CARLO GAVAZZI WM10DINAV93XXXX Guida d'installazione

Tipo
Guida d'installazione
CARLO GAVAZZI
Automation Components
C
arlo Gavazzi Controls SpA,
V
ia Safforze, 8 - 32100
Belluno (Italy)
Tel. +39 0437 931000,
Fax +39 0437 931021
W
M10DIN IM ML 061207 Code 8020838
WM10 DIN Multifunction
Meter
DESCRIPTION
A-
Joystick: move the joystick to direction 1 to display the
active power of each single phase and of the system, the
reactive power of each single phase and of the system and
the Power Factor of the system value. Move the joystick to
direction 2 to display the current values. Move the joystick to
direction 3 to display the voltage L-L of each single phase
and of the system, the voltage L-N of each single phase and
of the system and the frequency value. The default page is
relevant to the indication of WL1, WL2 and WL3. On TAB1
there are reported all the pages that can be displayed.
B- Phase sequence alarm: it means that the detected phase-
sequence is not correct.
The measurement is independent of the current flow
direction.
"EEE" is displayed in case of "OVERFLOW".
ELECTRICAL CONNECTIONS
[1]-
3 phases, 4 wires, unbalanced/balanced load.
[2]- 3 phases, 3 wires, unbalanced/balanced load.
SAFETY PRECAUTIONS
Read carefully the instruction manual.
If the
instrument is used in a manner not specified
by the producer, the protection provided by
the instrument may be impaired.
Maintenance: make
sure that the connections are correctly carried out in
order to avoid any malfunctioning or damage to the
instrument. To keep the instrument clean, use a slight-
ly damp cloth; do not use any abrasives or solvents.
We recommend to disconnect the instrument before
cleaning it.
TECHNICAL SPECIFICATIONS
Input specifications:
System type: 3-phase. Current: direct input,
current range 10 (65) A.
Voltage: 230VLN / 400VLL. Accuracy
(display): (@25°C ±5°C, R.H. 60%, 48-62Hz) Ib: 10A, Imax:
65A; Un: from 184 to 276VLN (from 318 to 480 VLL).
Current:
from 0,004Ib to 0.2Ib: ±(0.5% RDG +3DGT); from 0.2Ib to Imax:
±(0.5% RDG +1DGT). Active power ±(1%RDG +2DGT).
Temperature drift: 200ppm/°C. Sampling frequency: 1600
ENGLISH
DESCRIZIONE
A-
Joystick: spingere in direzione 1 per visualizzare il valo-
re delle potenze attive di fase e di sistema, potenze reatti-
ve di fase e di sistema e il valore del cos
ϕ di sistema.
Spingere in direzione 2 per visualizzare le correnti.
Spingere in direzione 3 per visualizzare i valori delle tensio-
ni fase-neutro di singola fase o di sistema, i valori delle
tensioni fase-fase singole e di sistema e il valore della fre-
quenza. La pagina visualizzata di default è quella relativa
alla visualizzazione delle potenze attive di fase (WL1, WL2,
WL3). Le pagine che possono essere visualizzate sono
riportate nella tabella TAB1.
B- Allarme sequenza fasi: indica che la sequenza delle fasi
non è corretta.
La misura è indipendente dal verso della corrente.
In caso di "OVERFLOW" lo strumento visualizza "EEE".
COLLEGAMENTI ELETTRICI
[1]-
3 fasi, 4 fili, carico squilibrato/equilibrato.
[2]- 3 fasi, 3 fili, carico squilibrato/equilibrato.
NORME DI SICUREZZA
Leggere attentamente il manuale istruzioni.
Qualora l’apparecchio venisse adoperato in un
modo non specificato dal costruttore, la prote-
zione prevista dall’apparecchio potrebbe essere compro-
messa.
Manutenzione: assicurarsi che i collegamenti
siano effettuati correttamente al fine di evitare qualsiasi
malfunzionamento o danneggiamento dello strumento.
Per mantener
e pulito lo str
umento usare un panno legger-
mente inumidito; non usare abrasivi o solventi. Si consi-
glia di scollegare lo strumento prima di pulirlo.
CARATTERISTICHE TECNICHE
Ingressi di misura:
Sistema trifase. Corrente: Ingresso diretto
portata corrente 10 (65) A.
Tensione 230VLN / 400VLL.
Precisione (display): (@25°C ±5°C, U.R. 60%, 48-62Hz) Ib:
10A, Imax: 65A; Un: da 184 a 276VLN (da 318 a 480 VLL).
Cor
r
ente:
da 0,004Ib a 0,2Ib:
±
(0,5% RDG +3DGT); da 0,2Ib a
Imax:
±
(0,5% RDG +1DGT).
Potenza attiva ±
(1%RDG +2DGT).
Potenza reattiva ±(2%RDG +2DGT). Deriva termica:
ITALIANO
BESCHREIBUNG
A-
Joystick: Joystick in Richtung 1 drücken, um die
Wirkleistung je Phase und System anzuzeigen, die
Blindleistung je Phase und System und um Cos Phi
Wert des Systems anzuzeigen. Um die Ströme anzu-
zeigen, muß der Joystick in Richtung 2 gedrückt
werden. Um die kvarh Zähler anzuzeigen, muss der
Joystick in Richtung 3 gedrückt werden. Die kWh
Zähler werden nach einer Minute automatisch ange-
zeigt.
B- Phasenfolge Alarm: die Phasenfolge ist nicht
korrekt. Die Messung ist unabhängig von der
Stromrichtung.
Im Falle einer Messbereichsüberschreitung, wird
“EEE” angezeigt.
ELEKTRISCHE ANSCHLUSS
[1]-
3-Phasen, 4-Adern asymmetrische/symmetriche Last.
[2]- 3-Phasen, 3-Adern, asymmetrische/symmetriche Last.
SICHERHEITSBESTIMMUNGEN
Die Betriebsanleitung aufmerksam lesen.
Sollte das Gerät nicht gemäss der
Herstellerangaben verwendet werden, könnte
der vom Gerät vorgesehene Schutz beeinträchtigt wer-
den.
Wartung: Beachten Sie den korrekten Anschluss
aller Anschlussterminals um eine Beschädigung des
Instruments zu vermeiden. Das Gerät mit einem feuch-
ten Tuch reinigen; keine Scheuer- oder Lösemittel ver-
wenden. Das Gerät vor der Reinigung ausschalten.
TECHNISCHE DATEN
Messeingänge (Nennwerte):
3 Phasensystem. Strommessung:
Direktmessung: Strombereich 10 (65) A. Spannung 230VLN /
400VLL.
Genauigkeit (Anzeige): (@25°C ±5°C, R.F. 60%, 48-
62Hz) Ib: 10A, Imax: 65A; Un: von 184 bis 276VLN (von 318 bis
480 VLL). Str
om:
von 0,004Ib bis 0,2Ib:
±(0,5% RDG +3DGT);
von 0,2Ib bis Imax:
±
(0,5% RDG +1DGT).
W
irkleistung
±
(1%RDG +2DGT).
Blindleistung ±
(2%RDG +2DGT).
DEUTSCH
DESCRIPTION
A-
Joystick: actionner le joystick dans la direction 1 pour
afficher la puissance active de chaque phase et du systè-
me, la puissance réactive de chaque phase et du système
et la valeur du facteur de puissance du système. Actionner
le joystick dans la direction 2 pour afficher les courants.
Actionner le joystick dans la direction 3 pour afficher la
tension L-L de phase et du système, la tension L-N de
phase et du système et la valeur de la fréquence. La page
par défaut se réfère à l’indication de WL1, WL2 et WL3.
Sur le tableau TAB1 sont détaillées toutes les pages qui
peuvent être affichées.
B- Alarme séquence de phase: la séquence de phase n’est
pas correcte. La mesure est indépendante de la direction
du courant.
L’appareil affiche “EEE” dans le case de "SURCHARGE".
SCHEMAS ELECTRIQUES
[1]-
3 phases, 4 câbles, charge déséquilibrée/équilibrée.
[2]- 3 phases, 3 câbles, charge déséquilibrée/équilibrée.
MESURES DE SECURITE
Lire attentivement le manuel de l’utilisateur.
Si
l’appareil est utilisé dans des conditions différen-
tes de celles spécifiées par le fabricant, le niveau
de protection prévu par l’instrument peut être compromis.
Entretien: s’assurer que les connexions sont réalisées cor-
rectement dans le but d’éviter toutes fautes ou endomma-
gements de l’appareil. Pour nettoyer l’instrument, utiliser un
chiffon humide; ne pas utiliser d’abrasifs ou de solvants. Il
faut déconnecter le dispositif avant de procéder au net-
toyage
.
CARACTERISTIQUES TECNIQUES
Entrées nominales:
système triphasé. Courant: Entrée directe:
plage de courant 10 (65) A. Tension 230VLN / 400VLL.
Précision
(afficheur): (@25°C ±5°C, H.R. 60%, 48-62Hz) Ib: 10A, Imax:
65A; Un: de 184 à 276VLN (de 318 à 480 VLL).
Courant: de
0,004Ib à 0,2Ib: ±(0,5% RDG +3DGT); de 0,2Ib à Imax: ±(0,5%
RDG +1DGT). Puissance active ±(1%RDG +2DGT). Puissance
réactive ±(2%RDG +2DGT). Dérive de température:
FRANÇAIS
DESCRIPCION
A-
Joystick: mover el joystick en dirección 1 para visuali-
zar la potencia activa de cada fase y del sistema, la poten-
cia reactiva de cada fase y del sistema y el factor de poten-
cia del sistema. Mover el joystick en dirección 2 para
visualizar los valores de intensidad. Mover el joystick en
dirección 3 para visualizar la tensión L-L de cada fase y del
sistema, la tensión L-N de cada fase y del sistema y el
valor de la frecuencia. La página por defecto se refiere a la
indicatión de WL1, WL2 y WL3. En la TAB1 se detallan
todas las páginas que pueden visualizarse.
B- Alarma secuencia fases: indica que la secuencia de las
fases no es correcta. La medida es independiente de la
dirección de la intensidad.
En caso de "SOBRERRANGO" el equipo visualiza "EEE".
CONEXIONES ELÉCTRICAS
[1]-
Trifásico, 4 hilos, carga desequilibrada/equilibrada.
[2]- Trifásico, 3 hilos, carga desequilibrada/equilibrada.
NORMAS DE SEGURIDAD
Lea atentamente este manual de instrucciones.
Si
el instrumento se usa de modo distinto al indicado
por el fabricante, la protección de seguridad ofreci-
da por el instrumento podrá resultar dañada.
Mantenimiento:
asegúrese de montar correctamente los módulos extraibles y
los cables correspondientes para evitar un mal funcionamien-
to y posibles daños en el equipo. Para limpiar el equipo, utili-
zar siempre un trapo ligeramente humedecido, nunca produc-
tos abrasivos o disolventes. Se recomienda desconectar
siempre el instrumento antes de limpiarlo.
ESPECIFICACIONES TECNICAS
Entradas de medida:
Sistema trifásico. Intensidad: conexión
directa 10 (65) A. Tensión 230VLN / 400VLL.
Precisión: (dis-
play)
: (@25°C ±5°C, H.R. 60%, 48-62Hz) Ib: 10A, Imax: 65A;
Vn: de 184 a 276VLN (de 318 a 480 VLL).
Intensidad: de 0,004Ib
a 0,2Ib: ±(0,5% lec. +3 díg.); de 0,2Ib a Imax: ±(0,5% lec. +1díg.).
Potencia activa ±(1% lec. +2díg.). Potencia reactiva ±(2%lec.
+2díg.).
ESPAÑOL
[1]
[2]
B
A
!
7
1,6
90
mm
45
43,6
16,4
6
6,3
! ! ! !
samples/s at 50Hz, 1900 samples/s at 60Hz. Display: 2 rows (1 x
7 DGT; 1 x 3 DGT). Type: LCD, h 9mm. Instantaneous variables:
3 DGT.
Overload status: EEE indications when the measured
value exceeds the “continuous input overload” (max. measuring
capacity). max. instantaneous variables: 999; Min. instantaneous
variables: 0;
Measurements: TRMS measurement method of dis-
torted wave forms. Coupling type: direct.
Crest factor: Ib 10A 4
(65A max. peak). Current overload: continuous: 65A at 50Hz. For
10ms: 1920A max at 50Hz. Voltage overload: continuous 1,2 Un.
For 500ms 2 Un. Input impedance: 400VL-L see “self-consump-
tion”: 65A: < 4VA. Frequency: from 45 to 65 Hz. Joystick: For the
selection of the measuring pages. Operating temperature: from -
25°C to +55°C (from -13°F to 131°F), (R.H. from 0 to 90% non
condensing @ 40°C).
Storage temperature: from -30°C to +70°C
(from -22°F to 140°F) (R.H. < 90% non-condensing @ 40°C).
Installation category: Cat. III (IEC60664, EN60664). Dielectric
strength: 4000 VRMS for 1 minute. Rejection: CMRR 100 dB
from 48 to 62 Hz.
EMC: according to EN62052-11. Electrostatic
discharges: 15kV air discharge; Immunity to irradiated test with
current: 10V/m from 80 to 2000MHz; electromagnetic field test
without any current: 30V/m from 80 to 2000MHz; Burst on cur-
rent and voltage measuring input circuits: 4kV. Immunity to con-
ducted disturbances: 10V/m from 150KHz to 80MHz. Surge on
current and voltage measuring input circuits: 4kV. Radio frequen-
cy suppression according to CISPR 22.
Standard compliance:
safety IEC60664, IEC61010-1 EN60664, EN61010-1 EN62052-11.
Approvals: CE. Connections: screw-type. Cable cross section
area: Max. 16 mm
2
; Min. 2.5 mm
2
. Min./max. screw tightening
gauge: 1.7 Nm / 3 Nm. DIN Housing: dimensions 71 x 90 x 64.5
mm. Material: nylon PA66; self-extinguishing: UL 94 V-0. DIN rail
mounting.
Protection degree: front: IP50. Connections: IP20.
Weight: approx. 400 g (packing included). Self power supply: -
20% +15% 48-62Hz. Self consumption: 20VA/1W.
200ppm/°C. Frequenza di campionamento: 1600 campioni/s a
50Hz, 1900 campioni/s a 60Hz.
Display: 2 linee (1 x 7 DGT 1 x 3
DGT). Tipo: LCD, h 9mm. Lettura variabili istantanee: 3 DGT.
Stato sovraccarico: indicazione EEE quando il valore misurato
eccede il “sovraccarico continuo d’ingresso” (massima capacità
di misura). Max. variabili istantanee: 999.
Misure: metodo TRMS
misura delle forme d’onda distorte. Tipo di accoppiamento: diret-
to.
Fattore di cresta: Ib 10A 4 (65A max. picco). Sovraccarico
corrente: continuo: 65A a 50Hz. Per 10ms: 1920A max a 50Hz.
Sovraccarico tensione: continuo 1,2 Un. Per 500ms 2 Un.
Impedenza d’ingresso: 400VL-L vedi “autoconsumo”: 65A: <
4VA. Frequenza: da 45 a 65 Hz. Joystick: Per la selezione delle
pagine di misura.
Temperatura di funzionamento: da -25°C a
+55°C (da -13°F a 131°F), (U.R. da 0 a 90% senza condensa @
40°C). Temperatura di immagazzinamento: da -30°C a +70°C
(da -22°F a 140°F) (U.R. < 90% senza condensa @ 40°C) .
Categoria di installazione: Cat. III (IEC60664, EN60664) .
Rigidità dielettrica: 4000 VRMS per 1 minuto. Reiezione CMRR
100 dB da 48 a 62 Hz. EMC: secondo EN62052-11. Scariche elet-
trostatiche: 15kV scarica in aria; Immunità campi elettromagneti-
ci irradianti: provato con corrente applicata: 10V/m da 80 a
2000MHz; Provato senza corrente applicata: da 30V/m da 80 a
2000MHz; Immunità ai transitori veloci: sui circuiti degli ingressi
di misura in corrente e tensione: 4kV. Immunità ai radiodisturbi
condotti: 10V/m da 150KHz a 80MHz. Immunità ad impulso: sui
circuiti degli ingressi di misura in corrente e tensione: 4kV.
Emissioni in radiofrequenza secondo CISPR 22.
Conformità alle
norme: sicurezza IEC60664, IEC61010-1, EN60664, EN61010-1.
Approvazioni CE.
Connessioni: a vite. Sezione del cavo: Max. 16
mm
2
; Min. 2,5 mm
2
(ingressi di misura). Coppia min./max ser-
raggio viti: 1,7 Nm / 3 Nm. Custodia DIN: Dimensioni 71 x 90 x
64.5 mm. Materiale: nylon PA66; autoestinguenza: UL 94 V-0.
Montaggio a guida DIN. Grado di protezione: frontale: IP50.
Connessioni: IP20. Peso: circa 400 g (imballo incluso).
Autoalimentazione: -20% +15% di Un 48-62Hz. Autoconsumo:
20VA/1W.
Temperaturbewegung: 200ppm/°C. Abtastrate: 1600
Abtastpunkte/s @ 50Hz, 1900 Abtastpunkte/s @ 60Hz.
Anzeige: 2
Linien (1 x 7 DGT; 1 x 3 DGT). Art: LCD, h 9mm.
Momentanmessgrößen: 3 DGT. Überlastungsanzeige: EEE-
Anzeige bei dauer hafter überhöhter Eingangsüberlastung (Über-
schreitung der Messeingangs-maximalwerte). Max. momentan-
messgrößen: 999; Min. Momentanmessgrößen: 0;
Messmethode: TRMS-Messungen von verzerrten Wellenformen.
Direktkopplung. Scheitelwertfaktor: Ib 10A 4 (65A Hochspitze).
Überlaststrom: dauer: 65A @ 50Hz. Für 10ms: 1920A max @
50Hz. Überlastspannung: dauer 1,2 Un. Für 500ms 2 Un.
Eingangsimpedanz: 400VL-L in Abhängigkeit der Leistungsauf-
nahme: 65A < 4VA.
Frequenz: von 45 bis 65 Hz. Joystick
(Frontseitiger): Zur Messgrößenwahl. Betriebstemperatur: von
-25°C bis +55°C (von -13°F bis 131°F), (R.F. von 0 bis 90% nicht-
kondensierend @ 40°C) gemäß EN62053-21 und EN62053-23.
Lagertemperatur: von-30°C bis +70°C (von
-22°F bis 140°F) (R.F. < 90% nicht-kondensierend @ 40°C)
Installationskatego-rie: Kat. III (IEC60664, EN60664).
Durchschlagfestigkeit: 4000 VRMS für 1 Minute.
Dämpfungsverhältnis: CMRR 100 dB von 48 bis 62 Hz. EMC:
gemäß EN62052-11. Elektrostatische Entladungen: 15kV air
discharge; Strahlungsimmunität: Test mit angelegten Strom:
10V/m von 80 bis 2000MHz; Test ohne angelegten Strom: von
30V/m bis 80 @ 2000MHz; Überspannungsfestigkeit: am Strom-
und Eingangsspannungsmesskreis: 4kV. Leiterstörungs-immuni-
tät: 10V/m von 150KHz bis 80MHz. Störimpulsfestigkeit: am
Strom- und Eingangsspannungsmesskreis: 4kV. Störabstrahlung
gemäß CISPR 22.
Standardkonformität: Sicherheit IEC60664,
IEC61010-1 EN60664, EN61010-1 EN62052-11. Zulassungen:
CE. Anschlusse: Schraubklemmen. Kabelquerschnitt: Max. 16
mm
2
(Messeingänge); Min. 2,5 mm
2
. Min./Max.
Schraubklemme-Drehmoment: 1,7 Nm / 3 Nm. Gehäuse DIN:
Abmessungen: 71 x 90 x 64.5 mm. Material: Nylon PA66; selbst-
löschend: UL 94 V-0. Montage: DIN Schiene.
Schutzgrad: Front:
IP50. Anschlusse: IP20. Gewicht: ca. 400 g (incl. verpackung).
Selbststromversorgung: -20% +15% 48-62Hz.
Leistungsaufnahme: 20VA/1W
200ppm/°C.
Taux d’échantillonnage: 1600 échantillons/s @
50Hz, 1900 échantillons/s @ 60Hz.
Afficheur: 2 lignes (1 x 7 DGT;
1 x 3 DGT). Type: LCD, h 9mm. Relevé des variables instantanées:
3 DGT. Etat de surcharge: le message “EEE” signal quand la
valeur en cours de mesure excède la “surcharge d’entrées conti-
nues” (capacité de mesure max.). Max. variables instantanées:
999. Min. variables instantanées: 0; énergies 0,0 ou 0.
LED: LED
rouge (consommation d’énergie), 100 imp./kWh. Fréquence max:
16Hz selon EN62052-11. Mesures: méthode mesures TRMS des
formes d’ondes déformées. Type de serrage: direct. Facteur de
crête: Ib 10A 4 (65A pic max.). Surcharges de courant: continu:
65A @ 50Hz. Pour 10ms: 1920A max @ 50Hz. Surcharges de
tension:
continu 1,2 Un. Pour 500ms 2 Un. Impédance d’entrée:
400VL-L Se référer à “consommation d’énergie”: 65A < 4VA.
Fréquence: de 45 à 65 Hz. Joystick: Pour la sélection des pages
de mesure. Température de fonctionnement: de -25°C à +55°C
(de -13°F à 131°F), (H.R. de 0 à 90% sans condensation @ 40°C).
Température de stockage: de -30°C à +70°C (de -22°F à 140°F)
(H.R. < 90% sans condensation @ 40°C). Catégorie d’installa-
tion: Cat. III (IEC60664, EN60664). Tension diélectrique: 4000
VRMS pour 1 minute. Emission de bruit: CMRR 100 dB de 48 à
62Hz. EMC: selon EN62052-11. Décharges électrostatiques: 15kV
décharge atmosphérique; Immunité aux bruits par conduction:
test avec courant: 10V/m de 80 à 2000MHz; Test sans courant
aucun courant: 30V/m de 80 à 2000MHz; Transitoires: sur circuits
d’entrées de mesure courant et tension: 4kV. Immunité aux bruits
par conduction: 10V/m de 150KHz à 80MHz. Immunité à l’impul-
sion: sur circuits d’entrées de mesure courant et tension: 4kV.
Suppression fréquence radio selon CISPR 22.
Conformité aux stan-
dards: sécurité IEC60664, IEC61010-1 EN60664, EN61010-1
EN62052-11. Approbations CE. Connexions: à vis. Section de câble:
Max. 16 mm
2
; Min. 2,5 mm
2
(entrées de mesure). Couple de ser-
rage de vis min./max: 1,7 Nm / 3 Nm. Boîtier DIN. Dimensions 71
x 90 x 64.5 mm. Matériau: nylon PA66; auto extinguible: UL 94 V-0.
Montage: sur rail DIN.
Indice de protection: face avant: IP50.
Terminaisons de vis: IP20. Poids: environs 400 g (emballage inclus).
Version auto-alimentée: -20% +15% 48-62Hz. Consommation d’éner-
gie: 20VA/1W.
Deriva térmica: 200ppm/°C. Frecuencia de muestreo: 1600
lecturas/s @ 50Hz, 1900 lecturas/s @ 60Hz.
Display: 2 líneas (1
x 7 díg; 1 x 3 díg). Tipo: LCD, h 9mm. Lectura de variables ins-
tantáneas: 3 DGT. Indicación de sobrerrango: EEE cuando el
valor medido excede la “Capacidad de entrada de forma conti-
nua"” (capacidad máxima de medida). Variables instantáneas
máx.: 999. Variables instantáneas mín.: 0; energías 0,0 o 0.
LED:
LED rojo (energía consumida), 100 pulsos/kWh. Frecuencia máx:
16Hz según EN62052-11. Medidas: medida TRMS de una onda
distorsionada. Tipo de conexión: directo. Factor de cresta: Ib 10A
4 (65A pico máx.). Sobrecargas intensidad: continua: 65A a
50Hz. Durante 10ms: 1920A máx @ 50Hz. Sobrecargas de ten-
sión:
continua 1,2 Vn. Durante 500ms 2 Vn. Impedancia de
entrada: 400VL-L ver “autoconsumo”: 65A < 4VA. Frecuencia:
de 45 a 65 Hz. Joystick: para la selección de las páginas de medi-
da. Temperatura de funcionamiento: de -25°C a +55°C (de -13°F
a 131°F), (H.R. de 0 a 90% sin condensación @ 40°C).
Temperatura de almacenamiento: de -30°C a +70°C (de -22°F a
140°F) (H.R. < 90% sin condensación @ 40°C). Categoría de ins-
talación: Cat. III (IEC60664, EN60664). Rigidez dieléctrica:
4000 VRMS durante 1 minuto. Inmunidad al ruido CMRR 100
dB de 48 a 62 Hz. Compatibilidad electromagnética (EMC):
según EN62052-11. Descargas electrostáticas: 15kV en el aire;
Inmunidad a los campos electromagnéticos radiados: prueba con
intensidad aplicada: 10V/m de 80 a 2000MHz; Prueba sin intensi-
dad aplicada: 30V/m de 80 a 2000MHz; Ráfagas en el circuito de
entradas de medida de intensidad y tensión: 4kV. Inmunidad a las
perturbaciones conducidas: 10V/m de 150KHz a 80MHz.
Aislamiento: en los circuitos de las entradas de medida en inten-
sidad y tensión: 4kV. Emisiones de radiofrecuencia CISPR 22.
Conformidad con las normas: seguridad IEC60664, IEC61010-1
EN60664, EN61010-1 EN62052-11. Homologaciones CE.
Conexiones: a tornillo. Sección de cable: máx. 16 mm
2
; mín. 2,5
mm
2
(entradas de medida). Mín/Máx. par de apriete: 1,7 Nm / 3
Nm. Caja DIN: Dimensiones 71 x 90 x 64,5 mm. Material: nylon
PA66; autoextinguible: UL 94 V-0. Montaje: carril DIN.
Grado de
protección: panel frontal: IP50. Conexiones: IP20. Peso: aprox.
400 g (embalaje incluido). Autoalimentación: -20% +15% 48-
62Hz. Autoconsumo: 20VA/1W.
WL1= 420kW
WL2= 415kW
WL3= 430kW
W sys= 897kW varL1= 18.0kvar
varL2= 15.8kvar
varL3= 17.3kvar
var sys= 48.3kvar Power factor sys = 0.99PF sys
Phase-sequence alarm.
Allarme sequenza fasi inversa.
Phasenfolge Alarm.
Alarme séquence phase.
Alarma secuencia fases.
V L1-N= 230V
V L2-N= 230V
V L3-N= 230V
VL-N sys= 230V sys VL1-L2= 380V
VL2-L3= 380V
VL3-L1= 380V
VLL sys= 380VLL Hz sys= 50.0Hz
A L1= 65.0A
A L2= 49.8A
A L3= 58.3A
=VLL
  • Page 1 1
  • Page 2 2

CARLO GAVAZZI WM10DINAV93XXXX Guida d'installazione

Tipo
Guida d'installazione