAAR DEZE INSTRUCTIES
Deze handleiding bevat belangrijke instructies die u dient te volgen tijdens de installatie en het
onderhoud van de UPS en de accu’s. Lees alle instructies voordat u de apparatuur in bedrijf neemt
en bewaar deze handleiding als naslagwerk.
Safety Warnings
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 7
GEVAAR
Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING. Alle reparaties en onderhoud
dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd. Er bevinden
zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD.
WAARSCHUWING
l
Deze UPS bevat een eigen energiebron (accu’s). De UPS-uitgang kan onder spanning staan,
zelfs wanneer de UPS niet is aangesloten op de netspanning.
l
Teneinde de kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw
met temperatuur‐ en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende
verontreinigingen aanwezig zijn. De omgevingstemperatuur mag 40°C niet overschrijden. Niet
gebruiken in de buurt van water of bij zeer hoge vochtigheid (max. 95%).
l
Sluit om brandgevaar te voorkomen de apparatuur uitsluitend aan op een circuit voorzien van
een overstroombeveiliging voor vertakte circuits van maximaal 100 A in overeenstemming met
de National Electrical Code (Nationale Elektriciteitsvoorschriften), ANSI/NFPA 70. Zien pagina 70
of pagina 46.
l
De uitgangsoverstroombeveiliging en de stroomonderbreker moeten door derden worden
geleverd.
l
Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele
apparatuur die op de uitgang van deze UPS is aangesloten, geen aardlekstroom van meer dan
3,5 milliampère hebben.
OPGELET
l
Batterijen leveren gevaar op voor elektrische schokken en kunnen brandwonden veroorzaken
door een grote kortsluitstroom. Neem de juiste voorzorgsmaatregelen in acht. Het onderhoud
moet worden uitgevoerd door bevoegde onderhoudsmonteurs die verstand hebben van accu’s
en op de hoogte zijn van de vereiste voorzorgsmaatregelen. Houd onbevoegden uit de buurt van
de accu’s.
l
De batterijen moeten op de juiste wijze worden opgeruimd. Raadpleeg hiervoor uw plaatselijke
voorschriften.
l
Nooit batterijen in het vuur gooien. De batterijen kunnen ontploffen.
Tarkeita Turvaohjeita
TÄRKEITÄ TURVAOHJEITA - SUOMI — SÄILYTÄ NÄMÄ OHJEET
mä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava UPS-virtalähteen ja akkujen
asennuksen ja huollon yhteydessä. Lue kaikki ohjeet ennen laitteiston käyttöä ja säilytä ohje
myöhempää tarvetta varten.
VAARA
Tämä UPS sisältää HENGENVAARALLISIA JÄNNITTEITÄ. Kaikki korjaukset ja huollot on jätettävä
VAIN VALTUUTETUN HUOLTOHENKILÖN TOIMEKSI. UPS ei sisällä MITÄÄN YTTÄJÄN
HUOLLETTAVIA OSIA.
Safety Warnings
8 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7
VAROITUS
l
Tässä UPS-virtalähteessä on oma energianlähde (akut). UPS-virtalähteen lähdössä voi olla
jännite, vaikka UPS-virtalähdettä ei ole kytketty verkkovirtaan.
l
Vähentääksesi tulipalon ja sähköiskun vaaraa asenna tämä UPS sisätiloihin, joissa lämpötila ja
kosteus on säädettävissä ja joissa ei ole virtaa johtavia epäpuhtauksia. Ympäristön lämpötila ei
saa ylittää 40 °C. Älä käytä lähellä vettä ja vältä kosteita tiloja (95 % maksimi).
l
Pienennä tulipalon vaaraa kytkemällä vain piiriin, jossa on 100 ampeerin maksimihaarapiirin
ylivirtasuoja kansallisen sähkölainsäädännön (ANSI/NFPA 70) mukaan. Hiippakunta hotellipoika
70 eli hotellipoika 46.
l
Muiden on toimitettava lähdön ylivirtasuoja ja irtikytkentäkytkin.
l
Kansainväliset normit ja johdotusmääräykset vaativat, että kaikkien tämän UPS-laitteen
ulostulokytkentöjen yhteinen maavuotovirta ei ylitä 3,5 milliampeeria (mA).
ADVARSEL
l
Akut voivat aiheuttaa sähköiskun tai palovammojen vaaran johtuen suuresta oikosulkuvirrasta.
Noudata kaikkia asianmukaisia varotoimia. Laitteen saa huoltaa vain ammattitaitoinen
huoltohenkilökunta, joka tuntee akut ja niihin liittyvät varotoimet. Älä päästä valtuuttamatonta
henkilöstöä lähelle akkuja.
l
Akusto täytyy hävittää säädösten mukaisella tavalla. Noudata paikallisia määräyksiä.
l
Älä koskaan heitä akkuja tuleen. Ne voivat räjähtää.
Consignes de sécurité
CONSIGNES DE SÉCURITÉ IMPORTANTES — CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute
procédure d’installation et de maintenance des batteries et de l’onduleur. Veuillez consulter
entièrement ces instructions avant de faire fonctionner l’équipement et conserver ce manuel afin
de pouvoir vous y reporter ultérieurement.
DANGER!
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de réparation
doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ. AUCUNE PIÈCE
RÉPARABLE PAR LUTILISATEUR ne se trouve dans l’onduleur.
Safety Warnings
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 9
AVERTISSEMENT!
l
Cette onduleur possède sa propre source d’alimentation (batteries). Il est possible que la sortie
de l’onduleur soit sous tension même lorsque l’onduleur nest pas connectée à une
alimentation CA.
l
Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur uniquement à
l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la température et l’humidité
ambiantes sont contrôlées. La température ambiante ne doit pas dépasser 40 °C. Ne pas utiliser
à proximité d’eau ou dans une atmosphère excessivement humide (95 % maximum).
l
Afin de réduire les risques d’incendie, ne raccordez qu’à un circuit muni d’une protection de
surintensité du circuit de dérivation maximum de 100 ampères conformément au Code
Électrique National (National Electrical Code) des États-Unis, ANSI/NFPA 70. Voir page 70 ou
page 46.
l
La protection de surintensité de sortie ainsi que le sectionneur doivent être fournis par des tiers.
l
Afin d’être conforme aux normes et règlements internationaux de câblage, le courant de fuite à
la terre de la totalité du matériel branché sur la sortie de l’onduleur ne doit pas dépasser 3,5 mA.
ATTENTION!
l
Les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant d’un
courant de court-circuit haute intensité. Observez les précautions appropriées. L’entretien doit
être réalisé par du personnel qualifié connaissant bien les batteries et les précautions
nécessaires. N’autorisez aucun personnel non qualifié à manipuler les batteries.
l
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en
vigueur dans votre localité.
l
Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire exploser.
Sicherheitswarnungen
WICHTIGE SICHERHEITSANWEISUNGEN — AUFBEWAREN
Dieses Handbuch enthält wichtige Anweisungen, die Sie während der Installation und Wartung
des USV (Unterbrechungsfreies Stromversorgungssystem) und der Batterien befolgen müssen.
Bitte lesen Sie alle Anweisungen des Handbuches bevor sie mit dem Gerät arbeiten. Bewaren Sie
das Handbuch zum Nachlesen auf.
WARNUNG
Die USV führt lebensgefährliche Spannungen. Alle Reparatur- und Wartungsarbeiten sollten nur
von Kundendienstfachleuten durchgeführt werden. Die USV enthält keine vom Benutzer zu
wartenden Komponenten.
Safety Warnings
10 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7
ACHTUNG
l
Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigene
Energiequelle (Batterien). Der USV-Ausgang kann Spannung führen, auch wenn das USV nicht
an eine Wechselstromquelle angeschlossen ist.
l
Um die Brand‐ oder Elektroschockgefahr zu verringern, diese USV nur in Gebäuden mit
kontrollierter Temperatur und Luftfeuchtigkeit installieren, in denen keine leitenden
Schmutzstoffen vorhanden sind. Die Umgebungstemperatur darf 40°C nicht übersteigen. Die
USV nicht in der Nähe von Wasser oder in extrem hoher Luftfeuchtigkeit (max. 95 %) betreiben.
l
Um die Brandgefahr zu verringern, nur an eine Leitung anschließen, die mit einem
Überlaststromschutz von maximal 100 Ampere in Übereinstimmung mit dem National Electrical
Code, ANSI/NFPA 70 ausgestattet ist. Siehe Seite 70 oder Seite 46.
l
Der Ausgangs-Überlaststromschutz und der Trennschalter müssen von anderen Herstellern
geliefert werden.
l
Um internationale Normen und Verdrahtungsvorschriften zu erfüllen, dürfen die an den Ausgang
dieser USV angeschlossenen Geräte zusammen einen Erdableitstrom von insgesamt
3,5 Milliampere nicht überschreiten.
VORSICHT!
l
Batterien können das Risiko eines elektrischen Schlags bergen oder durch hohen
Kurzschlussstrom in Brand geraten. Die richtigen Vorsichtsmaßnahmen beachten. Die Wartung
muss von qualifiziertem Wartungspersonal durchgeführt werden, das im Umgang mit Batterien
geübt ist und über gute Kenntnisse der erforderlichen Vorsichtsmaßnahmen verfügt. Nicht
autorisiertes Personal von Batterien fern halten.
l
Die Batterien müssen ordnungsgemäß entsorgt werden. Hierbei sind die örtlichen
Bestimmungen zu beachten.
l
Batterien niemals verbrennen, da sie explodieren können.
Avvisi di sicurezza
IMPORTANTI ISTRUZIONI DI SICUREZZA — CONSERVARE QUESTE ISTRUZIONI
Il presente manuale contiene importanti istruzioni da seguire durante l’installazione e la
manutenzione dell’UPS e delle batterie. Leggere integralmente le istruzioni prima di utilizzare
l’apparecchiatura e conservare il presente manuale per futuro riferimento.
PERICOLO
La TENSIONE contenuta in questo gruppo statico di continuità è LETALE. Tutte le operazioni di
riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE
TECNICO AUTORIZZATO. All’interno del gruppo statico di continuità NON vi sono PARTI
RIPARABILI DALL’UTENTE.
Safety Warnings
Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 11
AVVERTENZA
l
L’UPS contiene la propria fonte di energia (batterie). Le prese d’uscita dell’UPS possono essere
sotto tensione anche quando l’UPS non è collegato all’alimentazione elettrica CA.
l
Per ridurre il rischio di incendio o di scossa elettrica, installare il gruppo statico di continuità in un
ambiente interno a temperatura ed umidità controllata, privo di agenti contaminanti conduttivi.
La temperatura ambiente non deve superare i 40°C. Non utilizzare l’unità in prossimità di acqua
o in presenza di umidità eccessiva (95% max).
l
Per ridurre il rischio di incendio, effettuare il collegamento soltanto a un circuito dotato di una
protezione da sovraccarico per il circuito derivato di max. 100 ampere come stabilito dalle norme
statunitensi sugli impianti elettrici (National Electrical Code, ANSI/NFPA 70). Vedere pagina 70 o
pagina 46.
l
La protezione da sovraccarico per le uscite e l’interruttore di scollegamento devono essere
forniti da altri produttori.
l
Per conformità con gli standard internazionali e con le norme in merito al cablaggio, tutta
l’apparecchiatura collegata con l’uscita del gruppo statico di continuità non deve avere una
corrente di dispersione di terra superiore a 3,5 milliampere.
ATTENZIONE
l
Le batterie possono comportare un rischio di scossa elettrica o di ustione in seguito a un’elevata
corrente di corto circuito. Osservare le dovute precauzioni. L’assistenza deve essere eseguita da
personale qualificato esperto di batterie e delle necessarie precauzioni. Tenere il personale non
autorizzato lontano dalle batterie.
l
Le batterie devono essere smaltite in modo corretto. Per i requisiti di smaltimento fare
riferimento alle disposizioni locali.
l
Non gettare mai le batterie nel fuoco poichè potrebbero esplodere se esposte alle fiamme.
Viktig Sikkerhetsinformasion
VIKTIGE SIKKERHETSINSTRUKSJONER — GJEM DISSE INSTRUKSJONENE
Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og
vedlikehold av UPS-enheten og batteriene. Les alle instruksjoner før utstyret tas i bruk, og gjem
håndboken til fremtidig referanse.
FARLIG
Denne UPS’en inneholder LIVSFARLIGE SPENNINGER. All reparasjon og service må kun utføres
av AUTORISERT SERVICEPERSONALE. BRUKERE KAN IKKE UTFØRE SERVICE PÅ NOEN
AV DELENE i UPS’en.
Safety Warnings
12 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7
FARLIG
l
UPS-enheten inneholder sin egen energikilde (batterier). UPS-utgangen kan være strømførende
selv når UPS-enheten ikke er koblet til et strømuttak.
l
For å redusere fare for brann eller elektriske støt, bør denne UPS’en installeres i et innendørs
miljø med kontrollert temperatur og luftfuktighet som er fritt for ledende, forurensende stoffer.
Romtemperaturen må ikke overskride 40°C. Den må ikke brukes i nærheten av vann eller ved
meget høy luftfuktighet (95% maks.).
l
For å redusere brannfaren skal det bare kobles til et kretsløp med 100 A maksimum
linjeforgrenings overbelastningsbeskyttelse i henhold til National Electrical Code, ANSI/
NFPA 70. Se side 70 eller side 46.
l
Overbelastningsbeskyttelse for strømutgang og bryterkontakt skal leveres av andre.
l
Alt utstyr som er forbundet med utgangen av denne UPS’en må ikke ha en sterkere total
lekkasjestrøm enn 3,5 milliampere for å være i overensstemmelse med internasjonale
standarder og forkablingsbestemmelser.
FORSIKTIG
l
Batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. høy kortsluttingsstrøm. Treff
passende forholdsregler. Service bør utføres av kvalifisert servicepersonale med kjennskap til
batterier og nødvendige forholdsregler. Hold uautorisert personale borte fra batteriene.
l
Batterier må fjernes på korrekt måte. Se lokale forskrifter vedrørende krav om fjerning av
batterier.
l
Kast aldri batterier i flammer, da de kan eksplodere, hvis de utsettes for åpen ild.
Regulamentos de Segurança
INSTRUÇÕES DE SEGURANÇA IMPORTANTES — GUARDE ESTAS INSTRUÇÕES
Este manual contém instruções importantes que devem ser seguidas durante a instalação e
manutenção do no-break e das baterias. Leia todas as instruções antes de operar o equipamento e
guarde este manual para consultá-lo futuramente.
PERIGO
A UPS contém VOLTAGEM MORTAL. Todos os reparos e assistência técnica devem ser
executados SOMENTE POR PESSOAL DA ASSISTÊNCIA TÉCNICA AUTORIZADO. Não há
nenhuma PEÇA QUE POSSA SER REPARADA PELO USUÁRIO dentro da UPS.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139

Eaton BladeUPS none Manuale utente

Categoria
Gruppi di continuità (UPS)
Tipo
Manuale utente

in altre lingue