Taco Comfort Solutions VR1816HY2FC2A00 specificazione

Tipo
specificazione
©Taco Catalog #100-116 Eective Date: 05/30/17
Supersedes: 04/21/17 Printed in USA
The 00e® series — VR1816 circulator is an innitely variable speed, high-eciency
wet rotor circulator with an ECM permanent magnet motor. Operating modes
include innitely variable xed speed and self-adjusting constant pressure or
proportional pressure variable speed.
VR1816 ECM High-Efficiency Circulator
High-eciency ECM motor
uses up to 85% less electricity
Innitely variable speed settings
to ne tune ow for any system
SureStar automatic unblocking
and air purging mode
BIO Barrier® lter protects pump
from system contaminants
Dual electrical knock-outs and
6” stranded wire leads included
for easy wiring
Water Circulation
Pumps & Circulators
Replacement Chart (6-3/8” flange to flange dimension)
Taco Grundfos Armstrong Xylem/B&G Wilo
005
006
007
008
00R
00R
3-Speed
0015
3-Speed
UP 15-10 F
UP 15-10 FR
UP 15-42 F
UP 15-42 FR
UPS 15-42 F
UPS 1558 FC
UPS 15-58 FRC
ALPHA 15-55F
ALPHA 15-55FR
Astro 230CI
Astro 230CI-R
Astro 250CI
Astro 250CI-R
Astro 20
Astro 25
Astro 30
Astro 30-3
Astro 50-3
Compass 20-20
ecocirc 19-14 auto
ecocirc 19-14 vario
NRF-22
NRF-25
NRF-9F/LW
Star S 16F
Star S 16FX
Star S 21RFC
Star S 21FX
Star S 21F
Stratos ECO
16 RFC
18’ Shut-o head, 16 gpm max ow
ECM High-eciency motor
Easy to use dial to set operating
speed or pressure control
Operates in 3 dierent modes:
- Innitely Variable Fixed Speed
- Constant Pressure —
Self-adjusting, Variable Speed
- Proportional Pressure —
Self-adjusting, Variable Speed
5 color LED displays:
- Operating mode (Blue, Orange or Green)
- Error code diagnostics (Red or White)
Use with a Taco ZVC Zone Valve Control or
SR Switching Relay for ON/OFF operation
Integral Flow Check (IFC®) included
Whisper quiet operation
Optional 2-way ange
reduces SKU’s and provides
universal t-up to any
ange position
Double insulated, no ground required
Innitely variable speed operation to ne tune ow for any system.
TTT
Constant Pressure Mode
Across a series loop system
using zone valves
Fixed Speed Mode (Min/Max)
For zoning with circulators
Proportional Pressure Mode
Across multiple panel radiators
with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
Typical Applications
Fixed Speed Mode (Min/Max) For zoning with circulators
Constant Pressure Mode
Across a series loop system using zone valves
Proportional Pressure Mode Across multiple panel
radiators with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
TTT
Constant Pressure Mode
Across a series loop system
using zone valves
Fixed Speed Mode (Min/Max)
For zoning with circulators
Proportional Pressure Mode
Across multiple panel radiators
with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
TTT
Constant Pressure Mode
Across a series loop system
using zone valves
Fixed Speed Mode (Min/Max)
For zoning with circulators
Proportional Pressure Mode
Across multiple panel radiators
with thermostatic radiator valves
T= thermostatic radiator valve (TRV)
Features & Applications
Green LEDOrange LED
Blue LED
PROPORTIONAL
PRESSURE MODE
CONSTANT
PRESSURE MODE
FIXED SPEED
MODE
PC
min -
max
The VR1816 is factory-programmed for Max Speed
Setting. Simply turn the dial to change speed,
operating mode or pressure setting.
Min
Max
Q(gpm)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43210
0015 – Hi
008
0015 – Med
007
0015 – Low
006
003
Flow
Head in Feet
5
10
15
Q(gpm)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43210
008
0015—Med
007
0015—Low
006
Flow
Head in Feet
Low
Med
High
Q(gpm)
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H (ft)
0
2
4
6
8
10
12
14
16
18
20
Q (l/s)
0.0 0.2 0.4 0.6 0.8 1.0 1.2
H (m)
0
1
2
3
4
5
6
Q (m
3
/h)
43210
Flow
Head in Feet
Fixed Speed Mode (Min/Max)
Constant Pressure Mode
Proportional Pressure Mode
Fixed speed mode allows the installer
to ne tune the circulator ow rate
to precisely match design load
conditions. It is innitely variable
between min/max settings.
Ideal for zoning with circulators.
See chart to the left for equivalent 00®
model at each variable speed setting.
In constant pressure mode, the
circulator maintains a constant pressure
dierential (p-c) in the system as
heating load increases or decreases.
Selection options are 5, 10, or 15 feet
of head constant pressure.
Best option for zoning with zone valves.
See chart to the left for equivalent
the 00® model at each setting.
In proportional pressure mode, the
circulator maintains a proportional
pressure dierential (p-v) in the
system as heating load increases
or decreases. Flow will change in
relationship to the change in
pressure dierential.
Best option for panel radiators with
thermostatic radiator valves (TRV).
Selection options are Low, Medium,
or High. If unsure on proper setting,
select Medium and adjust as needed.
Modes & Performance
Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360
Taco (Canada) Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8 / (905) 564-9422 / Fax (905) 564-9436
www.TacoComfort.com

Specifications
Maximum Shut-off Head: 18 feet
Maximum Flow: 16 gpm
Maximum Operating Pressure: 125 psi
(8.6 bar)
Maximum Water Temp: 230°F (110°C)
Minimum Water Temp: 36°F (2°C)
Electrical specifications:
Voltage: 120V, 60 Hz
Single phase
Operating Power: 4W - 44W
Max. AMP Rating: 0.54
Equipped with a cast iron casing
and should be used for closed
loop systems only
Not suitable for chilled water or open
loop potable water systems
Taco circulator pumps are
for indoor use only
Acceptable for use with water or
maximum of 50% water/glycol solution
Pump Dimensions & Weights
Electrical Data
Model Volts Hz Ph Max.Amps Max. Watts RPM
All Models
120 60 1 .54 44 1590 - 4830
Motor
Type
ECM, Permanent Magnet, Thermally Protected
Materials of Construction:
Casing: ...............................Cast Iron
Stator Housing: .............Composite
Cartridge: .......................... Composite
Impeller: ............................Composite
Shaft: ....................................Ceramic
Bearings: ............................Carbon
Thrust Bearing: ..............Ceramic
O-Ring & Gaskets: ........EPDM
Integral Flow Check (IFC
®
):
Body, Plunger ....... Acetal
O-ring Seal .............EPDM
Spring ........................Stainless Steel
Applications
The VR1816 circulator is a variable speed, high-efficiency wet rotor circulator
with an ECM permanent magnet motor. Operating modes include infinitely
variable fixed speed to fine tune any zone, self-adjusting constant pressure for
zone valve applications and self-adjusting proportional pressure for panel
radiators with thermostatic radiator valves. The VR1816 is not suitable for
chilled water or open loop potable water systems.
Mounting Positions
Flange Orientation
Standard (S)
Part
Number
Flange
Code
A B C D F G Ship Wt.
in. mm in. mm in. mm in. mm in. mm in. mm lbs. Kg
VR1816-HY2-FC2A00
S 6 152 4-1/8 104 3-3/16 80 3-1/4 82 5 126 6-3/8 161 5.8 2.6
VR1816-HY2-4C2A00
U 6 152 4-1/8 104 3-3/16 80 3-1/4 82 5-1/8 130 6-3/8 161 6 2.7
Universal (U)
Submittal Data # 101-167 Eective: 05/30/17
Supersedes: 04/21/17
Submittal Data Information
Taco 00e
®
series — VR1816
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

Taco Comfort Solutions VR1816HY2FC2A00 specificazione

Tipo
specificazione