MANUAL SH2SSTRI424 V2 code 15-029-622 / 160115 http://www.carlogavazzi.com/ CARLO GAVAZZI
n WORKING MODE
If the SH2SSTRI424 is connected to the
Dupline®bus and the bus is working properly,
the output module is in STANDARD mode and
the green LED is ON. It enters LOCAL mode if
the push button is pressed. In LOCAL mode the
module doesn't accept any command from the
bus and the green LED will be flashing. The
relay can go back to STANDARD mode only
when the bus is ok and after one of the follow-
ing events: 1) As soon as the dupline bus
returns; 2) After a timeout of 1 minute after a
button press; 3) After a power cycle.
Pushbutton The push button is used for local
switching ON/OFF of the outputs, without
needing to connect the bus for test purposes.
Bus connected With a short pulse, the user
enters LOCAL mode and the green LED will be
flashing: at the same time all the outputs will be
switched ON, if at least one of them is OFF. If
all the outputs are ON they will be switched
OFF. Bus not connected or faulty If the bus is
not connected or faulty, the push button over-
writes the fail-state status of the outputs: if at
least one output is OFF, all of them will be
switched ON. If both the outputs are ON they
will be switched OFF. Should all the outputs be
configured for the safe-state recycle status,
then a short pressure will reset the timer and
revert to the original status of the outputs.
Fail/safe condition The output status of the
outputs, when the Dupline® bus is not connect-
ed or faulty, is programmed via the Sx tool and
the user can choose between the following
options: 1) Outputs always OFF; 2) Outputs
always ON; 3) The two outputs maintain the
status they had before the disconnection; 4)
The two outputs run in a cycle with program-
mable on and off periods: the user can set both
the off and on period from 1 to 255 minutes.
The factory setting is outputs always OFF.
n MODO DE FUNCIONAMIENTO
Si el SH2RE16A2E230 está conectado al bus
Dupline® y el bus funciona correctamente, el
módulo de relé estará en modo ESTÁNDAR y el
LED verde estará activado. El relé accede al
modo LOCAL si se pulsa el pulsador o si el bus
está defectuoso o no está conectado. En modo
LOCAL, el relé no admite ninguna orden del
bus y el LED parpadeará. El relé puede regre-
sar al modo ESTÁNDAR solo cuando el estado
del bus sea correcto y se produzca uno de los
siguientes eventos: 1) Inmediatamente des-
pués del retorno del bus Dupline®; 2) Tras un
tiempo límite de 1 minuto después de pulsar un
botón; 3) Tras reiniciar la alimentación.
Pulsador El pulsador sirve para la activar/des-
activar las salidas, sin necesidad de conectar el
bus para realizar pruebas. Bus conectado
Mediante una pulsación breve, el usuario acce-
de al modo LOCAL y el LED verde empieza a
parpadear; al mismo tiempo, se activarán
todas salidas, si al menos una de ellas está
desactivada. Si ambas salidas están activadas,
se desactivarán. Bus no conectado o defec-
tuoso Si el bus no está conectado o está
defectuoso, el pulsador reemplazará el estado
seguro en caso de fallo de las salidas; si al
menos una de las salidas está desactivada,
todas se activarán. Si todas las salidas están
activadas, se desactivarán. En caso de que
todas las salidas estén configuradas para el
estado de reinicio a prueba de fallos, mediante
una pulsación breve se restaurará el temporiza-
dor y se restablecerá el estado original de las
salidas. Estado seguro en caso de fallo El
estado de salida de las salidas, si el bus
Dupline®no está desconectado o si está defec-
tuoso, se programa a través de la herramienta
Sx y el usuario puede escoger entre las
siguientes opciones: 1) Salidas siempre desac-
tivadas; 2) Salidas siempre activadas; 3) Las
dos salidas mantienen el estado que tenían
antes de la desconexión; 4) Las salidas ejecu-
tan un ciclo con periodos de activación y des-
activación programables; el usuario puede
ajustar tanto el periodo de activación como el
periodo de desactivación entre 1 y 255 minu-
tos. Por ajuste de fábrica, las salidas siempre
están desactivadas.
n MODALITÀ DI FUNZIONAMENTO
Se SH2SSTRI424 è collegato al bus Dupline®,
ed il bus funziona regolarmente, il modulo relè
si trova nel modo STANDARD ed il LED verde è
acceso. Il relè passa in modalità LOCAL se
viene premuto il pulsante, oppure se il bus è
difettoso o non connesso. In modalità LOCAL,
il relè non accetta comandi dal bus e il LED
verde inizia a lampeggiare. Il relè ritorna alla
modalità STANDARD quando il bus è OK e
dopo uno dei seguenti eventi: 1) Non appena
viene nuovamente connesso il bus Dupline®; 2)
Dopo un timeout di 1 minuto dalla pressione di
un pulsante; 3) Dopo un riavvio. Pulsante Il
pulsante viene usato per la commutazione
locale ON/OFF delle uscite senza la necessità
di collegare il bus per le prove. Bus collegato
Con un breve impulso, l’utente passa in moda-
lità LOCAL ed il LED verde inizia a lampeggia-
re: allo stesso tempo entrambe le uscite saran-
no attivate, se almeno una di loro è disattivata.
Se entrambe le uscite sono attive, saranno dis-
attivate. Bus non collegato o difettoso Se il
bus non è connesso oppure è difettoso, il pul-
sante sovrascrive lo stato delle uscite: se alme-
no un’uscita è disattivata, entrambe si attive-
ranno. Se entrambe le uscite sono attive,
saranno disattivate. Qualora si dovessero con-
figurare tutte le uscite allo stato di riciclo in
sicurezza, allora una breve pressione resetterà
il timer e ripristinerà lo stato iniziale delle usci-
te. Condizioni di sicurezza in caso di guasto
Lo stato di uscita dei relè, quando il bus
Dupline®non è collegato o è difettoso, viene
programmato con Sx tool e l’utente potrà sce-
gliere tra le seguenti opzioni: 1) Uscite sempre
disattivate; 2) Uscite sempre attivate; 3) Le due
uscite mantengono lo stato che avevano prima
di disconnettersi; 4) Le due uscite eseguono un
ciclo con periodi di attivazione e disattivazione
programmabili: l’utente può impostare sia il
periodo di disattivazione che quello di attiva-
zione da 1 a 255 minuti. L’impostazione di fab-
brica prevede che le uscite siano sempre disat-
tivate.
Approvals: CE, cURus, according to UL60950.
UL notes:
• This product is intended to be supplied by a
Listed Information Technology Equipment AC
Adaptor marked NEC Class 2 or LPS.
• Max ambient temperature: 40°C.
• A readily accessible disconnect device shall
be incorporated in the building installation
wiring.
n MODE TRAVAIL
Si le SH2SSTRI424 est connecté au bus
Dupline®et si le bus fonctionne correctement,
le module des relais est en mode STANDARD
et la LED verte est allumée. Le relais passe en
mode LOCAL lorsqu'on appuie sur le bouton-
poussoir ou si le bus est défectueux ou décon-
necté. En mode LOCAL le relais n'accepte
aucune commande du bus et la LED verte cli-
gnote. Le relais peut repasser en mode STAN-
DARD uniquement si le bus fonctionne correc-
tement et suite à l'un des événements suivants:
1) dès rétablissement du bus Dupline®; 2) après
écoulement d'une minute suite à la sollicitation
d'un bouton; 3) après mise sous tension.
Bouton-poussoir Le bouton-poussoir permet
d'activer/désactiver les sorties localement,
sans nécessité de connecter le bus pour des
tests. Bus connecté Sur une brève impulsion,
l'utilisateur entre en mode LOCAL et la LED
verte clignote: au même moment, les deux sor-
ties passent à l'état ACTIVÉ, à condition qu'au
moins l'une des deux soit DÉSACTIVÉE. Si tou-
tes les sorties sont ACTIVÉES, elles passent
toutes les deux à l'état DÉSACTIVÉ. Bus non
connecté ou défaut bus Si le bus n'est pas
connecté ou s'il est défectueux, une sollicita-
tion du bouton poussoir écrase l'état mono sta-
ble des sorties: si au moins une sortie est
DÉSACTIVÉE, toutes les sorties passent à l'é-
tat ACTIVÉ. Si les deux sorties sont ACTIVÉES,
elles passent toutes les deux à l'état
DÉSACTIVÉ. Si toutes les sorties sont configu-
rées pour recycler l'état mono stable alors, une
brève sollicitation du bouton réinitialise la tem-
porisation et rétablit les sorties à leur état d'o-
rigine. État mono stable Si le bus Dupline®
n'est pas connecté ou s'il est défectueux, on
peut programmer l'état des sorties des relais
avec le logiciel Sx. L'utilisateur a le choix des
options suivantes: 1) Sorties toujours
DÉSACTIVÉES; 2) Sorties toujours ACTIVÉES;
3) Les deux sorties sont maintenues à leurs
états avant déconnexion; 4) Les deux sorties
exécutent un cycle avec des périodes ON et
OFF programmables par l'utilisateur de 1 à 255
minutes. Les sorties sont toujours
DÉSACTIVÉES (réglage d'usine par défaut).
n BETRIEBSMODUS
Wenn das SH2SSTRI424 mit dem Dupline®-
Bus verbunden ist und der Bus ordnungsge-
mäß arbeitet, befindet sich das Relaismodul im
Standardmodus (STANDARD), und die grüne
LED leuchtet (EIN). Wenn der Taster betätigt
wird oder auf dem Bus ein Fehler vorliegt bzw.
der Bus nicht verbunden ist, wechselt das
Relais in den lokalen Modus (LOCAL). Im loka-
len Modus akzeptiert das Relais keinerlei
Befehle mehr vom Bus, und die grüne LED
blinkt. Das Relais kehrt nur dann wieder zum
Standardmodus (STANDARD) zurück, wenn der
Bus fehlerfrei arbeitet oder eines der folgenden
Ereignisse eintritt: 1) Der Dupline®-Bus ist wie-
der verfügbar; 2) Nach einer Wartezeit von 1
Minute nach einem Tastendruck; 3) Nach dem
Trennen und Wiederherstellen der
Stromversorgung Drucktaster Der Drucktaster
dient zum lokalen EIN-/AUS-Schalten der
Ausgänge zu Testzwecken, ohne dass eine
Verbindung zum Bus hergestellt werden muss.
Bus verbunden Mit einem kurzen Impuls kann
der Benutzer den lokalen Modus (LOCAL) akti-
vieren. Die grüne LED blinkt. Gleichzeitig wer-
den alle Ausgänge eingeschaltet (EIN), wenn
mindestens einer ausgeschaltet ist (AUS).
Wenn sich beide Ausgänge im Zustand EIN
befinden, werden sie ausgeschaltet (AUS). Bus
nicht verbunden oder fehlerhaft Wenn der
Bus nicht verbunden oder fehlerhaft ist, über-
schreibt der Drucktaster den Fehlerzustand der
Ausgänge. Wenn sich mindestens ein Ausgang
im Zustand AUS befindet, werden alle
Ausgänge eingeschaltet (EIN). Wenn sich beide
Ausgänge im Zustand EIN befinden, werden sie
ausgeschaltet (AUS). Wenn alle Ausgänge für
die Weiternutzung des Zustands vor dem
Fehler konfiguriert wurden, wird bei einem kur-
zen Druck auf den Taster der Timer zurückge-
setzt und der ursprüngliche Zustand der
Ausgänge wiederhergestellt. Sicherheitszu-
stand bei Störungen Der Ausgangszustand,
den die Relais einnehmen, wenn der Dupline®-
Bus nicht verbunden oder fehlerhaft ist, wird
mithilfe des Sx-Tools programmiert. Folgende
Optionen stehen zur Auswahl: 1) Ausgänge
immer AUS; 2) Ausgänge immer EIN; 3) Die bei-
den Ausgänge behalten den Zustand bei, in
dem sie sich vor der Trennung befanden. 4) Die
beiden Ausgänge arbeiten in einem Zyklus mit
programmierbarer Ein- und Ausschaltdauer:
Der Benutzer kann sowohl für die Aus- als auch
für die Einschaltdauer einen Wert zwischen 1
und 255 Minuten festlegen. Werkseitig sind die
Ausgänge auf immer AUS eingestellt.
Homologations: CE, cURus, selon UL60950.
Notes UL:
• Ce produit est conçu pour être alimenté par
un adaptateur secteur Listés comme
équipements de technologie de l'information
NEC Classe 2 ou LPS.
• Température ambiante maxi: 40°C.
• Un dispositif de déconnexion facilement
accessible doit être incorporé dans l'installa-
tion électrique du bâtiment.
MANUAL SH2SSTRI424 V2 code 15-029-622_MANUAL SH2SSTRI424 V2 code 15-029-622.qxd 20/01/15 09.10 Pagina 2