ABB MEASUREMENT & ANALYTICS | COMMISSIONING INSTRUCTION
LLT100
Laser level transmitter
Quick start instructions for
LLT100 laser level transmitter
Measurement made easy
Introduction
The LLT100 is a high performance laser level
transmitter that accu rately measures level, distance,
and position over long ranges in industrial
environments. The LLT100, using an eye-safe pulsed
laser beam, features advanced timing and
sophisticated signal process ing for pinpoint
accuracy.
Features
• Range up to: 100 m (330 ft) for level of solids /
30 m (100 ft) for level of liquids / 200 m (660 ft)
for positioning applications
• Narrow, easy-to-aim laser beam
• Measures solid surface even at wide angles
• Measures liquid levels even for clear liquids
Robust aluminum or stainless steel enclosure
• Easy and intuitive setup / no calibration required
• Explosion proof class 1 / division 1 (zone 1)
• 2-wire power from the 4 to 20 mA loop
HART communication
• Embedded HMI / Display
For more information
Further publications for LLT100 transmitters are
available for free download from:
www.abb.com/laserlevel
Search for or click on:
Product –
Data Sheet
DS/LLT100 -EN
Product
Operating Instruction
OI/LLT10 0- EN
PInpoint accuracy using
eye-safe pulsed laser
beam technology
2
LLT100 | LASER LEVEL TRANSMITTER | CI/LLT100-EN REV. A
1 Health & Safety
WARNING
Bodily injury
Read the LLT100 Operating Instruction OI/LLT100-EN
care fully before working with the product.
For personal and system safety, and for optimum
performance, make sure that you thoroughly un derstand
the contents before installing, using or maintaining this
instrument.
NOTICE
All servicing of the equipment is to be per formed at
factory by qualified service person nel only.
No user / operator adjustments inside the LLT100 level
transmitter are recommended by the manufacturer.
Product labels
Symbols that appear on this product are shown below::
Protective earth (ground) terminal.
Direct current supply only.
2 Electrical connection
HART terminal – 2 wires
Internal protective earth
(ground)
Cover lock screw M4
Positive (+)
Negative (–)
*Optional external
meter (+)
External ground
termination point
HART terminal with heater option –
2 + 2 wires
Internal protective earth
(ground)
External DC supply:
+24 V DC, 3 W
Cover lock screw M4
0 V (return)
Positive (+)
Negative (–)
*Optional external
meter (+)
External ground
termination point
Attention – location of ground
The Ground symbols is used to identify protective
earth conductor terminals.
Attention – direct current
Use wires and cable glands rated 90 °C (194 °F) minimum.
3
LLT100 | LASER LEVEL TRANSMITTER | CI/LLT100-EN REV. A
3 Mounting
Install away from falling
material for easiest
configuration
For solids laser beam can
be aimed at any angle
Also typically applies to other
scattering surfaces such as
slurries and some turbulent
liquids
For typical liquid applications
laser beam must be as
perpendicular as possible,
not exceeding 90° ± 5° to
the surface
4 Easy setup
1 Rotate the housing: unscrew the stop tang-screw by
approximately 1 rotation (do not pull it out) before removing
the housing. When the desired position is reached,
re-tighten the stop tang-screw.
2 Connect the cables (15.5 to 42 V DC) to the LLT100 laser level
transmitter – if using HART the minimum input voltage is
21 V DC.
3 Power on the transmitter.
4 Press the Right arrow key ( ) on the display and select your
access level using the Up and Down arrow keys ( ).
5 Set the main parameters at the Easy Setup menu:
a Select the required language.
b Select the measurement mode:
standard, clear liquid, positioning or dust/vapor.
c Enter the vessel height (URP).
d Set the sensor offset from the vessel top.
e Select the primary variable (PV) for the 4 to 20 mA output:
level, ullage, volume.
f Choose the unit of the primary variable (PV):
m, cm, mm, ft.
g Set the value for vessel empty (LRV).
h Set the value for vessel full (URV).
i Enable or disable the filling rate.
j Enter the Tag name.
6 Once the settings are completed, press Exit to return to the
Distance view.
Refer to Operating Instruction OI/LLT100 - EN for detailed
configuration / setup information.
Exit Select
Easy Setup
Menu
CI/LLT100-EN Rev. A 12.2017
We reserve the right to make technical
changes or modify the contents of this
document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not
accept any responsibility whatsoever for
potential errors or possible lack of
information in this document.
We reserve all rights in this document and
in the subject matter and illustrations
contained therein. Any reproduction,
disclosure to third parties or utilization of
its contents – in whole or in parts – is
forbidden without prior written consent
of ABB.
© ABB, 2017
ABB Inc.
Measurement & Analytics
Level Measurement Products
3400, Rue Pierre-Ardouin
Québec (Qbec) G1P 0B2
Canada
Tel.: +1 800 858-3847 (North America)
Tel.: +1 418 877-2944 (other countries)
Fax: +1 418 877-2834
abb.com/measurement
5 General model
Sensor
offset
Vessel
height
(URP)
Level
Ullage
Vessel full
(20 mA)
(URV)
Vessel empty
(4 mA)
(LRV)
6 Specification
Environmental conditions
Operating temperature
40 to 6C (–40 to 14F),
up to 280°C (53F)
with cooling tube
Altitude
Up to 2000 m (6561 ft.)
Relative humidity
0 to 100%
Electrical equipment
Class III
Pollution degree
4 (IP66 / IP67 / Type 4X)
Overvoltage
Category 1
Output
Analog
4 to 20 mA, NAMUR compliant
Digital
HART 7 (multi-variable output)
Communication
Local HMI, EDD / DTM, handheld
Power supply
Powered from the loop
4 to 20 mA, 15.5 to 42 V DC
Heated lens option