red lion IMP Manuale utente

Tipo
Manuale utente
THE APOLLO INTELLIGENT METER SERIES
MODEL IMP INSTRUCTION MANUAL
INTRODUCTION
The Intelligent Meter for Process Inputs (IMP) is another unit in our
multi-purpose series of industrial control products that is
field-programmable for solving various applications. This series of
products is built around the concept that the end user has the capability
to program different personalities and functions into the unit in order to
adapt to different indication and control requirements.
The Intelligent Process Meter, which you have purchased, has the
same high quality workmanship and advanced technological capabilities
that have made Red Lion Controls the leader in today's industrial
market.
Red Lion Controls has a complete line of industrial indication and
control equipment, and we look forward to being of service to you now
and in the future.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
CAUTION: Risk of electric shock.
Table of Contents
SAFETY INFORMATION ·······························································1
Safety Summary ···································································1
Definition Of Terms ·································································1
GENERAL DESCRIPTION······························································2
Theory Of Operation ································································2
Block Diagram ·····································································3
PROGRAMMING & OPERATING THE IMP················································4
Programming the IMP ·······························································4
Module #1 - Scale By Signal Level Method ·············································6
Module #2 - Scale By Key-In Method ··················································8
Module #3 - Program Functions Accessible W/ Front Panel Lockout ·······················10
Module #4 - Programming Digital Filter and Remote Input ································12
Module #5 - Program Totalizer/Integrator··············································14
Module #6 - Program Alarm/Setpoint ·················································15
Module #7 - Program Serial Communications ··········································17
Module #8 - Program Re-Transmitted Analog Output ····································18
Module #9 - Service Operations ·····················································19
Operating the IMP ·································································20
Quick Programming ·······························································20
Factory Configuration ······························································21
Programming Example ·····························································22
Pressure Monitoring Example ·······················································23
EXCITATION (Optional) ······························································24
TOTALIZER/LINEARIZER/PEAK/VALLEY/TARE (Optional) ································24
Totalizer ·········································································24
Totalizer Example ·································································24
Linearizer ········································································25
Peak/Valley ······································································27
Tare ············································································27
ALARMS (Optional) ·································································28
20 mA CURRENT LOOP SERIAL COMMUNICATIONS (Optional) ···························29
General Description ·······························································29
Communication Format ····························································29
-i-
Sending Commands to the IMP ·················································30
Receiving Data from the IMP···················································32
CURRENT LOOP INSTALLATION ·················································34
Wiring Connections ··························································34
Serial Terminal Descriptions ···················································34
Serial Communications Example ················································35
Process Controlling System ···················································35
RE-TRANSMITTED ANALOG OUTPUT (Optional) ····································36
Analog Output Calibration ····················································37
APPENDIX “A” - INSTALLATION & CONNECTIONS ·································38
Installation Environment ······················································38
Panel Installation ·························································38
Select AC Power (115/230 VAC) ················································38
EMC Installation Guidelines ···················································39
Wiring Connections ··························································40
Power Wiring ····························································40
User Input Wiring ·························································40
Output Wiring ······························································40
Relay Connections ··························································40
Signal Wiring ····························································41
APPENDIX “B” - SPECIFICATIONS AND DIMENSIONS ································42
APPENDIX “C” - TROUBLESHOOTING GUIDE ······································44
APPENDIX “D” - PROGRAMMABLE FUNCTIONS ····································45
APPENDIX “E” - USERS PROGRAMMING VALUES CHART ····························47
APPENDIX “F” - ORDERING INFORMATION ········································49
-ii-
SAFETY INFORMATION
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the IMP to directly command motors valves, or other actuators not
equipped with safeguards. To do so, can be potentially harmful to persons or
equipment in the event of a fault to the unit.
DEFINITION OF TERMS
INSTALLATION CATEGORY (overvoltage category) I:
Signal level, special equipment or parts of equipment, telecommunication,
electronic, etc. with smaller transient overvoltages than Installation Category
(overvoltage category) II.
INSTALLATION CATEGORY (overvoltage category) II:
Local level, appliances, portable equipment, etc. with smaller transient
overvoltages than Installation Category (overvoltage category) III.
-1-
GENERAL DESCRIPTION
The Apollo Intelligent Meter for Process Inputs (IMP) accepts standard
process signals and precisely scales them into engineering units with high
resolution. One model covers any current range within 0 to 50 mADC. A full
6-digit display accommodates nearly any engineering units and holds large
totalization values. State-of-the-art digital circuitry virtually eliminates errors
due to drift. A full complement of option packages is available to fulfill many
process applications.
The indicator features a choice of two different scaling procedures which
greatly simplify initial set-up. English-style display prompts and front panel
buttons aid the operator through set-up and operation. A front panel lock-out
menu protects set-up data and operation modes from unauthorized personnel.
Programmable digital filtering enhances the stability of the reading.
Programmable remote input “E1-CON” pin can be utilized to control a variety of
functions, such as totalizing, alarm control, display hold or tare operations. All
set-up data is stored in E
2
PROM, which will hold data for a minimum of 10 years
without power.
An optional integrator (totalizer)/linearizer can be used to totalize or integrate
signals up to a maximum display value of 999,999. It features independent
scaling and a low signal cut-out to suit a variety of signal integration applications.
Additionally, nine segments and offsets can easily be programmed with this
option to linearize transducers with non-linear outputs, such as square law
devices. Programmable remote input “E2-CON” pin is included with the option
and can be utilized to control a variety of functions, such as totalizing, alarm
control, display hold or tare operations, simultaneously with “E1-CON” pin.
Peak/valley (max/min) reading memory, and a signal re-zeroing (tare) function
are included with this option and they are easily recalled and controlled by either
the front panel or a remote input. All readings are retained at power-down.
Optional dual relays with parallel solid state outputs are fully programmable
to operate in a wide variety of modes to suit many control or alarm applications.
Optional 20 mA loop, bi-directional serial communications provides
computer and printer interfacing to extend the capabilities of the indicator. More
than one unit can be connected in the loop with other RLC products which have
serial communications capabilities.
An optional 4 to 20 mA or 0 to 10 VDC re-transmitted analog output can be
scaled by the user to interface with a host of recorders, indicators and controllers.
The type of analog output is determined by the model ordered. (See Ordering
Information for available models.) The indicator has several built-in diagnostic
functions to alert operators of most malfunctions. Extensive testing of noise
interference mechanisms and full burn-in make the indicator extremely reliable
in industrial environments. The die-cast front bezel meets NEMA 4/IP65
requirements for washdown applications, when properly installed. Plug-in style
terminal blocks simplify installation and wiring change-outs.
THEORY OF OPERATION
The IMP employs a microprocessor to perform the A/D conversion on the
input signal via a voltage-to-frequency converter. It digitally scales the result,
corrects for meter drift which may be present and then displays the result in a
6-digit display (5 for input, 6 for totalizer). The inputs are filtered to enhance the
stability of the display. A non-volatile E
2
PROM memory device provides
permanent data retention for operating variables. The display consists of drivers
and 6-digit solid-state LEDs. The alarm option employs opto-isolators to isolate
the open collector devices from meter common. Operating in parallel, the relays
are type Form-C and are rated at 5-amps. The serial communication option
features a built-in 20 mA current source and complete opto-isolation. The analog
option features a 12-bit DAC and provides an output signal that is digitally
scaled. The re-transmitted output is isolated from meter common.
-2-
-3-
Note: Analog, Serial, and SNK output options are isolated from the signal common at a working voltage of 50 V. The commons should NOT be tied together.
FIG. 1:
BLOCK DIAGRAM
PROGRAMMING & OPERATING THE IMP
PROGRAMMING THE IMP
Prior to installing and operating the indicator, it may be necessary to
change the scaling to suit the display units particular to the application.
Although the unit has been pre-programmed at the factory, the set-ups will
generally have to be changed.
The indicator is unique in that two different scaling methods are available.
The operator may choose the method that yields the easier and more accurate
calibration. The two scaling procedures are similar in that the operator
keys-in two display values and either keys-in or applies a signal value that
corresponds to those display points (see FIG. 2). The location of the scaling
points should be near the process end limits, for the best possible accuracy.
Once these values are programmed (coordinates on a graph), the indicator
calculates the slope and intercept of the signal/display graph automatically.
No span/zero interaction occurs, making scaling a one-pass exercise. Basic
scaling is complete after decimal point selection, unit rounding (dummy
zeros) and digital filtering level selection. The following procedure should be
followed to scale the indicator.
Before actually trying to program the indicator, it is advised to organize all
the data for the programming steps to avoid any possible confusion and to read
the programming procedure entirely before proceeding.
To set-up the indicator, connect AC power and signal wires as outlined in the
connections section (Appendix “A”). Remove the jumper wire (if installed) from
TBA #3 (PGM. DIS.). This will allow the operator to enter and modify all of the
indicator’s parameters. Press the front panel button labeled “P”, momentarily.
Briefly, the display will show “Pro” alternately flashing with “0”. This is the
indicator’s programming mode. The programming mode is divided into sections,
numbered 0-9, each of which can be individually accessed. The front panel “UP”
and “DOWN” arrow buttons can be used to select one of these numbers and the
“P” button used to enter the selected programming module. In all of the
programming modules, “UP” and “DOWN” are used to either select from a list
of choices or enter a value. The “P” button is used to save the new value and
progress to the next step within a module (Note: the new value takes effect when
“P” is pressed). Upon completion of a module, the indicator returns to the “Pro”
<>“0” stage. Pressing the “P” button at this point causes the unit to display
“End” after which the unit returns to the normal display mode. The following
table explains the basic function of each step.
Note: < > This indicates that the display will alternate between the English
prompt and the actual data.
-4-
FIG. 2: SLOPE DIAGRAM
DISPLAY RESULT OF “P” BUTTON
“Pro”<>“0 Causes the indicator to return to normal display mode. Any
changes to set-up data are permanently stored in the
E
2
PROM.
“Pro” <>“1”
Entry into this module allows the user to select the decimal
point position, unit rounding and scaling by the method of
applying the actual signal levels to the indicator that
correspond to the programmed display values. Use this
method when the transducer is connected to the process and
the process can be brought to known levels (ie. weight,
flow, pressure, etc.). Alternately, a precision signal source
may be substituted to simulate the transducer. A second
method is available in Pro 2.
“Pro” <>“2”
Entry into this module allows the user to select the decimal
point position and unit rounding, as in Pro 1, but the method
of scaling differs in that the user keys in signal levels instead
of applying signals to the indicator. Use this method when
the signal transducer is pre-calibrated with known display
values at known signal levels. An alternate method is
available in Pro 1.
“Pro” <>“3”
Module #3 allows the user to program what can be accessed
from the front panel when the PGM. DIS. (Program Disable,
TBA #3) pin is connected to common. This feature protects
critical set-up data from accidental modification while
allowing access to setpoints and other functions. The front
panel lock-out menu (quick programming) includes setpoint
modification, totalizer resetting, and peak/valley resetting.
Note: The term “Quick Programming” is used to refer to
the ability to change the information that can be
accessed from the front panel when the “PGM. DIS.”
terminal is connected to “COMM.”.
DISPLAY
RESULT OF “P” BUTTON
“Pro”<>“4 Module #4 programs the digital filtering level and the
function of the remote input ”E1-CON" pin (TBA #4), and,
if the totalizer option is installed, the remote input
“E2-CON” pin (TBA #8). The functions of the remote E1
and E2 pins are the same and include display hold, peak/
valley modes, totalizer reset, alarm reset, signal re-zero
(tare), reading synchronization or print request.
“Pro” <>“5”
This module sets the time base, scale factor and low signal
disable function for the optional totalizer/ integrator.
“Pro” <>“6”
This module allows programming for the basic
configuration of the alarm option. The programming
includes HI/LO acting, tracking, alarm display, latched or
auto-reset, assignment to either signal or
integrator/totalizer, and alarm and hysteresis values.
“Pro” <>“7”
Module #7 is the serial communication parameter
programming. Baud rate, unit address, print request
function and condensed prints are all programmable.
“Pro”<>“8
This module allows digital scaling of the retransmitted
analog output. Display values that correspond to 4 mA or 0
VDC and 20 mA or 10 VDC are keyed-in to scale the output
and it may be assigned to either the signal or the
totalizer/integrator.
“Pro”<>“9
This module is the service operations sequence and is not
normally accessed by the user. This step re-calibrates the
basic input and is used to compensate for long-term drift.
Execution of this module should be done by technicians
with the proper equipment in accordance with a
maintenance plan of yearly recalibrations. A code number
entry step is used to protect from inadvertent entries. Also,
there is a number of other access codes which provide test
and set-up changes as an aid in troubleshooting.
-5-
MODULE #1 - SCALE BY SIGNAL LEVEL METHOD
PROGRAM DECIMAL POINT POSITION
Select the desired decimal point position of the scaled display by pressing
either the “Up” or “Down” button.
Note: Whatever decimal point is selected will appear in succeeding
programming steps. Also, the “P” button must be pressed after each step to enter
the desired data and to proceed to the next step.
“ dECPNt”<>“0
“0.0”
“0.00”
“0.000”
“0.0000”
PROGRAM ROUNDING INCREMENT AND RIGHT HAND
DUMMY ZEROS
Rounding values other than one cause the scaled number to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes ‘122’ to round to
‘120’ and ‘123’ to round to ‘125’). If the process is inherently jittery, the display
value may be rounded to a higher value than one. If the range of the process
exceeds the required resolution, (ex. 0-10,000 PSI, but only 10 PSI resolution
required), a rounding increment of 10 will effectively make the display more
stable. This programming step is usually used in conjunction with programmable
digital filtering (Pro 4) to help stabilize display readings. (If display stability
appears to be a problem and the sacrifice in display resolution is unacceptable,
program higher levels of digital filtering or increase the level of process
dampening.) Rounding increments of 10, 20, 50, and 100 may also be used to add
“dummy zeros” to the scaled readings, as desired.
“round”< > “1”
“2”
“5”
“10”
“20”
“50”
“100”
At this stage a choice of either return to “Pro 0” or continue with scaling of the
display is offered.
“SCALE” < > “yES”
“NO”
If “yES” was selected for the previous step, the scaling procedure is started. In
order to scale the indicator, by either method, two signal level values and two
display values that correspond to the signal values must be known. These four
values are then used to complete the scaling operation. An example of a
signal-display pair is listed below:
3.000 PSI @ 4.000 mA AND 15.000 PSI @ 20.000 mA
Scaling point #1 Scaling point #2
Note that reverse acting indication can be accomplished by either reversing
the two signal points or the display value points, but not both. If both are reversed,
then forward (normal) acting indication will occur. In either case do not reverse
the input wires to correct the action because the indicator is designed for positive
signals only. With this scaling procedure, the display values are keyed in and
signal values are applied to the indicator by either a signal simulator or the actual
signal source.
KEY-IN DISPLAY VALUE FOR SCALING POINT #1
“ dSP 1” < > “-99999” to “99999” (ex. 3.000 PSI)
APPLY SIGNAL TO INDICATOR FOR SCALING POINT #1
The meter will indicate the actual amount of signal being applied to the input .
However, the indicator still retains the previously applied value until “P” is
pressed, at which time the new value is stored. Pressing either the “UP” or
“DOWN” button causes the previous value to remain programmed in the unit.
“INP 1” < > “0-50” (ex. 4.000)
KEY-IN DISPLAY VALUE FOR SCALING POINT #2
“dSP 2” < > “-99999” to “99999” (ex. 15.000 PSI)
-6-
APPLY SIGNAL TO INDICATOR FOR SCALING POINT #2
The meter will indicate the actual amount of signal being applied to the input.
However, the indicator still retains the previous value until “P” is pressed, at
which time the new value is stored. Pressing either the “UP” or “DOWN” button
causes the previous value to remain programmed in the unit.
“INP 2” < > “0-50” (ex. 20.000)
At this stage, scaling is complete. The indicator will automatically calculate
the slope and offset of the display units after completing “Pro 1”.Itis
recommended that the scaling operation be verified by applying various signals
and checking the displayed reading.
If the totalizer/linearizer option is installed, the indicator, instead of
completing Module #1 and returning to “Pro 0”, will be ready to accept more
scaling points for multisegment linearization. The quantity and location of the
linearization points should be chosen very carefully to best utilize the segments
available. Refer to the section on linearization for a discussion on this matter.
PROGRAM NUMBER OF LINEAR SEGMENTS
This programming step loads in the number of linear segments desired for
multisegment linearization. If just single slope scaling is all that is desired, input
“1” for this step. If two segments are desired input “2”, etc. You must have one
more scaling point known than the number of segments selected (ie. 1 segment = 2
points, 2 segments = 3 points, etc). This step may be used to de-activate previously
programmed segments where lower segments would override (ex. changing
“SEGt” from 5 to 3 causes slopes4&5tobereplaced by an extension of slope 3).
“SEGt” < > “1” - “9”
If “1” was selected, the indicator will return to “Pro 0” since scaling for the
first segment was already completed. Otherwise, a choice of either returning to
“Pro 0” or commencing with the multislope-linearization scaling is offered.
“SCALE” < > “yES”
“NO”
KEY-IN DISPLAY VALUE FOR POINT #3
If “YES” was selected, the display value for the third point is entered.
Otherwise, the indicator returns to “Pro 0”.
“dSP 3” < > “-99999” to “99999”
APPLY SIGNAL TO INDICATOR FOR POINT #3
The signal level value for point 3 is applied.
“INP 3” < > “0-50”
The sequence of entering display and signal values continues with “dSP 4”
“INP 4”, “dSP 5”, etc. until the number programmed for “SEGt” is reached.
Upon completion, the indicator is scaled to the multiple segments. It is
recommended that the scaling be checked by applying signal values and
verifying for correct display values.
Note: As the “UP” or “DOWN” button is continually held in, the display will
progressively increment faster until the fourth most significant digit is
changing at a rate of 1 number per second.
-7-
MODULE #2 - SCALE BY KEY-IN METHOD
PROGRAM DECIMAL POINT POSITION
Select the desired decimal point position of the scaled display by pressing
either the “Up” or “Down” button.
Note: Whatever decimal point is selected will appear in succeeding
programming steps. Also, the “P” button must be pressed after each step to enter
the desired data and to proceed to the next step.
“ dECPNt”<>“0
“0.0”
“0.00”
“0.000”
“0.0000”
PROGRAM ROUNDING INCREMENT AND RIGHT HAND
DUMMY ZEROS
Rounding values other than one cause the scaled number to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes ‘122’ to round to
‘120’ and ‘123’ to round to ‘125’). If the process is inherently jittery, the display
value may be rounded to a higher value than one. This will allow the display to be
easier to read. If the range of the process exceeds the required resolution, (ex.
0-10,000 PSI, but only 10 PSI resolution required), a rounding increment of 10 will
effectively make the display more stable. This programming step is usually used in
conjunction with programmable digital filtering (Pro 4) to help stabilize display
readings. (If display stability appears to be a problem and the sacrifice in display
resolution is unacceptable, program higher levels of digital filtering or increase
the level of process dampening.) Rounding increments of 10, 20, 50, and, 100 may
also be used to add “dummy zeros” to the scaled readings, as desired.
“round”< > “1”
“2”
“5”
“10”
“20”
“50”
“100”
At this stage a choice of either return to “Pro 0” or continue with scaling of the
display is offered.
“SCALE” < > “yES”
“NO”
If “YES” was selected for the previous step, the scaling procedure is started. In
order to scale the indicator, two signal level values and two display values that
correspond to the signal values must be known. These four values are directly
entered into the indicator. An example of a signal-display pair is listed below:
3.000 PSI @ 4.000 mA AND 15.000 PSI @ 20.000 mA
Scaling point #1 Scaling point #2
Note that reverse acting indication can be accomplished by either reversing
the two signal points or the display value points, but not both. If both are reversed,
then forward (normal) acting indication will occur. In either case, do not reverse
the input signal wires because the indicator was designed to accept positive
signals only. With this scaling procedure, both the display values and signal
values are keyed in.
KEY-IN DISPLAY VALUE FOR SCALING POINT #1
“dSP 1” < > “-99999” to “99999” (ex. 3.000 PSI)
KEY-IN SIGNAL VALUE FOR SCALING POINT #1
“INP 1” < > “0-50” (ex. 4.000)
KEY-IN DISPLAY VALUE FOR SCALING POINT #2
“dSP 2” < > “-99999” to “99999” (ex. 15.000 PSI)
-8-
KEY-IN SIGNAL VALUE FOR SCALING POINT #2
“INP 2” < > “0-50” (ex. 20.000)
At this point, scaling is complete. The indicator will automatically calculate the
slope and offset of the display units. It is recommended that the scaling operation
be verified by applying various signals and checking the displayed reading.
If the totalizer/linearizer option is installed, the indicator, instead of
completing module #1 and returning to “Pro 0”, will be ready to accept more
scaling points for multisegment linearization. The quantity and location of the
linearization points should be chosen very carefully to best utilize the segments
available. Refer to the section on linearization for a discussion on this matter.
PROGRAM NUMBER OF LINEAR SEGMENTS
This programming step loads in the number of linear segments desired for
multisegment linearization. If just single slope scaling is all that is desired,
program “1” for this step. If two segments are desired, program “2”, etc. You
must have one more scaling point known than the number of segments selected
(ie. 1 segment = 2 points, 2 segments = 3 points, etc). This step may also be used
to de-activate previously programmed segments where lower segments would
override (ex. changing “SEGt” from 5 to 3 causes slopes 4 and 5 to be replaced
by an extension of slope 3).
“SEGt”<>“1”-“9
If “1” was selected, the indicator will return to “Pro 0” since scaling for the
first slope was already completed. Otherwise, a choice of either returning to “Pro
0” or commencing with the multislope-linearization scaling is offered.
“SCALE” < > “yES”
“NO”
If “yes” was selected, the display value for the third point is entered.
Otherwise, the indicator returns to “Pro 0”.
KEY-IN DISPLAY VALUE FOR SCALING POINT #3
“dSP 3” < > “-99999” to “99999”
KEY-IN INPUT VALUE FOR SCALING POINT #3
“INP 3” < > “0-50”
The sequence of entering display and signal values continues with “dSP 4”
“INP 4”, “dSP 5”, etc. until the number programmed for “SEGt” is reached.
Upon completion, the indicator is scaled to the multiple segments. It is
recommended that the scaling be checked by exiting the programming mode and
applying signal values and verifying for correct display values.
Note: As the “UP” or “DOWN” button is continually held in, the display will
progressively increment faster until the fourth most significant digit is
changing at a rate of 1 number per second.
-9-
MODULE #3 - PROGRAM FUNCTIONS ACCESSIBLE W/ FRONT PANEL LOCKOUT
This programming module programs what is accessible through the front
panel when the PGM. DIS. pin is connected to common (COMM.).
Note: The term “Quick Programming” is used to refer to the ability to change the
information that can be accessed from the front panel when the “PGM. DIS.”
terminal is connected to “COMM.”.
DISPLAY ALARM VALUES
If the alarm option is installed, this selects whether the alarm values will or
will not be displayed.
“dSP AL” < > “yES” or “NO”
ENTER ALARM VALUES =
If “YES” was selected for display alarm values, this will select if alarm values
may be modified from the front panel. If “NO” was selected for display alarm
values, then this step will default to “NO” and will not be displayed for selection.
“ENt AL” < > “yES” or “NO”
DISPLAY HYSTERESIS VALUES =
If the alarm option is installed, this selects whether the hysteresis values will or
will not be displayed.
“dSPHYS” < > “yES” or “NO”
ENTER HYSTERESIS VALUES =
If “YES” was selected for display hysteresis values, this selects whether
hysteresis values may be modified from the front panel. If “NO” was selected for
display hysteresis values, then this step will default to “NO” and will not be
displayed for selection.
“ENtHYS” < > “yES” or “NO”
= Note: This sequence may be locked-out due to other programmed sequences.
RESET LATCHED ALARMS
If the alarm option is installed and if either alarm is programmed to latch, this
will select if a latched alarm(s) can be reset from the front panel.
“rSt AL” < > “yES” or “NO”
DISPLAY PEAK/VALLEY MEMORY BUFFER
If the totalizer/linearizer option is installed, this selects whether peak and
valley buffers will be displayed.
“dSPbUF” < > “yES” or “NO”
RESET PEAK/VALLEY MEMORY BUFFER =
If “YES” was selected for the previous step, this selects whether the peak and
valley buffers may be reset from the front panel. If “NO” was selected, then this
step defaults to “NO” and will not be displayed for selection.
“rStbUF” < > “yES” or “NO”
SELECT DISPLAY *
If the totalizer/linearizer option is installed, this selects whether the display can be
switched from input display to total display and from total display to input display.
Note: When “NO” is selected, whatever display (Input or total) is shown, will be
the only display accessible.
“SELdSP” < > “yES” or “NO”
RESET TOTAL *
If the totalizer/linearizer option is installed, this selects whether the total can
be reset from the front panel.
“rSttOt” < > “yES” or “NO”
*Note: This function operates independent of the state of the “PGM. DIS.” Pin.
-10-
RE-ZERO INPUT *
If the totalizer/linearizer option is installed, this selects whether the signal can
be re-zeroed (tared) through the front panel.
“tArE” < > “yES” or “NO”
Note: The tare buffer can be cleared by “stepping” through “Pro 2”, using the P
button or via serial transmission.
Depending on functions selected under Pro 3 and Pro 6, alarms, hysteresis, peak,
and valley values can be monitored and/or changed when PGM. DIS. is tied to
COMM. This provides a “QUICK PROGRAMMING” method for “day to day”
process changes. (See QUICK PROGRAMMING SECTION for more details.)
*Note: This function operates independent of the state of the “PGM. DIS.” Pin.
-11-
MODULE #4 - PROGRAMMING DIGITAL FILTER AND REMOTE INPUT
PROGRAM DIGITAL FILTERING
If the displayed process signal is difficult to read due to small process
variations or noise, increased levels of filtering will help to stabilize the display.
This programming step may be used in conjunction with display rounding
programming (Pro1&2)to help minimize this effect. The digital filter used is an
“adaptive” filter. That is, the filter coeffecients change dynamically according to
the nature of the input signal. This feature simultaneously allows the filter to
settle quickly for large input changes while providing a stable display reading for
normal process variations. Because of the adaptive nature of the filter, it cannot
be characterized in terms of a time constant. The following table lists the
maximum settling time for a step input to within 99% of the final value.
Filter Value Settling Time (99%)
“FILtEr” < > “0” - no digital filtering 1.5 sec.
“1” - normal filtering 2 sec.
“2” - increased filtering 6 sec.
“3”
- maximum filtering 13 sec.
PROGRAM FUNCTION OF E1-CON &
OPTIONAL E2-CON PIN
The functions of the remote input “E1-CON” pin (TBA #4) and, if the totalizer
option is installed, the remote input “E2-CON” pin (TBA #8) are the same.
Functions are activated, as described in the appropriate function, when
connected to signal common (TBA #5). Whether a function is edge or level
activated, it must be held low for a minimum of 20 msec in order for the function
to occur. The remote input pins can be used simultaneously and with any
combination of functions. When the pins are tied together and activated,
E1-CON function is generally performed first.
“E1-CON” < > “0” - A negative going edge re-zeros (tares) the input signal.
Note: The tare buffer can be cleared by “stepping”
through “Pro 2”, using the P button or via serial
transmission.
“1” - A negative going edge resets the contents of the totalizer
to zero. Totalization commences regardless of the state
of the input.
“2” - A negative going edge resets the contents of the totalizer
to zero and allows totalization as long as the input is low.
If the input goes high, totalization is stopped and the
contents are saved. This acts as a totalization enable
control from time T1 to T2.
“3” - A low level allows totalization as long as the input is low.
If the input goes high, totalization is stopped and the
contents are saved. This acts as a totalization enable
control from time T1 to T2.
“4” - A low level holds the display (display hold). While this
input is low, the indicator continues to process the input
signal and drive the alarms, totalizer, etc. with the actual
signal. The contents of the totalizer are stored at the same
time the input display is held.
Note: If display hold is activated and input value is
requested via serial, the value on the display will be
sent instead of the actual input value at that time.
“5” - A negative going edge resets both peak and valley buffers.
Note: After P/V is called up, a change will not appear on
the display until the next time the P/V is called up.
“6” - A negative going edge resets only the peak buffer and
the indicator enters a peak reading display mode as
long as the input is low. If the input goes high, peak
detection and indication are stopped and the last peak
reading is retained.
“7” - A negative going edge resets only the valley buffer and
the indicator enters a valley reading display mode as
long as the input is low. If the input goes high, valley
detection and indication are stopped and the last valley
reading is retained.
-12-
“8” - If the alarm option is installed, a negative going edge
resets the latched alarm(s).
“9” - If the alarm option is installed, a low level resets a
latched or unlatched alarm into its inactive state. This
provides manual override of alarms for system startup
and other unusual events such as system testing.
“10” - A negative going edge toggles the display between
“input” and “total” (from input to total, or vice versa).
No action is taken on the positive going edge.
“11” - A negative going edge zeros (tares)
the input signal and
adds the value that was on the input display to the
totalizer value. The time-base, scale factor and low
signal cut-out in “Module #5” are in effect disabled,
when this function is selected. Example: 25.0 pounds of
one ingredient is loaded, input is tared to 0.0, totalizer =
25.0 pounds. 50.0 pounds of another ingredient are
loaded, input is tared to 0.0, totalizer = 75.0 pounds. This
acts as a batch totalization.
“12” - Display hold with tare. A negative going edge tares
(zeros) the input signal. Prior to the tare operation, the
input signal is saved and held (display hold) as long as
the remote input pin is low. On the positive edge the
input display will show zero. If there is a change to the
input signal while the remote input is low, the display
will reflect (show) the change at the positive edge.
“13” - Instrument reading synchronization. A low level
disables all meter operations (alarms, total, analog out,
etc.). A positive edge resets the start of the A/D
conversion, to allow synchronization with external
processes and controls. While this function is active, the
other E-CON pin will be acknowledged.
“14” - Print request. Transmits data according to the print options
that have been selected in Program Module #7. If the low
time exceeds 800 msec, a second print-out will occur.
“E2-CON” < > If the totalizer option is installed, E2-CON has the same
programmable functions as E1-CON.
-13-
MODULE #5 - PROGRAM TOTALIZER/INTEGRATOR
Programming for the totalizer/integrator consists of four programming steps:
totalizer decimal point position, time base, scale factor and low signal disable.
Note that the decimal point position of the totalizer can be independent of the
decimal point position of the scaled input signal. The totalizer value will roll over
and flash when the total exceeds, 999999 or -99999, indicating an overflow
condition. Reverse signal input will cause the totalizer value to count in the
opposite direction and eventually no longer be in an overflow condition.
PROGRAM DECIMAL POINT POSITION FOR THE TOTALIZER
The decimal point position for the totalizer are as follows:
“dECPNt” < > “0”
“0.0”
“0.00”
“0.000”
“0.0000”
PROGRAM TOTALIZER/INTEGRATOR TIME BASE
The time base determines the rate at which readings increase. The totalizer
display is updated 2 1/2 times per second regardless of time base selected, but
longer time bases decrease the magnitude of each increase. The three time bases
are per second, per minute and per hour. A constant signal input of 1000 units, for
example, would totalize to 1000 units in one second (with a TB of 1 sec.), 1000
units in one minute (with a TB of 1 min.), and 1000 units in one hour (with a TB of
1 hr.). (Note: Input changes can be made synchronous to the display by
programming E1 or optional E2-CON pin for function 13, Instrument reading
synchronization.) A multiplying scale factor may be used to span the standard
time ranges (or divide if scale factor < 1). The following equation expresses the
totalization process.
S. F.
D. T.
I. D.
T. B.
TIME
D. T. D. P.
I. D. D. P.
´
S.F. = Programmable Scale Factor
D.T. = Desired Totalizer value for a
fixed time duration
T.B. = Programmable Time Base
TB = If Program Select Number Chosen Is:
Enter in Formula
“0” for sec. 1
“1” for min. 60
“2” for hr. 3600
I.D. = Input Display Value
TIME = Actual Time period in seconds
D.T.D.P. = Desired Totalizer Decimal Point
Enter in Formula
01
0.0 10
0.00 100
0.000 1000
0.0000 10000
I.D.D.P. = Input Display Value Decimal Point
Enter in Formula
01
0.0 10
0.00 100
0.000 1000
0.0000 10000
“tbASE” < > “0” - per second
“1” - per minute
“2” - per hour
PROGRAM THE TOTALIZER SCALE FACTOR
As explained in the previous programming step, a multiplying scale factor can
be used to scale the update rate as required. This may be used to span the standard
ranges. A scale factor of “1.000” has no effect on the standard ranges.
“SCLFAC” < > “0.001” to “100.000”
PROGRAM THE LOW-END CUTOUT (low signal level disable)
In order to prevent false totalization during system startup or other low process
situations where totalization is undesirable, a programmable setpoint can be used
to disable totalization when the scaled input signal falls below this low-end
cutout level.
“Lo-cut” < > “-99999” to “999999”
-14-
MODULE #6 - PROGRAM ALARM/SETPOINT
If the alarm option is installed, this module is used to configure the operation
of the alarms to a variety of combinations. The programmable options are HI/LO
acting, auto/manual reset (latching), tracking, assignment to signal or totalizer,
display alarms, alarm values and hysteresis (deadband) values.
ALARM TRACKING
With alarm tracking, whenever alarm #2 is changed, alarm #1 will also change
so that the offset between alarm #2 and alarm #1 remains the same. This is useful
for hierarchical setpoints (pre-alarm and alarm) when one change applies to both
alarm values. When programming from the front panel, tracking only occurs
when PGM. DIS. is low (front panel lock-out mode, alarm #1 will not appear).
Tracking will always occur if alarm #2 is modified via serial communications
independent of PGM. DIS.
“trAc” < > “yES” or “NO”
DISPLAY ALARMS
If display alarms are desired, a message will flash on the display every 5-10
secs when an alarm activates. For alarm 1 the message will flash “AL1 on” and
alarm 2 will flash “AL2 on”, this warns an operator of an alarm condition. The
message will stop when the unit is no longer in an alarm condition.
“dISP” < > “yES” or “NO”
AUTO OR MANUAL RESET FOR ALARM #1
The reset action of alarm #1 may be programmed to reset automatically
(unlatched) or be programmed to require a manual reset (latched), through either
a remote input (E1-CON or optional E2-CON) or through the front panel.
Latched alarms are usually used when an operator is required to take some action
for the alarm condition.
“LAtC-1” < > “yES” or “NO”
ALARM #1 ASSIGNMENT TO INPUT SIGNAL OR TOTALIZER
Alarm #1 may be programmed to activate on either the input signal or the
totalizer value. If the totalizer option is not installed, this step defaults to the input.
“ASN-1” < > “INPUt” or “totAL”
PROGRAM VALUE FOR ALARM #1
The range of the alarm value is -99,999 to 999,999.
“AL-1” < > “-99999” to “999999”
PROGRAM HYSTERESIS VALUE FOR ALARM #1 (Cannot be
programmed if alarm latch is programmed)
The hysteresis (deadband) value for alarm #1 may be programmed from 1 to
99,999. The value is either added to or subtracted from the alarm value depending
on whether the alarm is high or low acting. (See “alarms” section for operation.)
“HyS-1” < > “1” to “999999”
ALARM #1 HIGH OR LOW ACTING
The action of alarm #1 may be programmed to activate either when the signal
goes above the alarm value (high acting) or goes below it (low acting).
“Act-1” < > “HI” or “LO”
AUTO OR MANUAL RESET FOR ALARM #2
The reset action of alarm #2 may be programmed to reset automatically
(unlatched) or be programmed to require a manual reset (latched), through either
a remote input (E1-CON or optional E2-CON) or through the front panel.
Latched alarms are usually used when an operator is required to take some action
for the alarm condition.
“LAtC-2” < > “yES” or “NO”
ALARM #2 ASSIGNMENT TO INPUT SIGNAL OR TOTALIZER
Alarm #2 may be programmed to activate on either the input signal or the
totalizer value. If the totalizer option is not installed, this step defaults to the input.
“ASN-2” < > “INPUt” or “totAL”
-15-
PROGRAM VALUE FOR ALARM #2
The range of the alarm value is -99,999 to 999,999.
“AL-2” < > “-99999” to “999999”
PROGRAM HYSTERESIS VALUE FOR ALARM #2 (Cannot be
programmed if alarm latch is programmed)
The hysteresis (deadband) value for alarm #2 may be programmed from 1 to
999,999. The value is either added to or subtracted from the alarm value depending
on whether the alarm is high or low acting. (See “alarms” section for operation.)
“HyS-2” < > “1” to “999999”
ALARM #2 HIGH OR LOW ACTING
The action of alarm #2 may be programmed to activate either when the signal
goes above the alarm value (high acting) or goes below it (low acting).
“Act-2” < > “HI” or “LO”
Note: Depending on options selected under Pro 3 and Pro 6, alarms, hysteresis,
peak, and valley values can be monitored and/or changed when PGM. DIS.
is tied to COMM. This provides a “QUICK PROGRAMMING” method for
“day to day” process changes. (See QUICK PROGRAMMING SECTION
for more details.)
-16-
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55

red lion IMP Manuale utente

Tipo
Manuale utente

in altre lingue