Eaton EX RT 11 3:1 Installation and User Manual

Categoria
Gruppi di continuità (UPS)
Tipo
Installation and User Manual

Questo manuale è adatto anche per

www.eaton.com
Installation and user
manual
EX RT 5 3:1
EX RT 7 3:1
EX RT 11 3:1
English
Français
Deutsch
Italiano
Español
Nederlands
3400772400/AD
www.eaton.com
Installation and user
manual
EX RT 5 3:1
EX RT 7 3:1
EX RT 11 3:1
Page 2 - 34007724EN/AD
Introduction
Important instructions that must always be followed.
Information, tips, help.
Visual indication.
Action.
Information may be found primarily by checking:
the contents, z
the index. z
Icons
Using this document
Thank you for selecting an EATON product to protect your equipment.
The EX RT range has been designed with the utmost care.
We recommend that you take the time to read this manual to take full advantage of the many features of
your UPS.
Warning: this is a class A UPS product. In a domestic environment, this product may cause radio
interference, in which case, the user may be required to take additional measures.
If the device must be installed in overvoltage category III or IV environments, additional upstream
overvoltage protection must be provided for.
To discover the entire range of EATON products and the options available for the EX RT range,
we invite you to visit our web site at www.eaton.com or contact your EATON representative.
Audible alarm.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
Environmental protection
EATON cares about the environmental impact of its products and has therefore implemented an eco-design
process for the entire life cycle of the EX RT product: design, usage and recycling.
34007724EN/AD - Page 3
Contents
1. Presentation
1.1 Standard configurations ........................................................................................ 5
Tower configuration ................................................................................................. 5
Rack configuration .................................................................................................... 5
1.2 Rear panels ............................................................................................................. 6
Power module EX RT 5/7/11 .................................................................................... 6
Battery module EX RT EXB 7/11 .............................................................................. 6
1.3 Display and control panel ..................................................................................... 7
1.4 Options .............................................................................................................. 7
Rack mounting kits .................................................................................................. 7
Transformer for galvanic isolation or earthing arrangement change ....................... 8
Battery extensions for UPS backup times up to 60 minutes .................................. 9
CLA module (Long backup time charger) for backup times from 2 to 8 hours ....... 9
Modules integration system .................................................................................. 10
Battery module with Remote Emergency Power Off function (REPO) ................. 10
Battery extension cable (1,8 m / 6 ft) ....................................................................10
2. Installation
2.1 Unpacking and parts check ................................................................................. 11
Power module ........................................................................................................ 11
Battery module ....................................................................................................... 11
2.2 Installation in tower configuration .................................................................... 12
2.3 Installation in rack configuration ...................................................................... 13
Adjustment of the orientation of the logo and control panels ............................... 13
Battery module rack mounting (optional rail required) ........................................... 13
Power or battery module rack mounting (optional rail required) ............................ 14
2.4 Communication ports ......................................................................................... 16
Connection to the RS232 communication port ....................................................... 16
Connection to the communications port by relays ................................................. 16
Remote Power Off ................................................................................................. 17
Remote Power Off communication port ................................................................. 17
Installation of communication cards (optional, standard with
the Network Pack version) ...................................................................................... 17
2.5 Installation depending on the system earthing arrangement (SEA) ............. 18
UPS with common Normal and Bypass AC inputs ................................................. 18
UPS with separate Normal and Bypass AC inputs ................................................. 18
UPS with separate Normal and Bypass AC inputs, supplied
by separate sources ................................................................................................ 19
Frequency converter (without Bypass AC input) .................................................... 19
Hot standby ............................................................................................................ 19
2.6 Required protective devices and cable cross-sections ................................... 20
Recommended upstream protection ..................................................................... 20
Recommended downstream protection ................................................................ 20
Required cable cross-section ................................................................................. 20
2.7 Connections of input/output power cables ...................................................... 21
UPS with common Normal and Bypass AC sources ............................................. 21
UPS with separate Normal and Bypass AC sources .............................................22
Frequency converter ............................................................................................... 23
Connection of battery cables .................................................................................. 24
Connection of galvanic isolation transformer .......................................................... 24
Connection of CLA module ..................................................................................... 25
Page 4 - 34007724EN/AD
Contents
3. Operation
3.1 Initial start up ....................................................................................................... 26
UPS personalisation ................................................................................................ 26
Accessing personalisation with front panel buttons ............................................... 26
Access to the personalisation through external software ...................................... 27
3.2 Final start up sequence ....................................................................................... 27
3.3 Operating modes .................................................................................................28
Normal (double conversion) mode .......................................................................... 28
Eco mode ............................................................................................................ 28
3.4 Operation on battery power .............................................................................. 29
Transfer to battery power ....................................................................................... 29
Threshold for the low-battery warning .................................................................... 29
End of backup time ................................................................................................. 29
3.5 Return of Normal AC source .............................................................................. 29
3.6 Shut down ............................................................................................................ 30
4. Maintenance
4.1 Troubleshooting ................................................................................................... 31
4.2 Hot-swapping the power module ...................................................................... 32
Disconnecting the power module ........................................................................... 32
Reconnecting the power module ............................................................................ 33
4.3 Hot-swapping the battery module ..................................................................... 33
Disconnecting the battery module .......................................................................... 33
Reconnecting the battery module ........................................................................... 33
4.4 Training center ..................................................................................................... 34
5. Appendices
5.1 Technical specifications ....................................................................................... 35
Electrical characteristics .......................................................................................... 35
Thermal characteristics ........................................................................................... 38
5.2 Glossary ............................................................................................................ 38
34007724EN/AD - Page 5
1. Presentation
1.1 Standard configurations
Rack configuration
Tower configuration
Battery module
(EX RT EXB 7/11)
Battery module
(EX RT EXB 7/11)
Power module
(EX RT 5/7/11)
Power module (EX RT 5/7/11)
Dimensions in mm/
inches (H x W x D)
EX RT 5
EX RT 7
EX RT 11
EX RT EXB 7
EX RT EXB 11
444 x 131 x 635
Dimensions in mm/
inches (H x W x D)
EX RT 5
EX RT 7
EX RT 11
EX RT EXB 7
EX RT EXB 11
131 (3U) x 444 x 635
Weight in kg/lbs
EX RT 5
EX RT 7
22.5
EX RT 11 27.5
EX RT EXB 7 64.5
EX RT EXB 11 68.5
Weight in kg/lbs
EX RT 5
EX RT 7
22.5
EX RT 11 27.5
EX RT EXB 7 64.5
EX RT EXB 11 68.5
Page 6 - 34007724EN/AD
BY
PASS
NORMAL
1. Presentation
1.2 Rear panels
Slot for communication cards.
Communication port by relays.
Remote Emergency Power Off communication port (REPO).
Connectors for automatic detection of battery module(s).
RS232 communications port.
Battery module connectors (to the UPS or to other battery
modules).
Manual Bypass switch.
Output terminal block.
Normal AC source circuit-breaker.
Normal AC source terminal block.
Bypass AC source terminal block.
Power module EX RT 5/7/11
Battery module EX RT EXB 7/11
Connectors for automatic detection of battery module(s).
Battery module connectors (to the UPS or to other battery
modules).
Battery circuit breaker.
1
1
6
6
6
6
8
8
10
10
11
12
12
11
2
2
3
3
4
4
4
4
5
5
7
7
9
9
34007724EN/AD - Page 7
OFF ON
E X 1 1 R T 3:1
1.4 Options
Rack mounting kits
1.3 Display and control panel
1. Presentation
Load protected LED.
Operation on battery LED.
Operation on bypass LED.
Fault LED.
Alphanumeric display.
UPS OFF button.
Function buttons (scroll up /
scroll down).
UPS ON button (or function button
in personalisation mode).
Telescopic rails for Power module mounting in 19" enclosure with mounting hardware
(Part number 68001)
Telescopic rails for Battery module mounting in 19" enclosure with mounting hardware
(Part number 68002)
Ear hangup.
Rear bracket system for
transportation.
Telescopic rails, 639 mm to
1005 mm length (27.36" to 39.96").
Input/Output box bracket system.
Ear hangup.
Rear bracket system for
transportation.
Telescopic rails, 639 mm to
1005 mm length (27.36" to 39.96").
LOAD LEVEL
4 kW / 5 kVA
22
22
22
22
23
23
23
23
24
24
24
24
25
25
13
13
18
18
14
14
19
19
15
15
20
20
16
16
21
21
17
17
Page 8 - 34007724EN/AD
Transformer for galvanic isolation or earthing arrangement change
(Part number 68003)
1. Presentation
Example of EX RT transformer connected upstream for EX RT galvanic isolation
Battery module (EX RT EXB)
Power module (EX RT 5/7/11)
Transformer module (EX RT)
UPS output to load
Normal AC input
This module is necessary either when a downstream neutral system from the UPS upstream is required, or
when a different power source connects the automatic bypass for higher availability.
Bypass AC input
34007724EN/AD - Page 9
1. Presentation
Battery extensions for UPS backup times up to 60 minutes (at full load)
EX RT offers a standard backup time of 5/9 minutes at full load.
To increase backup time, it is possible to connect EX RT EXB 7/11 modules to the UPSs.
Battery extensions for EX RT 5, EX RT 7 or EX RT 11
CLA module (Long backup time charger) for backup times from 2 to 8 hours
(Part number 68004)
Very long backup times, from 2 to 8 hours at full load, require a EX RT CLA module.
Total battery voltage : 240 V DC (20 x 12V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalisation
section).
+++
EX RT 5/7
+ EX RT EXB 7 RT
/
EX RT 11
+ EX RTEXB 11
EX RT EXB 7
/
EX RT
EXB 11
7 kVA:
11 kVA:
7 min
5 min
20 min
14 min
32 min
22 min
+ +
45 min
30 min
57 min
42 min
70 min
53 min
EX RT EXB 7
/
EX RT
EXB 11
EX RT EXB 7
/
EX RT
EXB 11
EX RT EXB 7
/
EX RT
EXB 11
EX RT EXB 7
/
EX RT
EXB 11
5 kVA:9 min 26 min 42 min 60 min 72 min 87 min
EX RT 5/7/11
EX RT CLA
~
50A
BY
PASS
NORMAL
Battery backup
time
Recommended batteries for:
EX RT 5 EX RT 7 EX RT 11
2 hours
50 Ah 65 Ah 100 Ah
4 hours
100 Ah 130 Ah 200 Ah
8 hours
200 Ah 260 Ah 400 Ah
Page 10 - 34007724EN/AD
1. Presentation
Modules integration system for
extended backup time configurations
to conveniently stack and secure up
to 8 modules on the same cart (swivel
wheels with brakes, leveling feet,
seismic side panels, plates to lock
modules and screws included).
Modules integration system (Part number 68005)
Battery module with Remote Emergency Power Off function (REPO)
Battery circuit breaker with Remote Emergency Power OFF shunt trip.
Battery extension cable (1,8 m / 6 ft, Part number 68006)
This extended battery cable will be used instead of the standard battery cable when battery modules are
distant from each other (located in two different enclosures, for instance).
Part number:
EX RT EXB 7 EPO: 68079
EX RT EXB 11 EPO: 68119
Transformer module
Power module
Batteries
modules
12
34007724EN/AD - Page 11
2.1 Unpacking and parts check
Two sets of tower stands.
RS232 communications cable.
Product documentation.
Telescopic rails for rack enclosure with
mounting hardware (optional, or standard
with Network Pack version).
Solution-Pac power management suite
CD-ROM.
Tower stand expanders.
Battery cable.
Battery communication cable.
Input/Output junction box (with 11 insulated ferrules).
Network Management card (optional, or standard in
Network Pack version).
Bezel screw driver.
Power module
Battery module
2. Installation
Packaging must be destroyed according to waste management standards. Recycling icons are displayed for
easy selection.
A dangerous voltage is present inside the power module and the battery module. Any operations to be carried out
on these modules must be done so by qualied staff.
22
22
23
23
24
2425
24
26
26
30
30
31
31
25
25
32
32
27
27
28
28
29
29
Page 12 - 34007724EN/AD
2. Installation
2.2 Installation in tower configuration
Use the tower stand template provided with the battery module.
1
3
4
2
1
4
3
2
4
4
Follow steps 1 to 4 to adjust the tower stands for the upright position.
Always keep 150 mm free space behind the UPS rear panel.
The distance between the tower stands should be 450 mm.
34007724EN/AD - Page 13
2.3 Installation in rack configuration
2. Installation
Adjustment of the orientation of the logo and control panels
1
2
3
4
5
6
Battery module rack mounting (optional rails required, part number: 68002)
We recommend to mount the battery module first, then mount the power module above the battery
The battery module is very heavy. To ease its rack integration, we strongly recommend to remove the
battery trays as explained below:
1
2
1
1
2
3
3
4
4
Page 14 - 34007724EN/AD
Follow steps 1 to 4 for rack mounting the UPS onto the rails.
The rails and the necessary mounting hardware are supplied by EATON.
Note for step 1: it is possible to adjust the position of both front mounting ears.
1
3
3
4
2
1
4
3
3
Power or battery module rack mounting (optional rails required, part number: 68001)
2. Installation
5
6
34007724EN/AD - Page 15
2. Installation
1
2
4
Input/output junction box bracket system (included with power module rail kit, part
number 68001)
This bracket will maintain the Input/Output box at the rear of the rack enclosure when hot-swapping the
power module.
It will then be easier to slide the replacement module into the connectors of the Input/Output box.
3
4
Rear bracket system (included with rail kits, part numbers 68001 and 68002)
1
1
To be used if you need to move the
rack enclosure with UPS already
rack-mounted inside.
3
2
2
3
Page 16 - 34007724EN/AD
BY
PASS
NORMAL
2. Installation
Connection to the RS232 communication port
1 - Connect the RS 232
23
communications cable to the serial
port on the computer.
2 - Connect the other end of the
communications cable
23
to the RS
232
5
communications port on the
UPS.
The UPS can now communicate with
various EATON power management
application software. Please note
that the configuration software is
included with Personal Solution Pac
for Windows.
Connection to the communication port by relays 2
Pin 1, 2: not used, z
Pin 3: Remote Power Off signal (5 to 27 V DC, 10 mA max), z
Pin 4: Operation on mains (not on battery), z
Pin 5: User common, z
Pin 6: Operation on automatic by-pass, z
Pin 7: Low battery, z
Pin 8: Load protected, z
Pin 9: Operation on battery. z
n.o.: contact normally open.
n.c.: contact normally closed.
When the status is active, the contact between the common (Pin 5) and the relevant information pin is
closed.
Output relays specifications
Voltage: 48 V DC max, z
Current: 2 A max, z
Power: 62,5 VA, 30 W. z
Example: for 48 V DC, Imax = 625 mA
2.4 Communication ports
EX RT provides 3 communication methods that can be used simultaneously:
The COM port provides RS232 communications using EATON SHUT protocol. Compatible with most z
power management software applications available into the enclosed Solution Pac CD-Rom.
The output contact port is used for basic signaling or for protection of IT systems like IBM iSeries z
(formerly AS400) and more.
The slot is compatible with any EATON communication card (check www.eaton.com web site for the z
complete list of compatible cards).
5
23
5432
9876
1
n.o.n.c. n.o. n.o. n.o.
common
34007724EN/AD - Page 17
RJ11
5432
1
6
5432
1
6
RJ11
2. Installation
Installation of communication cards (optional, standard with the Network Pack version)
It is not necessary to shut down the
UPS to install the communication card:
1 - Remove the slot cover secured by
two screws.
2 - Insert the card
1
into the slot.
3 - Secure the card with both screws.
Communication card.
Signal: z
- activation voltage: 5 V DC to 27 V DC.
- current: 10 mA max.
Remote Power Off communication port 3
5 V DC to
27 V DC
5 V DC to
27 V DC
Used in conjunction with the optional EPO battery module, this port enables total isolation of all power
sources connected to the UPS in case of emergency (the cable is not provided).
Remote power off contact normally open
Remote power off contact normally closed
Remote Power Off
Installation of a Remote power off function must be carried out in compliance with applicable regulations.
In order to fully de-energize devices and EX RT with an RPO port, it is necessary :
- To use a two-position switch (Normally Open or Closed contact should be held more than 1 second to be
taken into account).
- To use battery cabinet(s) EX RT EXB EPO.
- To connect to this RPO switch a device that allows to trip all breaker(s) located upstream
(1)
AC NORMAL
and AC BY PASS as well as downstream
(2)
the EX RT. This can be achieved through by means of a shunt
trip.
(1) If not, the output devices will remain powered through the AC BY PASS if RPO switch has been
loosened.
(2) If not, the output devices will remain powered several seconds after the RPO activation.
1
Page 18 - 34007724EN/AD
11
10
8
11
10
8
8
10
11
8
10
11
ASI avec réseaux d'entrée AC Normal et AC Bypass séparés
2. Installation
2.5 Installation depending on the system earthing arrangement (SEA)
UPS with common Normal and Bypass AC inputs
Changement de SLT entre amont et aval ou isolation galvanique requis
Changement de SLT entre amont et aval ou isolation galvanique requis
(*): The transformer is not necessary if:
Normal and Bypass AC inputs are connected to the same source, z
and wires cross sections and wires lengths on Normal and Bypass inputs are identical, z
and upstream protection is provided by only one switch with RCD (residual current device) for Normal z
and Bypass inputs.
EX RT must be fed from a 3-phase source with neutral.
Bypass AC
Normal AC
Bypass AC
Normal AC
Bypass AC
Normal AC
Main
low-voltage
switchboard
(MLVS)
load
load
Main
low-voltage
switchboard
(MLVS)
Main
low-voltage
switchboard
(MLVS)
load
Main
low-voltage
switchboard
(MLVS)
load
Bypass AC
Normal AC
(*)
(*)
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232

Eaton EX RT 11 3:1 Installation and User Manual

Categoria
Gruppi di continuità (UPS)
Tipo
Installation and User Manual
Questo manuale è adatto anche per

in altre lingue