Dynisco EIT Series Manuale utente

Tipo
Manuale utente
1
Operating manual
EIT Series
Intrinsically safe pressure transmitter
for industrial application
II2G
ATEX100A
CE
2
Table of Contents
Content
General
Notes on safety
Technical data
Function
Transport/
delivery
Installation
Commissioning
Maintenance
Accessories
Troubleshooting
-Declaration of
conformity
Ex-Declaration
of conformity
Chapter
1
2
3
4
5
6
7
8
9
10
11
12
Page
3
3
7
13
15
16
22
24
25
26
27
28
Icon
3
Operating manual
1. General
1.1 Important information 3
1.2 Copyright 3
1.3 Explanation of icons 4
1.4 Abbreviations 4
1.5 Correct use 4
1.6 User’s obligations 4
1.1 Important information
This manual applies to the EIT series only. It must
be kept near the equipment in a readily and
immediately accessible location at all times.
The content of this manual must be read,
understood and followed in all points by all relevant
people. This applies in particular to the notes on
safety. Following the safety instructions will help to
prevent accidents, defects and malfunctions.
DYNISCO will not be held liable for any injury, loss
or damage resulting from failure to follow the
instructions in this manual.
If malfunctions occur in spite of having followed the
operating instructions, please contact the
DYNISCO customer service department (see
chapter 8, Maintenance).
This applies in particular during the warranty
period.
1.2 Copyright
Copyright law requires that this manual be used for
in-house purposes only.
All reproduction, even partially and for in-house
purposes, requires the approval of DYNISCO. This
manual may not be forwarded to third parties.
4
1.3 Explanation of icons
The manual uses icons to indicate information
pertaining to safety:
Risk of destruction or damage to
equipment, machines or installations
General danger to life or limb
The safety instructions are provided again in the
individual chapters of the manual.
1.4 Abbreviations
The following abbreviations are used:
OM operating manual
PT pressure transducer
f.s. of full scale
1.5 Correct use
The EIT pressure transmitter is for measuring
pressure in industrial explosive environments (safety
class II 2G EEx ia IIC T5 up to 75°C, II 2G EEx ia IIC
T1-T4 up to 80°C) as part of a larger overall system.
Type specific installation of the PT with:
- Internal thread ISO 228/1 - G¼ (EIT 332)
- Screw-in trunnion with external thread
DIN 3852-A G¼A (EIT 352)
- Thread M18 x 1.5 (EIT 372)
The safety and accident prevention regulations
specific to the application must be followed.
When using the PT as a safety component in
accordance with the EC Machine Directive,
Annex IIc, the equipment manufacturer must
take any necessary precautions to ensure that
malfunctions of the PT cannot cause damage or
injury.
1.6 User’s obligations
The operator or owner of the larger overall system,
e.g. a machine, is responsible for following the safety
and accident prevention regulations that apply to the
specific application.
5
Operating manual
2. Notes on safety
The operator or owner of the larger overall
system is responsible for following the
safety and accident prevention regulations
that apply to the specific application.
When planning machinery and using the
PT, follow the safety and accident
prevention regulations that apply to your
application, e.g.:
EN 60204, Electrical equipment in
machines.
EN 292, Machine safety, general design
guidelines.
DIN 57 100 Part 410, Protection against
electric shock.
EN 50 014, Electrical equipment for
explosive atmospheres, general
provisions
EN 50 020, Intrinsic safety “i”
Mounting and electrical connection of the
PT must be done by specialists with EMC
training, following all applicable regulations,
and in pressureless, voltage-free,
intrinsically safe condition with the
machine switched off.
The machine must be secured against
being switched back on!
Ambient temperature for the electronics
housing max. +75°C (safety class T5;
T1 - T4 max. +80°C).
Higher temperatures can result in damage
and malfunction. Do not install the
pressure transmitter in places where this
temperature is exceeded.
Explosion hazard!
Deviation of the supply voltage from the
value given in the technical specifications,
or false polarity, can damage the pressure
transmitter and cause malfunctions that
can pose a risk of explosion.
6
Operate only with an intrinsically safe,
EMC compliant power supply with the
following specifications:
Supply voltage max. 28 V DC
Current output max. 93 mA
Power output max. 690 mW
Inductivity max. 1 mH
Capacity max.
53 nF
Explosion hazard!
The pressure transmitter must be
connected using a 2x2-core, twisted cable
(blue cable sheath).
Do not lay connecting cables in the direct
vicinity of cables carrying higher voltage or
used to switch inductive or capacitive
loads.
7
Operating manual
3. Technical Data
3.1 Ordering guide 7
3.2 Ordering example 7
3.3 Safety related specifications 8
3.4 Performance characteristics 8
3.4.1 Accuracy 8
3.4.2 Repeatability 8
3.4.3 Resolution 8
3.5 Pressure side connection 8
3.6 Pressure ranges 9
3.6.1 Pressure ranges in bar 9
3.6.2 Max. Overload 9
3.6.3 Burstpressure 9
3.6.4 Limit frequency 9
3.7 Electrical Data 9
3.8 Temperature influence 9
3.9 EMC requirements 10
3.10 Materials 10
3.11 Max. Mounting torque 10
3.12 Environmental protection 10
3.13 Weight 10
3.14 Seal 11
3.15 Dimensions 12
3.1 Ordering guide
EIT 3xx - xx - Option
Pressure range
Output signal
Pressure port
The exact meanings of the letter/digit combinations
are given in the corresponding sections of chapter 3.
3.2 Ordering example
EIT 352 - 5C Intrinsically safe PT
Press. port: 5 = External
thread DIN 3852-A G¼A
Output signal:
2 = 4 - 20 mA, 2-wire
Press. range: 0 - 500 bar
8
3.3 Safety related specifications
ATEX certificate No.: ZELM 01 ATEX 0071
Ex safety class EEx ia IIC T5 up to 75°C
EEx ia IIC T1-T4 up to 80°C
Safety class EEx ia IIC T5 includes the following other
safety classes:
Intrinsic safety “ib”
Explosion groups IIA and IIB
Temperature classes T1 - T4 up to 80°C
Certified maximum values
Associated electrical equipment must satisfy the
following conditions:
Supply voltage max. 28 V DC
Current output max. 93 mA
Power output max. 690 mW
Inductivity max. 1 mH
Capacity max. 53 nF
3.4 Performance characteristics (EIT3x2-xx)
3.4.1 Accuracy
(Linearity and hysteresis at T = constant)
EIT3x2 ±0.3% typ., ±0.5% of full
scale
3.4.2 Repeatability ± 0.1 % of full scale
pressure
3.4.3 Resolution infinite
3.5 Pressure side connection (EIT3X2-xx)
EIT332 Internal thread ISO228/1-G¼
EIT352 Screw-in trunnion with
external thread DIN 3852-A
G¼A
EIT372 Screw-in trunnion with
external thread M18 x 1.5
flush diaphragm
9
Operating manual
3.6 Pressure ranges (EIT3x2-XX)
3.6.1 Pressure ranges in bar
Model number Permitted pressure range
bar
EIT3x2-20 0 - 20 series 372 only
EIT3x2-35 0 - 35 series 372 only
EIT3x2-50 0 - 50
EIT3x2-1C 0 - 100
EIT3x2-1,5C 0 - 150
EIT3x2-2C 0 - 200
EIT3x2-3,5C 0 - 350
EIT3x2-5C 0 - 500
EIT3x2-7C 0 - 700
EIT3x2-1M 0 - 1000
Other pressure ranges on request
3.6.2 Max. Overload (without influencing operating
data)
2 x full scale pressure up to 700 bar
Max. 1500 bar for the 1000 bar range
3.6.3 Burst pressure 4 x full scale pressure
3 x full scale pressure for
the 20 bar and 1000 bar
range
3.6.4 Limit frequency 1.5 kHz [-3dB]
3.7 Electrical data
Configuration 4-arm Wheatstone bridge
strain gauge with int. amplifier
Output signal 2-wire 4 - 20 mA
Strain resistance RL < 750 bei US = 28 V
RL < 145 bei US = 15 V
Supply voltage 15 - 28 VDC -15 % +0 %
over approved electrical
equipment to EN 50 020
power consumption < 20 mA
Calibration function 80 % ± 0,5 % of full scale
(room temperature) output by externally con-
necting contacts E and F
Zero balance min. - 2 % / + 10 % f.s
Range balance ± 10 % of full scale
10
Leakage resistance > 1000 M bei 50 V
3.8 Temperature influence
Storage temperature - 45°C to + 120°C
(medium temperature)
Operating temperature - 25°C to + 80°C
(medium temperature)
Max. housing temperatures
Safety class T1 - T4 - 25°C to + 80°C
Safety class T5 - 25°C to + 75°C
Compensated
temperature range 0°C to + 70°C
(medium temperature)
Zero shift due to
temperature change ± 0.1 % f.s. / 10 °C typ.
Sensitivity shift due to
temperature change ± 0.2 % f.s. / 10 °C typ.
3.9 EMC requirements
Conforming to in accordance with EMC directive.
Emitted interference DIN EN 50081-1
(residential area)
Immunity DIN EN 50082-2
(industrial area)
Connecting cables defined as data lines
3.10 Materials
In contact with medium 15-5PH Mat.No. 1.4545
3.11 Max. Mounting torque 22 Nm
3.12 Environmental protection to IEC 529
Pressure transducer IP65 (without connector)
Standard female cable
connector DIN IP40
11
Operating manual
Cable connection
option D05 IP67
3.13 Weight 0.25 kg
3.14 Seal
Data of the standard seal:
Appropriate media Mineral oil, water, air,
oil-water-emulsions
Temperature range - 35°C to + 120°C according
to elastomer quality
Operating pressure When fitted in a recess up to
1000 bar.
Without recess and outside
of seal < 40 mm up to
400 bar
12
Fig. 01: EIT332
Fig. 02: EIT352
Fig. 03: EIT372
20 bar 35 bar 50 bar 100 bar 150 bar
X12.55±0.305 12.61±0.305 12.78±0.305 12.95±0.313 13.12±0.313
200 bar 350 bar 500 bar 700 bar 1000 bar
X13.225±0.313 13.515±0.313 13.75±0.313 13.95±0.313 14.29±0.313
3.15 Dimensions
13
Operating manual
4. Function
4.1 Construction 13
4.2 Description of functions 13
4.1 Construction
The PTs of series EIT are industry standard.
The most important advantages are:
- Intrinsically safe EEx ia IIC T5
- thermal stability
- insensitivity to pressure peaks
- insensitivity to electromagnetic radiation (EMC)
- fully welded housing
- potted electronics
- maximum pressure 1000 bar
4.2 Description of functions
Through a diaphragm, the PT furnishes an electrical
signal that is proportional to the pressure of the
medium.
The pressure applied by the medium is forwarded to
the measuring diaphragm. The deflection of the
measuring diaphragm changes the resistance of the
strain gauge bonded to the measuring diaphragm.
The strain gauge is a Wheatstone bridge.
Dependent on the PT model, an electric signal
proportional to the pressure is generated via the
supply voltage or the amplifier.
14
Fig. 04: Functioning principle of the PT of the EIT series
Housing of PT
Strain gauge
Sealing surface
Diaphragm
Intrinsic safe
mA amplifier
15
Operating manual
5. Transport / delivery
5.1 Transport / packing /
transport damage 15
5.2 Storage 15
5.3 Scope of delivery 15
ESD sensitive component. Electrostatic
discharge may damage the PT.
Take ESD precautions.
5.1 Transport/packing/transport damage
- Do not let the PT be damaged by other items
during transit.
- Use only the original packaging.
- Report transport damage to DYNISCO
immediately in writing.
5.2 Storage
- Store the PT in original packaging only.
- Protect against dust and moisture.
5.3 Scope of delivery
- PT with diaphragm protection cap
- Seal
- Cable socket
- Calibration sheet
- Operating manual
16
6. Installation
6.1 Screw-in trunnion / Mounting hole 16
6.2 Mounting the Pressure Transducer 18
6.3 Electrical connection 19
6.3.1 EMC / compliant connection 20
6.4 Connection assignments 20
6.5 Wiring 21
Ambient temperature for the electronics
housing max. +75°C (safety class T5;
T1 - T4 max. +80°C).
Higher temperatures can result in damage
and malfunction. Do not install the
pressure transmitter in places where this
temperature is exceeded.
6.1 Screw-in trunnion / Mounting hole
- Make screw-in trunnion / mounting hole as shown
in figure 05 / 06 and 07.
Fig. 05: Screw-in trunnion for PT EIT 332 with
internal thread according to ISO 228/1 - G¼
12
R1
1x45°
3
G¼A
17
Operating manual
Fig. 06: Mounting hole form X
for PT EIT 352 with screw-in trunnion
according to DIN 3852-A G¼A
1) The recess is not nessecary when no seal is used and the contact area is
plain and rectangular to the axis of the thread.
2) Thread counterbored to outside diameter.
Fig. 07: Mounting hole for PT EIT 372 with screw-in
trunnion M18 x 1.5
1) The recess is not nessecary when no seal is used and the contact area is
plain and rectangular to the axis of the thread.
2) Thread counterbored to outside diameter.
X min. see chap. 3.15,
Dimensions
18
When reworking the screw-in trunnion / mounting
hole, pay particular attention to the centricity of:
- the hole,
- the thread and
- the sealing surface.
Pressure sealing with the standard seal takes place
on the sealing surface and on the front cylindrical
section of the PT.
The sealing surface must be:
- correctly machined
- free from marks and rough edges
6.2 Mounting the Pressure Transducer
Mounting and electrical connection of the
PT must be done by specialists with EMC
training, following all applicable regulations,
and in pressureless, voltage-free,
intrinsically safe condition with the
machine switched off.
The machine must be secured against
being switched back on!
ESD sensitive component. Electrostatic
discharge may damage the PT.
Take ESD precautions.
Before mounting the PT, check the screw-
in trunnion / mounting hole carefully. The
PT must only be mounted when the
screw-in trunnion / mounting hole satisfy
the require-ments stipulated in chapter 6.1.
Screw-in trunnion / mounting hole that does
not satisfy these requirements can damage
the PT.
For pressure sealing use always the seal
that is delivered with the PT!
To prevent the PT from sticking
permanently at the screw-in trunnion /
mounting hole, coat the thread section of
the transducer with high temperature
resistant grease or a suitable parting
agent.
Always use a spanner applied to the
designated hexagon collar when screwing
the PT in and out.
19
Operating manual
Do not apply the tool to the housing!
Maximum mounting torque 22 Nm.
If the mounting torque is too high, the PT
may be damaged or its zero point may
shift.
- put the seal between PT and screw-in trunnion /
mounting hole. The seal has to fit plain to the
surface and must not be damaged.
- screw the PT to the screw-in trunnion / mounting
hole and tighten.
6.3 Electrical connection
Mounting and electrical connection of the
PT must be done by specialists with EMC
training, following all applicable regulations,
and in pressureless, voltage-free,
intrinsically safe condition with the
machine switched off.
The machine must be secured against
being switched back on!
Explosion hazard!
The pressure transmitter must be
connected using a 2x2-core, twisted cable
(blue cable sheath).
Do not lay connecting cables in the direct
vicinity of cables carrying higher voltage or
used to switch inductive or capacitive
loads.
Operate only with an intrinsically safe,
EMC compliant power supply with the
following specifications:
Supply voltage max. 28 V DC
Current output max. 93 mA
Power output max. 690 mW
Inductivity max. 1 mH
Capacity max.
53 nF
ESD sensitive component. Electrostatic
discharge may damage the PT.
Take ESD precautions.
The electrical connection must comply
with EMC requirements.
If the electrical connection is not made as
described in chapter 6.3.1, or if cables /
20
cable connectors / cable glands other than
those stipulated by DYNISCO are used,
DYNISCO cannot guarantee that EMC
requirements will be satisfied.
6.3.1 EMC / compliant connection
- Earth the machine section with the screw-in
trunnion / mounting hole for the PT in accordance
with regulations. The PT must be connected to
earth via the screw-in trunnion / mounting hole.
- Connect the shield of the connecting cable on
both sides, making sure it conducts with full and
continuous contact.
- When introducing the connecting cable into an
EMC compliant switch cabinet, for example,
connect the shield correctely (cable gland,
conducting, full contact, continuous) to the
conductive housing or route it via built-in cable
connector that is also connected to the conducti-
ve housing.
- Connect unused cable cores or free cable ends
correctely to the cable shield on both sides..
For order numbers of EMC compliant cable
connectors required for connecting the PT, see
chapter 9, Accessories.
6.4 Connection assignments
Standard models EIT:
Equipment connector: 7-pin male connector,
DIN
Female connector: DIN
Fig. 08: 7-pin female connector
The connector housing is connected conductively to
the housing of the PT.
Top view solderside
PIN Designation
1 supply voltage (+)
2 supply voltage (-)
3 signal (+)
4 signal (-)
5 calibration
6 calibration
7
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30

Dynisco EIT Series Manuale utente

Tipo
Manuale utente

in altre lingue