Giacomini R298 Istruzioni per l'uso

Tipo
Istruzioni per l'uso
Pos. Kv Qp Qbp
Fully close 3,25 0 % 100 %
0,5 mm 3,48 11 % 89 %
1 mm 3,79 18 % 82 %
2 mm 3,78 29 % 71 %
3 mm 3,12 44 % 56 %
4 mm 2,35 74 % 26 %
Fully open 1,78 100 % 0 %
Perdite di carico - Chute de pression - Pressur losses - Druckabfall
047U23268 03/2023
R298
ValVola miscelatrice tre Vie a Vitone
Vanne mélangeuse à troie Voie à piston
three way mixing ValVe with bonnet
3-wege-mischVentil mit handregulierkappe
Additional information
For additional information please check the website www.giacomini.com or contact the technical service:
' +39 0322 923372 6 +39 0322 923255 * [email protected]
This pamphlet is merely for information purposes. Giacomini S.p.A. retains the right to make modications for technical or commercial reasons,
without prior notice, to the items described in this pamphlet. The information described in this technical pamphlet does not exempt the user
from following carefully the existing regulations and norms on good workmanship.
Giacomini S.p.A. Via per Alzo, 39 - 28017 San Maurizio d’Opaglio (NO) Italy
La valvola miscelatrice a tre vie R298 trova impiego nell'impiantistica civile per la realizzazione di impianti di medie dimensioni ove sia richiesto un
controllo preciso della temperatura di mandata dell’acqua per mezzo di regolatori compensati od a punto sso. Viene di norma montata sui gruppi
universali serie R586, senza comunque escludere qualsiasi altro modo di impiego. La stessa valvola può essere utilizzata anche in impianti radianti
a pavimento o sotto nei quali sia prevista l’installazione di caldaie a condensazione impostate a bassa temperatura (55 –60°C) grazie alle quali la
dierenza tra la temperatura del primario e quella del secondario può essere contenuta.
Dati tecnici
Temperatura massima di esercizio 90°C
Pressione massima di esercizio 10 bar
Pressione dierenziale massima 1,2 bar
Miscelazione mediante vitone DN20 normalmente aperto sulla via di by-pass
Corsa otturatore 5 mm
Volantino con funzioni di protezione e manovra manuale
Utilizzabile per acqua usi riscaldamento e climatizzazione
Corpo, vitone e calotte in ottone UNI-EN12165 CW617N
Anelli di tenuta in EPDM
Attacchi a sede piana da 1-1/2”
Installazione
La valvola miscelatrice tre vie a vitone R298 deve essere installata seguendo le direzioni di usso indicate con una freccia impressa sul corpo.
Il circolatore del circuito secondario deve essere montato a valle della miscelatrice. Sono consentiti montaggi in verticale con motore posizionato
a destra o sinistra ed orizzontali con motore posizionato superiormente. Il montaggio orizzontale della valvola rivolta in basso non è permesso
perché eventuali condense in impianti rarescanti potrebbero inltrarsi nel motore con conseguenti problematiche elettriche di funzionamento.
Installazione dell’attuatore
La R298 è dotata di volantino per manovre manuali eettuabili con semplice rotazione oraria per l’apertura ed antioraria per la chiusura. L’apertura
totale del vitone e quindi della via di alimentazione primaria si ottiene avvitando a fondo il volantino mentre lo svitamento totale consente di
liberare la lettatura per il collegamento del motore di azionamento.
L’installazione dell’attuatore K281 viene eettuato avvitando manualmente, senza l’ausilio di attrezzi, la ghiera folle in ottone in senso orario sino a
battuta. Nel caso in cui si alimenti l’attuatore prima dell’installazione sulla miscelatrice è opportuno riportarlo allo stato iniziale (corrispondente a
valvola chiusa sulla via di alimentazione) in modo da poterlo installare senza dicoltà.
Alimentazione a bassa temperatura
Qualora si preveda la realizzazione di impianti nei quali il primario sia caratterizzato da bassa temperatura (es. caldaie a condensazione operanti a bassa
temperatura) sulla via di by-pass deve essere inserito il diaframma calibrato (A). In queste tipologie di applicazione la presenza di questo elemento
è fondamentale per il corretto equilibrio delle portate dei circuiti primario e secondario caratterizzate da una ridotta dierenza di temperatura.
AA
Performance idrauliche
Nella tabella riportata in seguito vengono forniti i valori di Kv e i rapporti percentuali di miscelazione (fra le portate di by-pass e del primario)
corrispondenti alle varie posizioni di apertura.
R298 Valvola miscelatrice tre vie a vitone
La vanne R298 est particulièrement recommandée pour la réalisation de chauage par le sol ou plafond de dimensions moyennes où il est
demandé un contrôle précis de la température de départ d’eau. Elle se monte sur le DUC R586 en liaison avec le K281 et la centrale GIACOKLIMA
ou des régulations avec les mêmes caractéristiques.
Données techniques
Température maximum d’exercice: 90°C
Pression maximum d’exercice: 10 bar
Pression diérentielle maximum: 1,2 bar
Mélange grâce au piston DN20 normalement ouvert sur la voie du bypass
Course d’ouverture/fermeture 5 mm
Volant avec fonction de protection et manœuvre manuelle
Utilisable pour l’Eau Chaude Sanitaire, le chauage et la climatisation
Corps et axe en laiton matricé à chaud UNI-EN12165 CW617N
Joint en EPDM
Raccordement en 1-1/2”
Montage
La R298 doit être installée en suivant la direction du ux indiqué par une èche sur le corps. La pompe du circuit secondaire doit être montée en
aval de la vanne de mélange. Il est possible de faire un montage vertical avec le moteur positionné à droite ou gauche et horizontal avec le moteur
au-dessus. Le montage horizontal de la vanne retournée en bas est déconseillé car il peut y avoir de la condensation dans le cas de rafraîchissement
et cela risquerait de créer des dommages électriques.
Motorisation
La R298 est pourvue d’un volant pour des manœuvres manuelles, en le tournant dans le sens des aiguilles d’une montre pour l’ouverture et l’inverse
pour la fermeture. Louverture totale du vitone donc de la voie d’alimentation primaire s’obtient en vissant à fond le volant alors que le dévissage
total permet de libérer le let pour la motorisation. Le montage du moteur K281 est eectué en vissant manuellement l’embout en laiton dans
le sens des éguilles d’une montre à fond. Dans le cas ou on alimente le moteur avant de le monter sur la vanne de mélange il est opportun de le
ramener à l’état initial (correspondant à la vanne fermée sur la voie d’alimentation) de manière pouvoir le monter sans problème.
Chaudiere fonctionnant à basse température
Quand la production de chaleur est preveu pour fonctionner à basse température (par exemple avec una chauderie à condensation) il faut insérer
sur la voie de by-pass le diaphragme calibré. Dans ce type d’installation la prèsence de cediaphragme est indispensable pour un assurer un bon
équilibre des débits primaire et secondaire caractèrisès par une faible dièrence de tempèrature.
AA
Caractéristiques hydrauliques
Le tableau suivant donne le Kv de la vanne et le pourcentage de mélange (entre le débit du by pass et le primaire) correspondant au diérentes
positions de la vanne.
R298 Vanne mélangeuse à troie voie à piston
Dimensioni - Dimensions - Dimensions - Größe
The R298 three way mixing valve is used for the construction of radiant oor or ceiling systems of medium dimensions, where precise control of
the water ow temperature is required. Normally it is installed on the R586 Universal Boiler Manifold Set and it is combined with the motor K281
and the GIACOKLIMA regulator, though many other applications are possible.
Technical Data
Max. working temperature: 90 °C
Max. working pressure: 10 bar
Max. dierential pressure: 1,2 bar
Mixing achieved by a DN20 normally open bonnet valve on the by-pass port
Shutter lift 5 mm
Handwheel with protection functions and manual operation
To be used with water for heating and cooling applications
Body, bonnet and nuts made of hot pressed brass UNI-EN12165 CW617N
Sealing rings in EPDM
1-1/2” Flat seat connections
Installation
The R298 must be installed according to the ow directions indicated by an arrow stamped on the body.
The circulator of the secondary circuit must be installed downstream of the mixing valve. Vertical installation with the motor installed on the left
or on the right is permitted and the horizontal installation with the motor positioned above the valve is also permitted. Horizontal installation with
the motor positioned below the valve is not recommended as condensation on the valve, when used in cooling systems, might penetrate into
the motor thus causing an electrical malfunction.
Actuator installation
The R298 is supplied with a handwheel to allow manual operation which is carried out by a simple clockwise rotation for opening and an
anticlockwise rotation for closing. Complete opening of the bonnet, and consequently of the primary supply port, is achieved by turning the hand-
wheel fully clockwise. Removal of the hand-wheel by complete unscrewing in an anticlockwise direction exposes the thread for the attachment
of the actuator motor. The assembly of the K281 motor is carried out by tightening the brass retaining collar in a clockwise direction. If you supply
the motor before the assembly on the mixing valve, it is opportune to bring it back to the initial situation (corresponding to the closed valve on
the supply way) so as to install it without fault.
Supply at low temperature
Should you expect the realization of installations where the primary circuit is characterised by low temperature (i.e. condensig boilers operating at
low temperature) on the by-pass way the calibrated diaphragm shall be inserted. In these applications, the presence of this element is fundamental
for the correct balance of the deliveries of the primary and secondary circuits, characterised by a reduced temperature dirence.
AA
Hydraulic performances
In the table below you nd Kv values and mixing percentage ratio (between by-pass delivery and delivery of the primary circuit) corresponding
to the dierent opening position.
R298 Three way mixing valve with bonnet
Das Mischventil R298 wird bei Fußboden- und Deckensystemen zur Heizung und Kühlung in Anlagen mittlerer Größe verwendet, wo eine genaue
Temperaturüberwachung des Wasservolumenstromes gefordert wird. Üblicherweise wird das Mischventil in Verbindung mit einer Universalkesselgruppe
R586, dem GIACOKLIMA-Regler und dem passenden Mischermotor K281 eingesetzt; aber auch andere Anwendungen sind möglich.
Technischen Daten
Max. Betriebstemperatur: 90 °C
Max. Betriebsdruck: 10 bar
Max. Dierenzdruck: 1,2 bar
Mischer arbeitet mit DN20 Kolbenventil, Bypass normal oen
Ventilhub 5 mm
Handregulierkappe für Schutzfunktion und Handbetrieb
Medien: Wasser für Heiz- und Kühlsysteme
Gehäuse, Kolben und Muttern aus warmgepresstem Messing CuZn40Pb2 UNI-EN12165 CW617N
Dichtungen aus EPDM
Anschlüsse 1-1/2” achdichten
Montage
Das Mischventil R298 muss so montiert werden, dass die Durchussrichtung mit der auf dem Gehäuse eingeprägten Pfeilrichtung übereinstimmt.
Es ist auf der Saugseite und damit vor der Umwälzpumpe des Sekundärkreises einzubauen. Eine vertikale Installation mit dem Motor auf der rechten
oder linken Seite und auch eine horizontale Installation mit dem Motor oberhalb des Ventils ist möglich. Aus Sicherheitstechnischen Gründen ist
eine horizontale Installation, bei der der Motor unterhalb des Mischers angeordnet ist, nicht erlaubt, da z.B. im Kühlbetrieb Kondenswasser in den
Motor eindringen und einen Kurzschluss verursachen könnte.
Motorisierung
Das Mischventil R298 ist werkseitig mit einer Handregulierkappe ausgerüstet, um den Handbetrieb zu ermöglichen; eine Drehung im Uhrzeigersinn
önet und im Gegenuhrzeigersinn schließt den Mischervorlauf (Primärvorlauf ). Wird die Handregulierkappe bis zum Anschlag im Uhrzeigersinn
gedreht, ist der Mischervorlauf ganz geönet. Bei entgegengesetzter Drehung kann die Handregulierkappe abgeschraubt werden und das
Befestigungsgewinde für den Mischermotor wird sichtbar. Die Befestigung des Motors K281 erfolgt von Hand ohne zusätzliches Werkzeug. Der
Motor wird durch Drehung der Überwurfmutter im Uhrzeigersinn am Ventil befestigt. Weitere Wenn der Motor vor der Montage des Mischventils
eingeschaltet wird, sollte dieser wieder in die Ausgangs-stellung gebracht werden (entsprechend dem geschlossenen Ventil in Durchussrichtung),
um eine einwandfreie Montage sicherzustellen.
Heizekreislauf bei niedriger temperatur
Bei Anwendungsfallen, in denen der primar-Heizkreislauf eine niedrige temperatur im by-pass aufweist (typisches beispiel: heizkessel, die bei
niedriger temperatur im kondensantbereich arbeitem), ist die drosselscheibe einzusetzen. Bei derantigen anwendungsfallen muss die drosselscheibe
umbedingt eingesetzt werden, um eine ausgewogene versorgung ber primar- und sekundar - heizkreize, die nur eine geringe temperaturdierenz
aufweisen, zu gewahrleisten.
AA
Hydraulik-Funktionen
Die folgende tabelle Dort nden Sie die Kv-Werte und das prozentuale Mischverhältnis zwischen By-pass und Primär-Heizkreislauf, je nach Position
des Mischers.
R298 3-Wege-Mischventil mit Handregulierkappe
G
A
L
I
B B
G
KK
J
J
D
E
F
Product code G B A [mm] I [mm] L [mm] D [mm] E [mm] F [mm] K [mm] J [mm]
R298Y027 G 1-1/2”M G 1-1/2”F 59 120 209 28 50 104 41 53
M
N
Product code M [mm] N [mm]
K298Y027 + K281X002 113 255
K298Y027 + K281X012 115 265
  • Page 1 1
  • Page 2 2

Giacomini R298 Istruzioni per l'uso

Tipo
Istruzioni per l'uso