■ Se il livello di luce ambientale misurato è superiore al livello attivo, il registro di
ingressi 42 indica "attivo".
■ Se il livello di luce ambientale misurato si trova tra il livello Attivo e Stand-by, il
registro di ingressi 42 indica "Bassa intensità", pertanto è consigliabile impostare i
livelli Attivo e Standby nei registri di mantenimento 35 e 36 in base all'illuminazione
dell'ambiente.
VERIFICA DELLE ISTRUZIONI PER L'INSTALLAZIONE
Se il tuo dispositivo non funziona come previsto, controlla le connessioni.
MAPPE DEL REGISTRO DEL MODBUS
INPUT REGISTERS
Data type Description Data Values
1Actual temperature value signed int. Actual temperature level -300—700 500 = 50,0°C
2Temperature output value unsigned int. Output value according to temperature 0—1000 0 = 0 %
1.000 = 100 %
3Temperature alert flag unsigned int.
Flag indicates that measured Temperature is outside
set alert values. Set to '1' when the measured value
is outside temperature alert values defined by
holding registers 13 and 14
0—1 0 = Temperature measurement OK
1 = Temperature measurement too low/high
4Temperature range limit
flag unsigned int.
Flag indicates that measured temperature is outside
set range limit values. Set to '1' when the measured
temperature is outside limit range values defined by
holding registers 11 and 12
0—1 0 = Temperature range OK
1 = Temperature range too low/high
5Temperature sensor state unsigned int. Flag that shows if the communication with
temperature sensor is lost 0—1 0 = No
1 = Yes
6—9 Reserved, return 0
10 Actual relative humidity
value unsigned int. Actual relative humidity level 0—1000 1.000 = 100,0 % rH
11 Relative humidity output
value unsigned int. Output value according to relative humidity 0—1000 0 = 0 %
1.000 = 100 %
12 Relative humidity alert flag unsigned int.
Flag indicates that measured Relative humidity
is outside set alert values. Set to '1' when the
measured value is outside relative humidity alert
values defined by holding registers 17 and 18
0—1 0 = Relative humidity measurement OK
1 = Relative humidity measurement too low/high
13 Relative humidity range
limit flag unsigned int.
Flag indicates that measured Relative humidity is
outside set range limit values. Set to '1' when the
measured relative humidity is outside limit range
values defined by holding registers 15 and 16
0—1 0 = Relative humidity range OK
1 = Relative humidity range too low/high
14 Humidity sensor state unsigned int. Flag that shows if communication with humidity
sensor is lost 0—1 0 = No
1 = Yes
15 Calculated dew point signed int. Calculated dew point -700—700 200 = 20,0°C
16—20 Reserved, return 0
21 Actual CO2eq value unsigned int. Equivalent CO2 level 400—60000 1000 = 1000 ppm
22 CO2eq output value unsigned int. Output value according to CO2eq 0—1.000 0 = 0 %
1.000 = 100 %
23 CO2eq alert flag unsigned int.
Flag indicates that measured CO2eq level is outside
set alert values. Set to '1' when the measured value
is outside CO2eq values defined by holding registers
21 and 22
0—1 0 = CO2eq measurement OK
1 = CO2eq measurement too low/high
24 CO2eq range limit flag unsigned int.
Flag indicates that measured CO2eq is outside set
range limit values. Set to '1' when measured CO2eq
is outside limit range values defined by holding
registers 19 and 20
0—1 0 = CO2eq range OK
1 = CO2eq range too low/high
25 CO2eq Sensor state unsigned int. Flag that shows if the communication with the
CO2eq sensor is lost 0—1 0 = No
1 = Yes
26 Actual TVOC value unsigned int. TVOC level 0—60000 2000 = 2000 ppb
27 TVOC Output value unsigned int. Output value according to TVOC 0—1.000 0 = 0 %
1.000 = 100 %
28 TVOC alert flag unsigned int.
Flag indicates that measured TVOC level is outside
set alert values. Set to '1' when the measured value
is outside TVOC values defined by holding registers
25 and 26
0—1 0 = TVOC measurement OK
1 = TVOC measurement too low/high
29 TVOC range limit flag unsigned int.
Flag indicates that measured TVOC is outside set
range limit values. Set to '1' when measured TVOC
is outside limit range values defined by holding
registers 23 and 24
0—1 0 = TVOC range OK
1 = TVOC range too low/high
ODVCM-R TRASMETTITORE MULTIFUNZIONALE PER
AMBIENTI DIFFICILI