Carel pRack pR300 Manuale utente

Tipo
Manuale utente

Questo manuale è adatto anche per

Integrated Control Solutions & Energy Savings
Manuale d’uso
User manual
EVD EVO driver management
with pRack
Operation and conguration
3
+030220735 - 1.0 - 19.05.2016
ITA
Indice
1. INTRODUZIONE 5
2. TABELLA DI COMPATIBILITÀ 5
3. PROCEDURA DI CONFIGURAZIONE 6
4. NOTE AGGIUNTIVE 7
Gestione del driver EVD EVO con pRack
Operation and conguration
5
+030220735 - 1.0 - 19.05.2016
ITA
1. INTRODUZIONE
2. TABELLA DI COMPATIBILITÀ
Per quanto riguarda le versioni del software pRack e le versioni del driver EVD EVO, non tuti gli incroci sono
possibili. La tabella seguente riporta la compatibilità dichiarata. Si raccomanda di tenerne conto specialmente
in caso di upgrade del software pRack o di sostituzione del driver EVD EVO.
pRack Model pRack SW Version Driver EVD Version Compatibility
pR300T
<= 3.1
5.0 / 5.1
ü
5.6 / 5.7
û
>= 3.2
5.0 / 5.1
ü
5.6 / 5.7
ü
pR100T
<= 3.1
5.0 / 5.1
ü
5.6 / 5.7
û
>= 3.2
5.0 / 5.1
ü
5.6 / 5.7
ü
pR300
< 3.2.0
5.0 / 5.1
ü
5.6 / 5.7
ü
>= 3.2.0
5.0 / 5.1
û
5.6 / 5.7
ü
Tab. 2.a
Il controllore pRack pR300 e pR300T si avvantaggia dell’utilizzo del driver EVD EVO il pilotaggio delle valvole
motorizzate al fine della regolazione e come espansione di ingressi e uscite.
Il driver configurato attraverso le maschere del pRack e non è obbligatorio che sia dotato di un display.
Questo tuttavia è consigliato se si desidera avere costantemente visibile linformazione sull’apertura della
valvola.
Lo scopo della seguente guida è quello di illustrare il metodo consigliato per la prima installazione o la
sostituzione di un driver EVD EVO utilizzato in Fieldbus.
6
+030220735 - 1.0 - 19.05.2016
ITA
3. PROCEDURA DI CONFIGURAZIONE
Per la configurazione di un driver si raccomandano le seguenti operazioni:
1. nel caso di nuova installazione, terminare la configurazione del pRack tramite Wizard, avendo cura di
specificare l’utilizzo del driver
pR300T
Booster system
pR300
Cascade system
pR300
Pumped system
2. collegare il driver alla porta J26 e assicurarsi che abbia indirizzo corrispondente a quello impostato nel
pRack (default 198)
3. tramite la maschera Id03 eseguire lo scarico della configurazione, comando “Download EVD settings
Restore EVD defaults:
NO
Download EVD settings:
NO
Defaults EVD Id03
4. spegnere e riaccendere il controllore pRack
In caso di sostituzione del driver, verificare la compatibilità tra versioni di pRack e EVD EVO come mostrato
al paragrafo 2, quindi eseguire la procedura di configurazione dal punto 2.
7
+030220735 - 1.0 - 19.05.2016
ITA
4. NOTE AGGIUNTIVE
In caso di utilizzo di valvole non Carel e di una versione di pRack pR300T precedente alla 3.3.5, verificare il
numero di passi configurati. In caso di mancata corrispondenza con quelli richiesti dal modello specifico,
eseguire le seguenti operazioni:
modificare il tipo di valvola in maschera Eic02, selezionando CAREL EXV;
selezionare nuovamente la valvola desiderata.
8
+030220735 - 1.0 - 19.05.2016
ITA
Note
3
+030220735 - 1.0 - 19.05.2016
ENG
Contents
1. INTRODUCTION 5
2. COMPATIBILITY TABLE 5
3. CONFIGURATION PROCEDURE 6
4. ADDITIONAL NOTES 7
EVD EVO driver management with pRack
Operation and conguration
5
+030220735 - 1.0 - 19.05.2016
ENG
1. INTRODUCTION
2. COMPATIBILITY TABLE
As regards the pRack software versions and EVD EVO driver versions, not all combinations are possible. The
table below shows compatibility between the different versions. This should be referred to in particular
when upgrading the pRack software or replacing the EVD EVO driver.
pRack Model pRack SW Version Driver EVD Version Compatibility
pR300T
<= 3.1
5.0 / 5.1
ü
5.6 / 5.7
û
>= 3.2
5.0 / 5.1
ü
5.6 / 5.7
ü
pR100T
<= 3.1
5.0 / 5.1
ü
5.6 / 5.7
û
>= 3.2
5.0 / 5.1
ü
5.6 / 5.7
ü
pR300
< 3.2.0
5.0 / 5.1
ü
5.6 / 5.7
ü
>= 3.2.0
5.0 / 5.1
û
5.6 / 5.7
ü
Tab. 2.a
The pRack pR300 and pR300T controllers benefit from the use of the EVD EVO driver to both control
motorised valves and as an input and output expansion.
The driver is configured using the pRack screens and consequently does not need to be fitted with a display.
Nonetheless, this is recommended in order to constantly monitor information on valve opening.
The purpose of this guide is to illustrate the recommended procedure for installing or replacing an EVD EVO
driver on the Fieldbus port.
6
+030220735 - 1.0 - 19.05.2016
ENG
3. CONFIGURATION PROCEDURE
To configure a driver, proceed as follows:
1. for a new installation, complete the pRack configuration using the Wizard, making sure to specify that
the driver is used
pR300T
Booster system
pR300
Cascade system
pR300
Pumped system
2. connect the driver to port J26 and make sure that the address corresponds to the value set on pRack
(default 198)
3. on screen Id03, download the configuration by selecting “Download EVD settings”
Restore EVD defaults:
NO
Download EVD settings:
NO
Defaults EVD Id03
4. switch the pRack controller off and on again
If replacing the driver, check compatibility between the pRack and EVD EVO versions, as shown in
paragraph 2, then complete the configuration procedure starting from point 2.
7
+030220735 - 1.0 - 19.05.2016
ENG
4. ADDITIONAL NOTES
If using non-Carel valves and a pRack pR300T version prior to 3.3.5, check the number of steps configured. If
this does not correspond to the number required by the specific model, proceed as follows:
change the type of valve on screen Eic02, selecting CAREL EXV;
select the desired valve again.
8
+030220735 - 1.0 - 19.05.2016
ENG
Notes
CAREL INDUSTRIES HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 049.9716611 - Fax (+39) 049.9716600
e-mail: [email protected] - www.carel.com
Agenzia / Agency:
+030220735 - 1.0 - 19.05.2016
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Carel pRack pR300 Manuale utente

Tipo
Manuale utente
Questo manuale è adatto anche per

in altre lingue