EM270 “Energy Analyzer”
1.2.3...
...3.2.1
OK
a
b
c
fig.3
fig.2
4
1
2
3
ENGLISH
1
press the key, to scroll the menus or increase/decrease the values to be set up.
2
you can enter the submenus and change the value change mode from
positive to negative or vice versa according to the logic indicated in g. 3.
3
the LED ashes proportionally to the active energy consumption.
4
turn the trimmer clockwise up to its run end to block programming
mode.
A= year of production plus rmware release; B= kWh per pulse
(relevant to the front led); C= type of system (6.1P); D= order of tcd
phases selected; E= VT rating value; F and G= Digital pulse output 1
and 2 (kWh x pulse); H= primary value of TCD; I= serial communication
address; L= reset the max demand values; M= kWh 765432.1 kW
10.1; N= system kW dmd 221; O= maximum demand 261 kW; P=
AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65.0V;
R= VL12 390V, VL23 390V, VL31 390V.
BASIC PROGRAMMING AND RESET: to enter the
complete programming mode, press the key 2 for at least 3 sec. (g
1). Entering the programming mode, all the measurements and control
functions are inhibited. During this phase the ashing of the LED has not
to be considered.
01
PASS?: entering the right password (default value is 0) allows
accessing the main menu.
02
CnG PASS: it allows changing the
password.
03
SYS: 1.3P, 3-phase (3 or 4 wires) management of one
3-phase load; 2.3P, 3-phase (3 or 4 wires) management of two 3-phase
loads; 3.1P, 1-phase (4 wires) management of three 1-phase loads;
6.1P, 1-phase (4 wires) management of six 1-phase loads.
04
SUM:
sum function of TCD.
05
EC: function Easy Connection.
06
07
tCd
A1(A2): TCD phase order (123 or 321).
08
P.int ti: integration time for
“dmd” power calculation.
09
Ut rAt.: VT ratio.
10
PuL 1: it selects
the pulse weight (number of kWh per pulse, from 0.01 to 9.99) Load 1.
11
PuL 2: it selects the pulse weight (number of kWh per pulse, from
0.01 to 9.99) Load 2.
12
t.on: T ON time (pulse duration (40msec or
100msec).
13
AddrESS: serial address: from 1 to 247.
14
bAud:
Modbus baud rate.
15
PAritY: Modbus parity.
16
EnEPA.rE: reset
of the Load 1 and Load 2 energy values.
17
EnEto.rE: reset of the
total energies.
18
End: it allows exiting the programming mode.
ITALIANO
1
premere il tasto per scorrere i menu o incrementare o decrementare i
valori da impostare.
2
è possibile entrare nei sub menù e modicare
i valori cambiando da positivo a negativo come esemplicato in g. 3.
3
il LED lampeggia proporzionalmente all’energia attiva consumata.
4
per bloccare l’accesso alla programmazione, ruotare il trimmer in
senso orario no a ne corsa.
A= anno di produzione più revisione rmware; B= kWh per impulso (led
frontale); C= tipo di sistema (6.1P); D= ordine delle fasi nei TCD; E=
Rapporto di trasformazione TV; F e G= uscita impulsiva 1 e 2 (kWh per
impulso); H= valore del primario del TCD; I= indirizzo di comunicazione
seriale; L= reset dei valori DMD massimi; M= kWh 765432,1 kW 10,1;
N= 221 kW dmd di sistema; O= valore DMD massimo 261 kW; P=
AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65,0V;
R= VL12 390V, VL23 390V, VL31 390V.
PROGRAMMAZIONE BASE E RESET: per accedere alla
programmazione completa premere il tasto 2 e mantenerlo premuto per
almeno 3 secondi (g. 1). Entrati nel modo di programmazione tutte le
misure e funzioni di controllo sono inibiti. In questa fase il lampeggio del
LED non deve essere considerato.
01
PASS?: inserendo la password corretta (di default è 0) si
accede al menù principale.
02
CnG PASS: permette di modicare
la password.
03
SYS: 1.3P, 3 fasi (3 o 4 li) gestione di un carico
trifase; 2.3P, 3 fasi (3 o 4 li) gestione di due carichi trifase; 3.1P, 1 fase
(4 li) gestione di tre carichi monofase; 6.1P, 1 fase (4 li) gestione di
sei carichi monofase.
04
SUM: funzione somma dei TCD.
05
EC:
funzione Easy Connection.
06
07
tCd A1(A2): ordine delle fasi dei
TCD (123 o 321).
08
P.int ti: tempo di integrazione per il calcolo
della potenza “dmd”.
09
Ut rAt.: rapporto TV.
10
PuL 1: seleziona
il peso dell’impulso del carico 1 (numero di kWh per impulso, da 0,01 a
9,99).
11
PuL 2: seleziona il peso dell’impulso del carico 2 (numero di
kWh per impulso, da 0,01 a 9,99).
12
t.on: Lunghezza impulso T ON
(40msec o 100msec).
13
AddrESS: indirizzo porta seriale: da 1 a
247.
14
bAud: baud rate Modbus.
15
PAritY: parità Modbus.
16
EnEPA.rE: ripristino dei valori dell’energia del Carico 1 e del Carico 2.
17
EnEto.rE: reset delle energie totali.
18
End: permette di uscire
dal menu di programmazione.
DEUTSCH
1
Die Taste drücken, um das Menü durchzublättern oder die
einzugebenden Werte zu erhöhen bzw. zu verringern.
2
Es besteht
die Möglichkeit, die Submenüs aufzurufen und die Werte von
positiv auf negativ zu ändern, wie als Beispiel in Abb. 3 dargestellt.
3
Die LED blinkt proportional zur verbrauchten aktiven Energie.
4
Zum Sperren des Zugriffs auf die Programmierung, den Trimmer bis
zum Anschlag im Uhrzeitersinn drehen.
A= Produktionsjahr plus Firmware-Release; B= kWh pro Impuls
(relevant für die Front-LED); C= System-Typ (6.1P); D= Reihenfolge
der Phasen der TCD; E= Wandlungsverhältnis TV; F und G=
digitaler Pulsausgang 1 und 2 (kWh x Puls); H= Primärstromwert
des TCD; I= Serielle Kommunikationsadresse; L= Reset der
maximalen Demand-Werte; M= kWh 765432,1 kW 10,1; N= 221 kW
dmd des Systems; O= Maximaler Demand-Wert 261 kW; P= AL1
130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65,0V;
R= VL12 390V, VL23 390V, VL31 390V.
BASIS-PROGRAMMIERUNG UND RESET: Zum Aufruf
der kompletten Programmierung die Taste 2 betätigen und mindestens
3 Sekunden gedrückt halten (Abb.1). Nach Aufruf der Programmierung
sind alle Messungen und Kontrollfunktionen gesperrt. In dieser Phase
muss das Blinken von LED nicht berücksichtigt werden.
01
PASS?: Bei Eingabe des korrekten Password (Default-Wert ist
0) wird das Hauptmenü aufgerufen.
02
CnG PASS: Gestattet die
Änderung des Passwords.
03
SYS: 1.3P, 3 Phasen (3 oder 4 Litzen)
für eine Drehstromlast; 2.3P, 3 Phasen (3 oder 4 Litzen) für zwei
Drehstromlasten; 3.1P, 1 Phase (4 Litzen) für drei Einphasenlasten;
6.1P, 1 Phase (4 Litzen) für sechs Einphasenlasten.
04
SUM:
Summen-Funktion der TCD.
05
EC: Funktion Easy Connection.
06
07
tCd A1(A2): Reihenfolge der Phasen der TCD (123 oder 321).
08
P.int ti: Integrationszeit zur Berechnung der Leistung “dmd”.
09
Ut rAt.: Verhältnis TV.
10
PuL 1: Selektiert das Gewichts des
Impulses der Last 1 (Anzahl kWh für Impulse, von 0,01 bis 9,99).
11
PuL 2: Selektiert das Gewichts des Impulses der Last 2 (Anzahl kWh
für Impulse, von 0,01 bis 9,99).
12
t.on: Zeit T ON (Impulsdauer (40
msec oder 100 msec).
13
AddrESS: Adresse des seriellen Ports:
zwischen 1 und 247.
14
bAud: Modbus- Baudrate.
15
PAritY:
Parität Modbus.
16
EnEPA.rE: Zurücksetzung der Last 1- und Last
2-Energiewerte.
17
EnEto.rE: Reset Gesamt-Energie.
18
End:
Gestattet das Verlassen des Programmierungs-Menüs.
FRANÇAIS
1
presser la touche pour déler les menus ou augmenter ou diminuer les
valeurs à régler.
2
il est possible d’entrer dans les sous-menus et modier
les valeurs en changeant de positif à négatif comme illustré à la g. 3.
3
la DEL clignote proportionnellement à l’énergie active consommée
4
pour bloquer l’accès à la programmation, tourner le trimmer dans le
sens des aiguilles d’une montre jusqu’en butée.
A= année de production plus version rmware; B= kWh par impulsion
(led frontale); C= type de système (6.1P); D= ordre des phases dans
les TCD; E= Rapport de transformation TT; F et G= Sortie d’impulsion
logique 1 et 2 (kWh par impulsion); H= valeur du primaire du TCD;
I= adresse de communication série; L= réinitialisation des valeurs
«demand» maximales; M= kWh 765432,1 kW 10.1; N= 221 kW
dmd de système; O= valeur «demand» maximale 261 kW; P= AL1
130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65,0V;
R= VL12 390V, VL23 390V, VL31 390V.
PROGRAMMATION DE BASE ET REINITIALISATION:
pour accéder à la programmation complète presser la touche 2 et la
maintenir enfoncée pendant au moins 3 secondes (g. 1). Une fois dans
le mode de programmation toutes les mesures et fonctions de contrôle
sont bloquées. Durant cette phase le clignotement de la DEL ne doit pas
être pris en considération.
01
PASS?: en saisissant le mot de passe correct (par défaut 0) on
accède au menu principal.
02
CnG PASS: permet de modier le
mot de passe.
03
SYS: 1.3P, 3 phases (3 ou 4 ls) gestion d’une
charge triphasée; 2.3P, 3 phases (3 ou 4 ls) gestion de deux charges
triphasées; 3.1P, 1 phase (4 ls) gestion de trois charges monophasées;
6.1P, 1 phase (4 ls) gestion de six charges monophasées.
04
SUM:
fonction somme des TCD.
05
EC: fonction Easy Connection.
06
07
tCd A1(A2): ordre des phases des TCD (123 ou 321).
08
P.int
ti: temps d’intégration pour le calcul de la puissance “dmd”.
09
Ut
rAt.: rapport TT.
10
PuL 1: sélectionne le poids de l’impulsion de
la charge 1 (nombre de kWh par impulsion, de 0,01 à 9,99).
11
PuL
2: sélectionne le poids de l’impulsion de la charge 2 (nombre de kWh
par impulsion, de 0,01 à 9,99).
12
t.on: T ON time (durée d’impulsion
(40msec ou 100msec).
13
AddrESS: adresse port série: de 1 à 247.
14
bAud: débit en bauds Modbus.
15
PAritY: parité Modbus.
16
EnEPA.rE: réinitialisation des valeurs d’énergie de la Charge 1 et de
la Charge 2.
17
EnEto.rE: réinitialisation des énergies totales.
18
End: permet de quitter le menu de programmation.
ESPAÑOL
1
pulsar la tecla para avanzar por los menús y para
aumentar o reducir los valores a congurar.
2
es posible
entrar en los submenús y modicar los valores cambiando de
positivo a negativo o viceversa, como se indica en la g. 3.
3
el LED parpadea proporcionalmente a la energía activa consumida.
4
para bloquear el acceso a la programación, girar el potenciómetro
en sentido horario hasta el tope.
A= año de producción más la versión de rmware; B= kWh por pulso
(correspondiente al LED delantero); C= tipo de sistema (6.1P); D=
orden de las fases en los TCD; E= Relación de transformación de VT; F
y G= Salida 1 y 2 de pulso digital (kWh x pulso); H= valor del primario
del TCD; I= dirección de comunicación en serie; L= puesta a cero de los
valores máximos de demanda; M= kWh 765432,1 kW 10,1; N= 221 kW
dmd de sistema; O= valor máximo de demanda 261 kW; P= AL1 130A,
AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65,0V; R= VL12
390V, VL23 390V, VL31 390V.
PROGRAMACIÓN BÁSICA Y PUESTA A CERO: para
acceder a la programación completa, pulsar la tecla 2 y mantenerla
pulsada durante al menos 3 segundos (g. 1). Una vez dentro del modo
de programación, se inhiben todas las medidas y funciones de control.
En esta fase no debe tenerse en cuenta el parpadeo del LED.
01
PASS?: introduciendo la contraseña correcta (por defecto es 0)
se accede al menú principal.
02
CnG PASS: permite modicar la
contraseña.
03
SYS: 1.3P, 3 fases (3 o 4 hilos) gestión de una carga
trifásica; 2.3P, 3 fases (3 o 4 hilos) gestión de dos cargas trifásicas; 3.1P,
1 fase (4 hilos) gestión de tres cargas monofásicas; 6.1P, 1 fase (4 hilos)
gestión de seis cargas monofásicas.
04
SUM: función suma de los
TCD.
05
EC: función Easy Connection.
06
07
tCd A1(A2): orden
de las fases de los TCD (123 o 321).
08
P.int ti: tiempo de integración
para calcular la potencia “dmd”.
09
Ut rAt.: relación de VT.
10
PuL
1: selecciona el valor del pulso 1 (número de kWh por pulsos, de 0,01
a 9,99).
11
PuL 2: selecciona el valor del pulso 2 (número de kWh
por pulsos, de 0,01 a 9,99).
12
t.on: tiempo ON (duración del pulso
(40 msec o 100 msec).
13
AddrESS: dirección puerto serie: de 1 a
247.
14
bAud: velocidad en baudios, Modbus.
15
PAritY: paridad
Modbus.
16
EnEPA.rE: restablecimiento de los valores de energía
Carga 1 y Carga 2.
17
EnEto.rE: puesta a cero de energías totales.
18
End: permite salir del menú de programación.
DANSK
1
Tryk på tasten for at rulle ned igennem menuerne eller forøge og
formindske de værdier, der skal indstilles.
2
Man kan gå ind i undermenuerne
og ændre værdierne ved at skifte fra positiv til negativ som vist i g. 3.
3
Lysdioden lyser i forhold til den forbrugte aktive energi.
4
Drej på
trimmeren i urets retning, indtil den ikke kan komme længere, for at
spærre for adgang til programmering.
A= produktionsår og udgivelse af rmware; B= kWh pr. impuls (relevant
for forreste LED); C= systemets type (6.1P); D= faserækkefølge i TCD;
E= omdannelsesforhold for TV; F og G= digital pulsudgang 1 og 2 (kWh
x puls); H= primær værdi af TCD; I= seriekommunikationsadresse; L=
reset af værdier med maksimale krav; M= kWh 765432,1 kW 10,1; N=
221 kW dmd af systemet; O= værdi med maksimalt krav 261 kW; P=
AL1 130A, AL2 130A, AL3 130A; Q= VL1 230V, VL2 89,0V, VL3 65,0V;
R= VL12 390V, VL23 390V, VL31 390V.
GRUNDLÆGGENDE PROGRAMMERING OG RESET:
For at få adgang til den fulde programmering skal man trykke på
tast 2 og holde den inde i mindst 3 sekunder (g. 1). Når man er i
programmeringsmode, er alle målinger og kontrolfunktioner blokerede. I
denne fase lyser LED’en, men det skal man ikke tage hensyn til.
01.
PASS?: Ved at indsætte den korrekte adgangskode (standard
er 0) får man adgang til hovedmenuen.
02.
CnG PASS: Tillader en
ændring af adgangskoden.
03.
SYS: 1.3P, 3 faser (3 eller 4 ledninger)
styring af trefaset belastning; 2.3P, 3 faser (3 eller 4 ledninger) styring
af to trefasede belastninger; 3.1P, 1 fase (4 ledninger) styring af tre
enfasede belastninger; 6.1P, 1 fase (4 ledninger) styring af seks
enfasede belastninger.
04.
SUM: Funktionen Sum af TCD.
05.
EC:
Funktionen Easy Connection.
06.
07.
tCd A1(A2): Faserækkefølge
af TCD (123 eller 321).
08.
P.int ti: Integration tid for beregning af
effekten “dmd”.
09.
Ut rAt.: TV-forhold.
10.
PuL 1: Vælger vægten
af impulsen for belastning 1 (antal kWh for impulser, fra 0,01 til 9,99).
11.
PuL 2: Vælger vægten af impulsen for belastning 2 (antal kWh for
impulser, fra 0,01 til 9,99).
12.
t.on: T ON time (pulsvarighed (40msec
eller 100msec).
13.
AddrESS: Adressen på den serielle port: fra
1-247.
14.
bAud: Baudhastighed på Modbus.
15.
PAritY: Modbus-
paritet.
16.
EnEPA.rE: Nulstilling af energiværdier for belastning 1 og
2.
17.
EnEto.rE: Reset af totale energier.
18.
End: Tillader, at man
går ud af programmeringsmenuen.
A
B
C
D
E
H
I
L
M
N
O
P
Q
R
RESET!
fig.1
F
G
CARLO GAVAZZI
Automation Components
Carlo Gavazzi Controls SpA,
Via Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 355811,
Fax +39 0437 355880
EM270 72D IM TS ML 8021426 210715
EM270 “Energy Analyzer”
ENGLISH
SAFETY PRECAUTIONS
Read carefully the instruction manual. If the
instrument is used in a manner not specied by
the producer, the protection provided by the
instrument may be impaired. Maintenance:
make sure that the connections are correctly carried out
in order to avoid any malfunctioning or damage to the
instrument. To keep the instrument clean, use a slightly
damp cloth; do not use any abrasives or solvents. We
recommend to disconnect the instrument before cleaning
it.
TECHNICAL SPECIFICATIONS
Rated Input. Current type Galvanic insulation carried
out by means of external TCD current transformer
accessories. Current range: Trough TCD current
transformers (Up to 630 A). Voltage range: 240VLN and
415VLL (MV5), 133VLN and 230VLL (MV6). Accuracy:
The data considers the whole measuring chain: EM270
base meter and TCD current transformer (Display, serial
communication). Current range: In: 160A, 250A, 630A
(TCD primary current). Voltage range: MV5 range Un: 160
to 260VLN (277 to 450VLL). MV6 range Un: 40 to 144VLN
(70 to 250VLL). Phase-neutral voltage, In the range Un:
±(0,5% RDG +1DGT). Phase-phase voltage, In the range
Un: ±(1% RDG +1DGT). Active power, from 0.2In to Imax,
within Un range, PF=1: ±(1.25% RDG +1DGT). Energies:
(considering the whole measurement chain) kWh:
better than the combination of a class 1 of EN62053-
21 meter (EM270 base) and class 0.5 of EN60044-1
CTs. Start up current: 0.002In. Display: instantaneous
variables readout: 3-DGT. Imported Energies Partials
and Total: 6+1 or 7 DGT. Overload status: indication
EEE. Red LED (Energy consumption only, 1 imp./kWh).
Green LED for Power-on (steady) and communication
status: RX-TX (in case of RS485 option only), blinking.
Voltage Overloads: Continuous 1.2*Un. For 500ms
2*Un (except power supply terminals). Voltage input
impedance: Self-power supply, power consumption:
< 4VA / 2W. Pulse output: Number of outputs: 2,
Programmable from 1.0 to 9.99 kWh per pulse. Type
Output connectable to the energy meters (kWh). Output,
V
ON
2.5 VAC/DC/ max. 70 mA. Load V
OFF
40 VAC/DC
max. Insulation 4kVp/2,5kVAC output to measuring
inputs. RS485: Connections 2-wire max. distance
1000m. Protocol, MODBUS/JBUS (RTU). Driver input
capability 1/5 unit load. Maximum 160 transceivers on
the same bus. Insulation, by means of opto-couplers,
4kVp/2,5kVAC output to measuring input. Transformer
ratio: VT (PT) ratio 1.0 to 99.9 / 100 to 999. CT primary
current Auto-detection of the primary current of the TCD
current transformer. The 2 TCD’s shall have the same
primary current. The maximum value of the VT is limited to
grant the measurement of the max possible power (210MW).
Max VT (PT) ratio: MV5 model. Primary current 160 A:
VT max 620. Primary current 250 A: VT max 410. Primary
current 630 A: VT max 150. MV6 model. Primary current
160 A : VT max 999. Primary current 250 A: VT max 720.
Primary current 630 A: VT max 270. Reset: By means of
the front keypad: • total energies: kWh (if function SUM on)
• partial energies (single load) : kWh and demanded power:
Wdmd • Max demand (Md) of active and apparent power.
Operating temperature: -25 to +55°C (-13°F to +131°F)
(R.H. from 0 to 90% non-condensing @ 40°C) according
to EN62052-11. Storage temperature: -30 to +70°C
(-22°F to +158°F) (R.H. < 90% non-condensing @ 40°C) )
according to EN62052-11). Overvoltage category: Cat.
III (IEC 60664, EN60664). Dielectric strength: 4000VAC
RMS for 1 minute (all terminals to front panel). Standard
compliance: Safety IEC60664, EN60664, IEC61010-
1, EN61010-1 EN62052-11, EN50470-1. Pulse output
DIN43864, IEC62053-31. Approvals: CE. Connections:
(input and output terminals) Max wire cross section 1.5
mm² (14 AWG). Min./max. screws tightening torque:
0.2/0.25 Nm. Housing: Dimensions (WxHxD) 72 x 72
x 65 mm. Material Noryl, self-extinguishing: UL 94 V-0.
Mounting DIN-rail or Panel mounting. Protection degree:
Front IP50. Screw terminals IP20. Self power supply
90 to 460VAC (45-65Hz) (VL2-L3). Power consumption:
4VA.
ITALIANO
NORME DI SICUREZZA
Leggere attentamente il manuale istruzioni.
Qualora l’apparecchio venisse adoperato in un
modo non specicato dal costruttore, la
protezione prevista dall’apparecchio potrebbe
essere compromessa. Manutenzione: assicurarsi che i
collegamenti siano effettuati correttamente al ne di
evitare qualsiasi malfunzionamento o danneggiamento
dello strumento. Per mantenere pulito lo strumento usare
un panno leggermente inumidito; non usare abrasivi o
solventi. Si consiglia di scollegare lo strumento prima di
pulirlo.
CARATTERISTICHE TECNICHE
Ingressi di misura: Tipo corrente: Isolamento galvanico
ottenuto mediante i trasformatori di corrente TCD
accessori. Portata corrente: Tramite trasformatori di
corrente TCD (fino a 630 A). Range tensione: 240VLN
e 415VLL (MV5), 133VLN e 230VLL (MV6). Precisione:
i dati sotto considerano la misura dell’intera catena:
contatore EM270 base e trasformatori di corrente TCD.
Portata corrente: In: 160A, 250A, 630A (TCD corrente
primaria). Portata tensione: MV5 Un: da 160 a 260VLN
(da 277 a 450VLL). Range MV6 Un: da 40 a 144VLN
(da 70 a 250VLL). Tensione fase neutro: nel campo Un:
±(0,5% RDG +1DGT). Tensione fase fase: nel campo
Un: ±(1% RDG +1DGT). Potenza attiva: da 0,2In a Imax,
del campo Un, PF=1: ±(1,25% RDG +1DGT). Energie:
(considerando l’intera catena di misurazione) kWh:
migliore della combinazione di un misuratore di classe 1
EN62053-21 (base EM270) e di trasformatori di corrente
EN60044-1 di classe 0,5. Corrente di spunti: 0,002In.
Display: Lettura variabili istantanee: 3-DGT. Parziali e
totale: 6+1 o 7 DGT. Stato di sovraccarico: indicazione
EEE. LED rosso (Solo consumo di energia), 1 imp./kWh.
LED verde relativo allo stato di “strumento acceso”, se a
luce fissa, a luce lampeggiante in caso di comunicazione
RS485 presente e operativa. Sovraccarico corrente:
Continuo: 1,2*Un. Per 500ms: 2*Un (eccetto le
connessioni di alimentazione). Impedenza d’ingresso
tensione: Autoalimentazione, autoconsumo:
< 4VA / 2W. Uscite impulsi: Numero di uscite: 2,
programmabili da 1,0 a 9,99 kWh per impulso. Tipo:
Uscita associabile al contatore di energia (kWh). Uscita
statica: opto-mosfe. Carico V
ON
2,5VCA/CC/ max.70mA
V
OFF
40VCA/CC max. Isolamento 4kVp/2,5kVAC fra
uscita e ingressi di misura. RS485: Connessione:
2- fili max. distanza 1000m. Protocollo: MODBUS/
JBUS (RTU). Dispositivi in rete 1/5 unit load. Massimo
160 dispositivi nella stessa rete. Isolamento tramite
optoisolatori, 4kVp/2,5kVAC tra uscite e ingressi di
misura. Rapporto di trasformazione: Rapporto TV (PT):
da 1,0 a 99,9 / da 100 a 999. Corrente primaria CT: Auto
determinazione della corrente primaria dei trasformatori di
corrente TCD. I 2 TCD devono avere lo stesso primario di
corrente. Il valore massimo del TV è limitato per garantire
la misura della massima potenza possibile (210MW). Max
rapporto TV (PT): Modello MV5: Corrente primaria 160 A:
TV max 620. Corrente primaria 250 A: TV max 410. Corrente
primaria 630 A: VT max 150. Modello MV6: Corrente primaria
160 A: VT max 999. Corrente primaria 250 A: VT max 720.
Corrente primaria 630 A: VT max 270. Reset: Mediante la
tastiera frontale: • energie totali: kWh (se la funzione SUM è
attivata) • energie parziali (carico singolo) : kWh e potenza
richiesta: Wdmd • Max dmd (Md) della potenza attiva e
apparente. Temperatura di funzionamento: da -25°C
a +55°C (da -13°F a 131°F) (U.R. da 0 a 90% senza
condensa @ 4C) secondo EN62052-11. Temperatura
di immagazzinamento: da -30°C a +70°C (da -22°F a
158°F) (U.R. < 90% senza condensa @ 40°C) secondo
EN62052-11. Categoria d’installazione: Cat. III (IEC
60664, EN60664). Conformità alle norme: Sicurezza:
IEC60664, EN60664, IEC61010-1, EN61010-1 EN62052-
11, EN50470-1. Emissioni in radiofrequenza: DIN43864,
IEC62053-31. Approvazioni: CE. Connessioni: (terminali
di ingresso e di uscita) Massima sezione trasversale filo
1,5 mm² (14 AWG). Coppia di serraggio viti massima/
minima: 0,2/0,25 Nm. Custodia: Dimensioni (WxHxD):
72 x 72 x 65 mm. Materiale: Noryl, autoestinguenza:
UL 94 V-0. Montaggio: guida DIN o Pannello. Grado di
protezione: Frontale: IP50. Connessioni: IP20. Versione
autoalimentata: da 40V a 460VAC LL, da 45 a 65Hz, tra
L2 e L3. Autoconsumo: 4VA.
DEUTSCH
SICHERHEITSBESTIMMUNGEN
Die Betriebsanleitung aufmerksam lesen. Sollte
das Gerät nicht gemäss der Herstellerangaben
verwendet werden, könnte der vom Gerät
vorgesehene Schutz beeinträchtigt werden.
Wartung: Beachten Sie den korrekten Anschluss aller
Anschlussterminals um eine Beschädigung des
Instrumentes zu vermeiden. Das Gerät mit einem
feuchten Tuch reinigen; keine Scheuer- oder Lösemittel
verwenden. Das Gerät vor der Reinigung ausschalten.
TECHNISCHE DATEN
Messeingang: Stromtyp: Galvanische Isolierung durch
externes TCD-Stromwandler-Zubehör. Strombereich:
TCD-Durchlassstrom-Transformatoren (bis 630 A).
Spannungsbereich: 240VLN und 415VLL (MV5),
133VLN und 230VLL (MV6). Genauigkeit: die unten
aufgeführten Daten berücksichtigen die gesamte
Messkette: EM270-Basiszähler und TCD-Stromwandler.
Strombereich: 160A, 250A, 630A (TCD-Primärstrom).
Spannungsbereich: MV5 Bereich Un: 160 bis 260VLN
(277 bis 450VLL). MV6 Bereich Un: 40 bis 144VLN (70 bis
250VLL). Phase-Nullleiter im Bereich Un: ±(0,5% RDG
+1DGT). Phase-Phasenspannung im Bereich Un: ±(1%
RDG +1DGT). Wirkstrom Von 0,2In bis lmax, innerhalb
Un-Bereich, PF=1: ±(1,25% RDG +1DGT). Energien:
(unter Berücksichtigung der kompletten Messkette)
kWh: besser als die Kombination aus einem Klasse
1 EN62053-21 Messgerät (EM270-Basis) und Klasse
0,5 EN60044-1 CTs. Startstrom: 0,002In. Anzeige:
Momentanmessgrößen 3-DGT. Teil und Gesamt: 6+1
oder 7 DGT. Überlast-Status: Anzeige EEE. Rote LED
(nur Energieverbrauch), 1 imp./kWh. Grüne LED für
Einschaltung (stetig) und Kommunikationsstatus:
RX-TX (nur im Falle der RS485-Option), blinkend.
Überlastspannung: kontinuierlich: 1,2*Un. Für 500ms:
2*Un (außer versorgungsklemmen). Spannungs-
Eingangsimpedanz: Eigenstromversorgung:
Energieverbrauch:< 4VA / 2W. Pulsausgang: Anzahl der
Ausgänge: 2, programmierbar von von 1,0 bis 9,99 kWh
pro Impuls. Typ: Ausgang verbindbar mit Stromzählern
(kWh). Ausgang: V
ON
2,5 VAC/DC/ max. 70 mA. Last: V
OFF
40 VAC/DC max. Isolierung: 4kVp/2,5kVAC Ausgang zur
Messung von Eingängen. RS485: Anschlüsse: 2-adrig.
max. Abstand 1000m. Protokoll: MODBUS/JBUS (RTU).
Besondere Funktionen: 1/5 Einheitsladung. Maximal 160
Sender-Empfänger am selben Bus. Isolierung: Durch
Optokoppler, 4kVp/2,5kVAC Ausgang zu Messeingang.
Wandler-Verhältnis: VT (PT)-Verhältnis: 1,0 bis 99,9 /
100 bis 999. CT-Primärstrom: Automatische Erkennung
des Primärstroms des TCD-Stromwandlers. Die 2 TCDs
müssen denselben Primärstrom haben. Der Maximalwert
des VT ist darauf beschränkt, die Messung der maximal
möglichen Leistung (210MW) zu gewähren. Max. VT
(PT)-Verhältnis: MV5-Modell: Primärstrom 160 A: VT
max. 620. Primärstrom 250 A: VT max. 410. Primärstrom
630 A: VT max. 150. MV6-Modell: Primärstrom 160
A: VT max. 999. Primärstrom 250 A: VT max. 720.
Primärstrom 630 A: VT max. 270. Zurücksetzen:
Mittels vorderem Tastenfeld: • Gesamtenergien: kWh
(wenn die Funktion SUM eingeschaltet ist) • Teilenergien
(Einzellast): kWh und geforderte Leistung: Wdmd • Max
Anforderung (Md) von Wirk- und Scheinleistung.
Betriebstemperatur: -25 bis +55°C (-13°F bis +131°F)
(R.F. von 0 bis 90% nicht kondensierend @ 40°C) gemäß
EN62052-11. Lagertemperatur: -30 bis +70°C (-22°F
bis +158°F) (RH < 90% ohne Kondensation bei 40°C)
gemäß EN62052-11). Überspannungs-Kategorie:
Kl. III (IEC 60664, EN60664). Standardkonformität
Sicherheit IEC60664, EN60664, IEC61010-1, EN61010-
1 EN62052-11, EN50470-1 Pulsausgang DIN43864,
IEC62053-31. Zulassungen: CE. Verbindungen:
(Eingangs- und Ausgangsanschlüsse) Min./Max.
Schraubenanzugsmoment: 0,2/0,25 Nm. Gehäuse:
Abmessungen (BxHxT): 72 x 72 x 65 mm. Gehäusematerial:
Noryl, selbstlöschend: UL 94 V-0. Montage: DIN-
Schienen- und Panelmontage. Schutzgrad: Front: IP50.
Schraubklemmen: IP20. Modelle mit Eigenversorgung:
Von 40V bis 460VAC LL, 45 bis 65Hz, zwischen L2 und
L3. Leistungsaufnahme: 4VA.
FRANÇAIS
PRÉCAUTIONS DE SECURITE
Lire attentivement le manuel de l’utilisateur. Si
l’appareil est utilisé dans des conditions
différentes de celles spéciées par le fabricant,
le niveau de protection prévu par l’instrument
peut être compromis. Entretien: s’assurer que les
connexions sont réalisées correctement dans le but
d’éviter toutes fautes ou endommagements de l’appareil.
Pour nettoyer l’instrument, utiliser un chiffon humide; ne
pas utiliser d’abrasifs ou de solvants. Il faut déconnecter
le dispositif avant de procéder au nettoyage.
SPÉCIFICATIONS
Entrées nominales: Type de courant: Isolation
galvanique réalisée au moyen d’accessoires du
transf. de courant TCD externe. Plage de courant: Par
transformateurs de courant TCD (Jusqu’à 630 A). Plage
de tension: 240VLN et 415VLL (MV5), 133VLN et 230VLL
(MV6). Précision: Les données ci-dessous prennent en
considération l’entière chaine de mesure: le compteur
EM270 de base et le transformateur de courant TCD.
Plage de courant: In: 160A, 250A, 630A (courant primaire
TCD). Plage de tension: plage MV5 Un: de 160 à 260VLN
(de 277 à 450VLL). Plage MV6 Un: de 40 à 144VLN (de
70 à 250VLL). Tension phase-neutre. Dans la gamme
Un: ±(0,5% RDG +1DGT). Tension phase-phase. Dans
la gamme Un: ±(1% RDG +1DGT). Puissance active:
De 0,2In à Imax, dans la gamme Un, PF=1: ±(1,25%
RDG +1DGT). Énergies: (en considérant toute la chaîne
de mesurage) kWh: plus efficace que la combinaison
de la classe 1 d’un compteur EN62053-21 (EM270 de
base) et que la classe 0,5 des TC EN60044-1. Courant
de démarrage: 0,002In. Affichage: Lecture variables
instantanées: 3-DGT. Energies. Partielles et Totales:
6+1 ou 7 DGT. État de surcharge: indication EEE. LED
rouge (seulement Consommation d’énergie, 1 imp./kWh.
LED verte pour Marche (fixe) et état communication:
RX-TX (seulement en cas d’option RS485), clignotante.
Surcharges de tension: Continu: 1,2*Un. Pour 500 ms:
2*Un (sauf bornes d’alimentation). Impédance d’entrée
tension: Auto-alimentation. Consommation d’Energie:
< 4VA/2W. Sortie à impulsions: Nombre de sorties: 2,
Programmables de 1,0 à 9,99 kWh par impulsion. Type:
sortie raccordable aux compteurs d’énergie (kWh).
Sortie V
ON
2,5 VCA/CC/ max. 70 mA. Charge: V
OFF
40
VCA/CC max. Isolation: 4kVp/2,5kVCA entre sortie et
entrées de mesure. RS485: Connexions: 2 fils, distance
max 1000m. Protocole MODBUS/JBUS. (RTU). Capacité
d’entrée du pilot 1/5 charge d’unité. Maximum 160
émetteurs-récepteurs sur le même bus. Isolation: au
moyen d’optocoupleurs, 4kVp/2,5kVAC entre sortie et
entrée de mesure. Rapport transformateur: Rapport
transf. de tension VT (TP). De 1,0 à 99,9 /de 100 à 999.
Courant primaire TC. Auto-détection du courant primaire
du transformateur de courant TCD. Les 2 TCD devront
avoir le même courant primaire. La valeur maximum
du transformateur de tension est limitée pour garantir
la mesure de la puissance max possible (210MW).
Rapport max transformateur de tension VT (TP):
Modèle MV5. Courant primaire 160A: transf. de tension
max 620. Courant primaire 250A: transf. de tension max
410. Courant primaire 630A: transf. de tension max 150.
Modèle MV6. Courant primaire 160A: transf. de tension
max 999. Courant primaire 250A: transf. de tension max
720. Courant primaire 630A: transf. de tension max
270. Réinitialisation: Au moyen du pavé numérique à
l’avant: • énergies totales: kWh (si fonction SUM activée)
• énergies partielles (charge individuelle): kWh et puissance
demandée: Wdmd • Demande max (Md) de puissance
active et apparente. Température de fonctionnement:
-25 à +55°C (-13°F à +131°F) (H.R. de 0 à 90% sans
condensation @ 40°C) selon EN62052-11. Température
de stockage: -30 à +70°C (-22°F à +158°F) (H.R. <
90% sans condensation @ 40°C) selon EN62052-11.
Catégorie surtension: Cat. III (IEC 60664, EN60664).
Conformité aux normes: Sécurité IEC60664, EN60664,
IEC61010-1, EN61010-1 EN62052-11, EN50470-1. Sortie
à impulsions DIN43864, IEC62053-31. Approbations:
CE. Connexions: (bornes d’entrée et de sortie) Section
max fil 1,5 mm² (14 AWG). Couple de serrage vis min./
max.: 0,2/0,25 Nm. Boîtier: Dimensions (LxHxP) 72 x 72
x 65 mm. Matériel: Noryl, auto-extinguible: UL 94 V-0.
Montage: Rail DIN ou Montage sur panneau. Indice de
protection: Frontal: IP50. Bornes à vis: IP20. Version
auto-alimentée: De 40V à 460VAC LL, de 45 à 65Hz,
entre L2 et L3. Consommation d’énergie: 4VA.
ESPAÑOL
NORMAS DE SEGURIDAD
Lea el manual y siga atentamente las
instrucciones. Si se utiliza el equipo de manera
distinta de como indica el Fabricante, se puede
dañar la protección de la que está provisto el
instrumento. Mantenimiento: asegurarse de que las
conexiones son correctas para evitar un mal
funcionamiento o daños en el instrumento. Para tener el
instrumento limpio, limpiar periódicamente la carcasa
con un trapo un poco humedecido. No utilizar productos
abrasivos o disolventes. Desconectar el equipo antes de
limpiarlo.
ESPECIFICACIONES
Entrada nominal: Tipo de intensidad. Aislamiento
galvánico que se lleva a cabo por medio de accesorios
del transformador de intensidad TCD externos. Escala
de intensidad: a través de transformadores de corriente
TCD (hasta 630 A). Escala de tensión: 240VLN y
415VLL (MV5), 133VLN y 230VLL (MV6). Precisión:
los siguientes datos corresponden a toda la cadena
de medición: contador base EM270 y transformador
de intensidad TCD. Escala de intensidad: In: 160A,
250A, 630A (Intensidad del primario de TCD). Escala
de tensión: MV5 Un: 160 a 260 VLN (277 a 450 VLL).
MV6 rango Un: 40 a 144 VLN (70 a 250 VLL). Tensión de
fase neutra. En el rango Un: ±(0,5% lec. +1díg.). Tensión
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

CARLO GAVAZZI EM27072DMV53XOSX Guida d'installazione

Tipo
Guida d'installazione