8
MIOxx
ATTENTION!
The two removable serial number stickers should be taken off the module; one should be
attached to the box where the device is to be housed, the other to the installation layout.
Once all the loop devices have been properly connected, refer to the control panel installation and programming
manual for instructions regarding the configuration and addressing procedures.
Testing and maintenance
The functionality of the module should be tested immediately
after installation and periodically during maintenance
inspections, in accordance with the established standard
regulations and codes in force.
Using the PRG20 driver
The PRG20 driver allows you to change the operating parameters
of the devices connected to the loop and also to obtain accurate
diagnostic data. It can operate through the USB port of a
computer furnished with the relative software programme, or can
function autonomously by way of the battery housed inside.
For further information and details regarding use of the PRG20
driver, refer to the respective handbook.
Warnings and limitations
The MIOxx module must be used exclusively with control panels
that operate on CAME S.p.A. protocol. This product is not
suitable for outdoor installation. However, if outdoor installation
is necessary, ensure that the device is housed inside a suitable
enclosure with the required protection grade.
CE marking and certifications
DoP, EC DoC and certificates related to these products can be
downloaded from the following link:
www.came.com, DOWNLOAD/CERTIFICATIONS section
MIOxx Technical specifications Short-circuit isolator Technical specifications
Power supply 19-30 Vdc Vmax The maximum line voltage 30 Vdc
Current draw in standby status Max 80PA @ 24V Vnom The nominal line voltage 24 Vdc
Current draw in alarm status 20 mA @27.6V Vmin The minimum line voltage 19 Vdc
Input balancing resistance 22K Ohm VSO max
The maximum voltage at which the
device isolates
(i.e. switches from closed to open) 12.5 Vdc
Alarm input resistance 2,2K Ohm VSO min
The minimum voltage at which the
device isolates
(i.e. switches from closed to open) 10 Vdc
Supervised output EOL resistance 22K Ohm VSC max
The maximum voltage at which the
device reconnects
(i.e. switches from open to closed) 9 Vdc
Relay contact rating MAX 1A / 30Vdc IL max
The maximum leakage current with the
switch open
(isolated state) 15 mA
Operating temperature -5°C/+40°C Ic max The maximum rated switching current
(e.g. with the switch closed) 600 mA
Humidity (without condensation) 95% RH IS max The maximum rated continuous current
(e.g. under short circuit conditions) 600 mA
Height (with terminal boards) 106 mm ZC max The maximum series impedance with
the switch closed 0.5 mOhm
Height (without anchor locations) 99 mm
Width 113 mm
Depth (with terminal boards) 29 mm
Depth (without terminal boards) 19 mm
Weight (with terminal boards) 140 g
0832
CAME S.p.A.
Via Martiri della libertà, 15
31030 Dosson Di Casier (Tv) - Italy
15
0832-CPR-F0981
0832-CPR-F0982
0832-CPR-F0983
0832-CPR-F0984
0832-CPR-F0985
EN 54-17:2005
EN 54-18:2005
MIO44S
MIO44R
MIO4I
MIO40S
MIO40R
Intelligent analogue addressable multi input/output module
with short-circuit isolator for fire detection and fire alarm
systems installed in buildings
Essential Characteristics Performance
Response delay (response time) PASS
Performance under fire conditions PASS
Operational reliability PASS
Durability of
operational
reliability:
Temperature resistance PASS
Vibration resistance PASS
Humidity resistance PASS
Corrosion resistance PASS
Electrical stability PASS
CAME S.p.A. reserves the right to change the
technical specifications of this product without prior
notice.