CARLO GAVAZZI CA18FAF08BPM1IO Manuale utente

Tipo
Manuale utente
IO-Link
capacitive sensors
Carlo Gavazzi Industri Over Hadstenvej 40, 8340 Hadsten, Denmark
Instruction manual
Manuel d’instructions
Manuale d’istruzione
Betriebsanleitung
Manual de instrucciones
Brugervejledning
使用手册
CA18FA, CA30FA
Contents
ENGLISH .............................. 3
DEUTSCH ............................ 32
FRANÇAIS ........................... 62
ESPAÑOL ............................ 92
ITALIANO ........................... 122
DANSK ............................. 152
中文 第页 ............................ 182
3
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
Table of contents
1. Introduction .........................................................4
1.1 Description ............................................................... 4
1.2 Validity of documentation ..................................................... 4
1.3 Who should use this documentation ............................................. 4
1.4 Use of the product .......................................................... 4
1.5 Safety precautions ......................................................... 4
1.6 Other documents .......................................................... 4
1.7 Acronyms ............................................................... 5
2. Product .............................................................6
2.1 Main features ............................................................. 6
2.2 Identification number ........................................................ 6
2.3 Operating modes .......................................................... 7
2.3.1 SIO mode ............................................................ 7
2.3.2 IO-Link mode .......................................................... 7
2.4 Output Parameters ......................................................... 8
2.4.1. Sensor front .......................................................... 8
2.4.2. Input selector ......................................................... 11
2.4.3. Logic function block .................................................... 11
2.4.4. Timer (Can be set individually for Out1 and Out2) .............................. 13
2.4.5. Output Inverter ....................................................... 16
2.4.6. Output stage mode .................................................... 16
2.5. Teach procedure ......................................................... 17
2.5.1. External Teach (Teach-by-wire) ............................................. 17
2.5.2. Teach from IO-Link Master ............................................... 17
2.6. Sensor Specific adjustable parameters .......................................... 20
2.6.1. Selection of local or remote adjustment ...................................... 20
2.6.2. Process data and variables ............................................... 20
2.6.3. Sensor application setting ................................................ 20
2.6.4. Temperature alarm threshold .............................................. 20
2.6.5. Safe limits ........................................................... 21
2.6.6. Event configuration .................................................... 21
2.6.7. Quality of run QoR .................................................... 21
2.6.8. Quality of Teach QoT ................................................... 22
2.6.9. Filter Scaler .......................................................... 22
2.6.10. LED indication ....................................................... 22
2.7. Diagnostic parameters ..................................................... 23
3. Wiring diagrams .....................................................24
4. Commissioning ......................................................24
5. Operation ..........................................................25
5.1. User interface of CA18FA…IO and CA30FA… IO .................................. 25
6. IODD file and factory setting ............................................26
6.1. IODD file of an IO-Link device ................................................ 26
6.2. Factory settings .......................................................... 26
7. Appendix ..........................................................26
7.1. Acronyms .............................................................. 26
7.2. IO-Link Device Parameters for CA18FA.. and CA30FA.. .............................. 27
7.2.1. Device parameters ..................................................... 27
7.2.2. SSC parameters ...................................................... 28
7.2.3. Output Parameters ..................................................... 29
7.2.4. Sensor specific adjustable parameters ....................................... 30
7.2.5. Diagnostic parameters .................................................. 31
Dimensions ..........................................................212
Mounting ...........................................................212
Detection Stability .....................................................213
Installation Hints ......................................................214
ENGLISH
4
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
1.1 Description
Carlo Gavazzi capacitive sensors are devices designed and manufactured in accordance with IEC
international standards and are subject to the Low Voltage (2014/35/EU) and Electromagnetic
Compatibility (2014/30/EU) EC directives.
All rights to this document are reserved by Carlo Gavazzi Industri, copies may be made for internal use
only.
Please do not hesitate to make any suggestions for improving this document.
1. Introduction
This manual is a reference guide for Carlo Gavazzi IO-Link capacitive proximity sensors CA18FA…IO
and CA30FA…IO. It describes how to install, setup and use the product for its intended use.
1.2 Validity of documentation
This manual is valid only for CA18 and CA30 capacitive sensors with IO-Link and until new documentation
is published.
This instruction manual describes the function, operation and installation of the product for its intended use.
1.3 Who should use this documentation
This manual contains important information regarding installation and must be read and completely
understood by specialized personnel dealing with these proximity capacitive sensors.
We highly recommend that you read the manual carefully before installing the sensor. Save the manual for
future use. The Installation manual is intended for qualified technical personnel.
1.4 Use of the product
Capacitive proximity sensors are non-contact devices capable of measuring the position and/or change
of position of any conductive target. They are also capable of measuring thickness or density of non-
conductive materials. Capacitive proximity sensors are used in a wide variety of applications including
plastic moulding processing, feeding systems for chicken or pigs, assembly line testing, filling or emptying
processes of solid or liquid objects.
The CA18FA…IO and CA30FA…IO sensors are equipped with IO-Link communication. By using an IO-
Link master it is possible to operate and configure these devices.
1.6 Other documents
It is possible to find the datasheet, the IODD file and the IO-Link parameter manual on the Internet at
http://gavazziautomation.com
1.5 Safety precautions
This sensor must not be used in applications where personal safety depends on the function of the sensor (The
sensor is not designed according to the EU Machinery Directive).
Installation and use must be carried out by trained technical personnel with basic electrical installation
knowledge.
The installer is responsible for correct installation according to local safety regulations and must ensure that
a defective sensor will not result in any hazard to people or equipment. If the sensor is defective, it must be
replaced and secured against unauthorised use.
5
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
1.7 Acronyms
I/O Input/Output
PD Process Data
PLC Programmable Logic Controller
SIO Standard Input Output
SP Setpoints
IODD I/O Device Description
IEC International Electrotechnical Commission
NO Normally Open contact
NC Normally Closed contact
NPN Pull load to ground
PNP Pull load to V+
Push-Pull Pull load to ground or V+
QoR Quality of Run
QoT Quality of Teach
UART Universal Asynchronous Receiver-Transmitter
SO Switching Output
SSC Switching Signal Channel
6
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2. Product
2.1 Main features
New IO-Link Carlo Gavazzi 4-wire DC 4th Generation Tripleshield sensors, built to the highest quality
standards, are available in two different housing sizes.
CA18FA.. PTFE M18-cylindrical threaded barrel housing for flush or non-flush installation with 4-pole
M12 connector or 2 metre PVC cable.
CA30FA.. PTFE M30-cylindrical threaded barrel housing for flush or non-flush installation with 4-pole
M12 connector or 2 metre PVC cable.
They can operate in standard I/O mode (SIO), which is the default operation mode. When connected
to an IO-Link master, they automatically switch to IO-Link mode and can be operated and easily
configured remotely.
Thanks to their IO-Link interface, these devices are much more intelligent and feature many additional
configuration options, such as the settable sensing distance and hysteresis, also timer functions of the
output. Advanced functionalities such as the Logic function block and the possibility to convert one
output into an external input makes the sensor highly flexible in solving decentralized sensing tasks.
2.2 Identification number
Code Option Description
C - Sensing principle: Capacitive Sensor
A - Cylindrical housing with threaded barrel
18 M18 housing
30 M30 housing
F - PTFE housing
A - Axial sensing
F Flush installation
N Non-flush installation
08 8 mm sensing distance (for CA18…)
12 12 mm sensing distance (for CA18…)
16 16 mm sensing distance (for CA30…)
25 25 mm sensing distance (for CA30…)
B -
Selectable functions: NPN, PNP, Push-Pull, External Input (only pin 2), External
teach input (only pin 2)
P - Selectable: NO or NC
A2 2 metre PVC cable
M1 M12, 4-pole connector
IO - IO-Link version
Additional characters can be used for customized versions.
7
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.3 Operating modes
IO-Link capacitive sensors are provided with two switching outputs (SO) and can operate in two
different modes: SIO mode (standard I/O mode) or IO-Link mode.
2.3.1 SIO mode
When the sensor operates in SIO mode (default), an IO-Link master is not required. The device works
as a standard capacitive sensor, and it can be operated via a fieldbus device or a controller (e.g.
a PLC) when connected to its PNP, NPN or push-pull digital inputs (standard I/O port). One of the
greatest benefits of these capacitive sensors is the possibility to configure them via an IO-Link master
and then, once disconnected, they will keep the last parameter and configuration settings. In this
way it is possible, for example, to configure the outputs of the sensor individually as a PNP, NPN or
push-pull, or to add timer functions such as T-on and T-off delays or logic functions and thereby satisfy
several application requirements with the same sensor.
2.3.2 IO-Link mode
IO-Link is a standardized IO technology that is recognized worldwide as an international standard (IEC
61131-9).
It is today considered to be the “USB interface” for sensors and actuators in the industrial automation
environment.
When the sensor is connected to one IO-Link port, the IO-Link master sends a wakeup request (wake
up pulse) to the sensor, which automatically switches to IO-Link mode: point-to-point bidirectional
communication then starts automatically between the master and the sensor.
IO-Link communication requires only standard 3-wire unshielded cable with a maximum length of 20 m.
1
2 4
3
L+
C/Q
L-
IO-Link
SIO
IO-Link communication takes place with a 24 V pulse modulation, standard UART protocol via the
switching and communication cable (combined switching status and data channel C/Q) PIN 4 or
black wire.
For instance, an M12 4-pin male connector has:
Positive power supply: pin 1, brown
Negative power supply: pin 3, blue
Digital output 1: pin 4, black
Digital output 2: pin 2, white
The transmission rate of CA18FA…IO or CA30FA…IO, sensors is 38.4 kBaud (COM2).
Once connected to the IO-Link port, the master has remote access to all the parameters of the sensor and
to advanced functionalities, allowing the settings and configuration to be changed during operation,
and enabling diagnostic functions, such as temperature warnings, temperature alarms and process
data.
8
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
Thanks to IO-Link it is possible to see the manufacturer information and part number (Service Data) of
the device connected, starting from V1.1. Thanks to the data storage feature it is possible to replace
the device and automatically have all the information stored in the old device transferred into the
replacement unit.
Access to internal parameters allows the user to see how the sensor is performing, for example by
reading the internal temperature.
Event Data allows the user to get diagnostic information such as an error, an alarm, a warning or a
communication problem.
There are two different communication types between the sensor and the master and they are
independent of each other:
Cyclical for process data and value status – this data is exchanged cyclically.
Acyclical for parameter configuration, identification data, diagnostic information and events
(e.g. error messages or warnings) – this data can be exchanged on request.
2.4 Output Parameters
The sensor measures five different physical values. These values can be independently adjusted and
used as source for the Switching Output 1 or 2; in addition to those an external input can be selected
for SO2. After selecting one of these sources, it is possible to configure the output of the sensor with
an IO-Link master, following the six steps shown in the Switching Output setup below.
Once the sensor has been disconnected from the master, it will switch to the SIO mode and keep the
last configuration setting.
Sensor front Selector
A
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
Selector
B
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
EXT-Input
S.P., Two P.
Window,
Adj. Hyst.
1. SSC1
S.P., Two P.
Window,
Adj. Hyst.
2. SSC2
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
B
A
B
Out 1
Out 2
EXT-
Input
2.4.1. Sensor front
When an object, solid or liquid, approaches the face of the sensor, the capacitance of the detecting
circuit is influenced and the sensor output changes its status.
1 2 3 4 5 6
2.4.1.1. SSC (Switching Signal Channel)
For presence (or absence of presence) detection of an object in front of the face of the sensor, the
following settings are available: SSC1 or SSC2.
The setpoints can be set from 0 to 10.000 units which represent the change of capacitance of the
detecting circuit. The higher the value, the closer the target appears to the sensing face of the sensor,
also a higher dielectric value of the target will increase the value. E.g. a metal target has a higher
dielectric value than a plastic target.
1
9
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.4.1.2. Switchpoint mode:
The Switchpoint mode setting can be used to create more advanced output behaviour. The following
switchpoint modes can be selected for the switching behaviour of SSC1 and SSC2
Disabled
SSC1 or SSC2 can be disabled individually, but this will also disable the output if it is selected
in the input selector (the logic value will always be “0”).
Single point mode
The switching information changes, when the measurement value passes the threshold defined in
setpoint SP1, with rising or falling measurement values, taking into consideration the hysteresis.
Sensor
Sensing distance
ON OFF
SP1
Hysteresis
Two point mode
The switching information changes when the measurement value passes the threshold defined in
setpoint SP1. This change occurs only with rising measurement values. The switching information
also changes when the measurement value passes the threshold defined in setpoint SP2. This
change occurs only with falling measurement values. Hysteresis is not considered in this case.
Sensor
Sensing distance
SP2
Hyst
OFF OFF
ON
SP1
Hyst
window
Window mode
The switching information changes, when the measurement value passes the thresholds defined in
setpoint SP1 and setpoint SP2, with rising or falling measurement values, taking into consideration
the hysteresis.
Sensor
Sensing distance
ON OFF
SP2
Hysteresis
SP1
Example of presence detection - with non-inverted logic
Example of presence detection - with non-inverted logic
Example of presence detection - with non-inverted logic
10
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.4.1.3. Hysteresis Settings
In SSC1 and SSC2 - single point mode and in windows mode the hysteresis can be set between 1 and
100 % of the actual switching value. Standard settings depend on the sensing type:
CA18FAF… 4%
CA18FAN… 15%
CA30FAF… 5%
CA30FAN… 10%
(SP2 + Hysteresis < SP1) & (SP1 + hysteresis < Sensing range upper limit).
Information
An extended hysteresis is generally used to solve vibration or EMC issues in the application.
2.4.1.4. Dust alarm 1 and Dust alarm 2
The safe limit between when the sensing output is switching and the value at which the sensor can
detect safely even with a slightly build up of dust, can be set.
See 2.6.5 Safe limits.
2.4.1.5. Temperature alarm (TA)
The sensor constantly monitors the internal temperature in the front part of the sensor. Using the
temperature alarm setting it is possible to get an alarm from the sensor if temperature thresholds are
exceeded. See §2.6.4
The temperature alarm has two separate values, one for setting maximum temperature and one for
setting minimum temperature.
It is possible to read the temperature of the sensor via the acyclic IO-Link parameter data.
NOTE!
The temperature measured by the sensor will always be higher than the ambient temperature, due to
internal heating.
The difference between ambient temperature and internal temperature is influenced by how the sensor
is installed in the application. If the sensor is installed in a metal bracket the difference will be lower
than if the sensor is mounted in a plastic one.
2.4.1.6. External input
The output 2 (SO2) can be configured as an external input allowing external signals to be fed into the
sensor, this can be from a second sensor or from a PLC or directly from machine output.
11
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2
2.4.2. Input selector
This function block allows the user to select any of the signals from the “sensor front” to the Channel
A or B.
Channels A and B: can select from SSC1, SSC2, Dust1, Dust2, Temperature alarm and external input.
Sensor front Selector
A
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
Selector
B
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
EXT-Input
S.P., Two P.
Window,
Adj. Hyst.
1. SSC1
S.P., Two P.
Window,
Adj. Hyst.
2. SSC2
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
B
A
B
Out 1
Out 2
EXT-
Input
Channel A
Channel B
3
2.4.3. Logic function block
In the logic function block a logic functionca be added directly to the selected signals from the input
selector without using a PLC – making decentralised decisions possible.
The logic functions available are: AND, OR, XOR, SR-FF.
Sensor front Selector
A
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
Selector
B
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
EXT-Input
S.P., Two P.
Window,
Adj. Hyst.
1. SSC1
S.P., Two P.
Window,
Adj. Hyst.
2. SSC2
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
B
A
B
Out 1
Out 2
EXT-
Input
Out 1
Out 2
EN
12
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
OR function
Symbol Truth table
A B Q
0 0 0
0 1 1
1 0 1
1 1 1
Boolean Expression Q = A + B Read as A OR B gives Q
2-input OR Gate
XOR function
Symbol Truth table
A B Q
0 0 0
0 1 1
1 0 1
1 1 0
Boolean Expression Q = A + B A OR B but NOT BOTH gives Q
2-input XOR Gate
+
AND function
Symbol Truth table
A B Q
0 0 0
0 1 0
1 0 0
1 1 1
Boolean Expression Q = A.B Read as A AND B gives Q
2-input AND Gate
2-input OR Gate
13
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
“Gated SR-FF” function
The function is designed (to: e.g. function) as a filling or emptying function using only two intercon-
nected sensors
Symbol Truth table
A B Q
0 0 0
0 1 X
1 0 X
1 1 1
X – no changes to the output.
2.4.4. Timer (Can be set individually for Out1 and Out2)
The Timer allows the user to introduce different timer functions by editing the 3 timer parameters:
• Timer mode
• Timer scale
• Timer value
Sensor front Selector
A
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
Selector
B
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
EXT-Input
S.P., Two P.
Window,
Adj. Hyst.
1. SSC1
S.P., Two P.
Window,
Adj. Hyst.
2. SSC2
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
B
A
B
Out 1
Out 2
EXT-
Input
Out 1
Out 2
4
2.4.4.1. Timer mode
This selects which type of timer function is introduced on the Switching Output. Any one of the
following is possible:
2.4.4.1.1. Disabled
This option disables the timer function no matter how the timer scale and timer delay is set up.
2.4.4.1.2. Turn On delay (T-on)
The activation of the switching output is generated after the actual sensor actuation as shown in
the figure below.
14
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
Example with normally open output
Presence of
target
N.O.
Ton Ton Ton
Presence of target
2.4.4.1.3. Turn Off delay (T-off)
The deactivation of the switching output is delayed until after to the time of removal of the target
in the front of the sensor, as like shown in the figure below.
Presence of
target
N.O.
Toff Toff Toff Toff
Presence of target
2.4.4.1.4. Turn ON and Turn Off delay (T-on and T-off)
When selected, both the T-on and the Toff delays are applied to the generation of the switching
output.
N.O.
Ton Ton Ton
Toff
Toff
Presence of target
Example with normally open output
Example with normally open output
15
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.4.4.1.5. One shot leading edge
Each time a target is detected in front of the sensor the switching output generates a pulse of
constant length on the leading edge of the detection. See figure below.
Presence of target
2.4.4.1.6. One shot trailing edge
Similar in function to the one shot leading edge mode, but in this mode the switching output is
changed on the trailing edge of the activation as shown in the figure below.
Example with normally open output
Presence of target
Example with normally open output
2.4.4.1.7. Timer scale
The parameter defines if the delay specified in the Timer delay should be in milliseconds, seconds
or minutes
2.4.4.1.8. Timer Value
The parameter defines the actual duration of the delay. The delay can be set to any integer value
between 1 and 32 767
16
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.4.5. Output Inverter
This function allows the user to invert the operation of the switching output between Normally Open
and Normally Closed.
Sensor front Selector
A
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
Selector
B
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
EXT-Input
S.P., Two P.
Window,
Adj. Hyst.
1. SSC1
S.P., Two P.
Window,
Adj. Hyst.
2. SSC2
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
B
A
B
Out 1
Out 2
EXT-
Input
Out 1
Out 2
5
RECOMMENDED FUNCTION
The recommended function is found in the parameters under 64 (0x40) sub index 8 (0x08) for SO1
and 65 (0x41) sub index 8 (0x08) for SO2. It has no negative influence on the Logic functions or the
timer functions of the sensor as it is added after those functions.
CAUTION!
The Switching logic function found under 61 (0x3D) sub index 1 (0x01) for SSC1 and 63 (0x3F) sub
index 1 (0x01) for SSC2 are not recommended for use as they will have a negative influence on the
logic or timer functions. Using this function will turn an ON delay into an Off delay if it is added for
the SSC1 and SSC2. It is only for the SO1 and SO2.
2.4.6. Output stage mode
In this function block the user can select if the switching outputs should operate as:
SO1: Disabled, NPN, PNP or Push-Pull configuration.
SO2: Disabled, NPN, PNP, Push-Pull , External input (Active high/Pull-down), External input
(Active low/pull up) or External Teach input.
Sensor front Selector
A
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
Selector
B
Logic
A - B
Time
delay
Output
inverter
Sensor
output
One of
1 to 6
AND, OR,
XOR, S-R
divider
ON, OFF
One-shot
N.O., N.C. NPN, PNP,
Push-Pull
EXT-Input
S.P., Two P.
Window,
Adj. Hyst.
1. SSC1
S.P., Two P.
Window,
Adj. Hyst.
2. SSC2
3. Dust 1
4. Dust 2
5. Temp
6. EXT-Input
A
B
A
B
Out 1
Out 2
EXT-
Input
Out 1
Out 2
6
17
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.5. Teach procedure
2.5.1. External Teach (Teach-by-wire)
NB! This function works in single point mode and only for SP1 in SSC1.
The Teach-by-wire must be set up first using an IO-link master:
a) Select: “2=Teach by wire” in the Selection of local/remote adjustment parameters 68 (0x44).
b) Select: “1=Single Point Mode”, is already selected in “SSC1 Configuration” 61(0x3D),
“Mode 1” 2(0x02), (this value should already be set as default).
c) Select: 6=Teach-In (Active High) in Channel 2 (SO2) 65 (0x41) sub index 1 (0x01).
Teach-by-wire procedure.
1) Place the target in front of the sensor and connect the teach-by-wire input (pin 2 white wire) to V+
(pin 1 brown wire). The yellow LED will Flash with 1Hz (ON 100mS and OFF 900 mS).
2) Within 3-6 seconds the wire must be disconnected, and the yellow led will be flashing with 1Hz
(ON 900 mS and OFF 100 mS).
3) After a successful Teach the yellow LED will flash with 2 Hz (ON 250 mS and OFF 250 mS).
NB! If the Teach procedure is to be cancelled do not remove the wire after 3 to 6 seconds but keep
the connection for 12 secs until the yellow LED is flashing with 10 Hz (On 50 mS and off 50 mS).
2.5.2. Teach from IO-Link Master
a) To enable Teach from the IO-Link master first disable the trimmer input:
Select: “0=Disabled” in the Selection of local/remote adjustment parameters 68 (0x44).
b) The individual team commands can be written to index 2.
2.5.2.1. Single point mode procedure
Select the Switching channel to be taught
a) Select: 1=SSC1 or 2=SSC2 in the “Teach-in Select” 58(0x3A) or 255 = All SSC.
b) Change the Hysteresis if requested for SSC1 or SSC2.
“SSC1 configuration” 61(0x3D) “Hysteresis” 3(0x03).
“SSC2 configuration” 62(0x3E) “Hysteresis” 3(0x03).
NB! It is not recommended to change the hysteresis below the values stated in the SSC
parameter list.
1) Single value teach command sequence:
#65 “SP1 Single value teach”
#64 “Teach apply” (optional command)
Command Sequence
1) “SP1 Single value Teach”
2) “Teach Apply”
Sensing distance
Sensor
SSC
18
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2) Dynamic teach command sequence
#71 “SP1 dynamic teach start”
#72 “SP1 dynamic teach stop”
#64 “Teach apply” (optional command)
3) Two value teach command sequence
#67 “SP1 two value teach TP1”
#68 “SP1 two value teach TP2”
#64 “Teach apply” (optional command)
Command Sequence
1) “SP1 Two value Teach TP1”
2) “SP1 Two value Teach TP2”
3) “Teach Apply”
2.5.2.2. Two point mode procedure
1) Two value teach command sequence:
#67 “SP1 two value teach TP1”
#68 “SP1 two value teach TP2”
#64 “Teach apply” (optional command)
#69 “SP2 two value teach TP1”
#70 “SP2 two value teach TP2”
#64 “Teach apply” (optional command)
Command Sequence
1) “SP1 Two value Teach TP1”
2) “SP1 Two value Teach TP2”
3) “Teach Apply”
4) “SP2 Two value Teach TP1”
5) “SP2 Two value Teach TP2”
6) “Teach Apply”
Sensing distance
Sensing distance
Sensor
SSC
Sensor
SSC
19
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2) Dynamic teach command sequence:
#71 “SP1 dynamic teach start”
#72 “SP1 dynamic teach stop”
#73 “SP2 dynamic teach start”
#74 “SP2 dynamic teach stop”
#64 “Teach apply” (optional command)
2.5.2.3. Windows mode procedure
1) Single value teach command sequence:
#65 “SP1 Single value teach”
#66 “SP2 Single value teach”
#64 “Teach apply” (optional command)
Command Sequence
1) “SP1 Single value Teach”
3) “Teach Apply”
2) “SP2 Single value Teach”
3) “Teach Apply”
2) Dynamic teach command sequence:
#71 “SP1 dynamic teach start”
#72 “SP1 dynamic teach stop”
#73 “SP2 dynamic teach start”
#74 “SP2 dynamic teach stop”
#64 “Teach apply” (optional command)
Sensing distance
Sensing distance
SSC
Sensor
SSC
Command Sequence
1) “SP1 Dynamic Teach Start”
2) “SP2 Dynamic Teach Stop”
3) “Teach Apply”
Sensing distance
Sensor
SSC
Command Sequence
1) “SP1 Dynamic Teach Start”
2) “SP2 Dynamic Teach Stop”
3) “Teach Apply”
Sensor
20
EN
Rev.00 - 02.2020 | CA18FA/CA30FA Capacitve sensors with IO-Link interface | © 2020 | CARLO GAVAZZI Industri
2.6. Sensor Specific adjustable parameters
Besides the parameters directly related to output configuration, the sensor also have various internal
parameters useful for setup and diagnostics.
2.6.1. Selection of local or remote adjustment
It is possible to select how to set the sensing distance by either selecting the Trimmer or Teach-by-wire
using the external input of the sensor, or to disable the potentiometer to make the sensor tamperproof.
2.6.2. Process data and variables
When the sensor is operated in IO-Link mode, the user has access to the cyclic Process Data Variable.
By default the process data shows the following parameters as active: 16 bit Analogue value, Switching
Output1 (SO1) and Switching Output 2 (SO2).
The following parameters are set as Inactive: SSC1, SSC2, DA1, DA2, TA, SC.
However by changing the Process Data Configuration parameter, the user can decide to also enable
the status of the inactive parameters. This way several states can be observed in the sensor at the
same time.
Byte 0
31 30 29 28 27 26 25 24
MSB
Byte 1
23 22 21 20 19 18 17 16
LSB
Byte 2
15 14 13 12 11 10 9 8
SC TA DA2 DA1 SSC2 SSC1
Byte 3
7 6 5 4 3 2 1 0
SO2 SO1
4 Bytes
Analogue value 16 … 31 (16 BIT)
2.6.3. Sensor application setting
The sensor has 3 pre-settings depending on the application:
Full scale range, the setpoints of the sensor can be adjusted at full scale and the sensing
speed is set to maximum
Liquid level: this is to be used for slow moving objects with a high dielectric value such as in
the detection of water-based liquids. When this function is selected the teach and
potentiometer settings are optimized to high range scaling.
In this mode the “Filter Scaler” is set to 100
Plastic Pellets: this is to be used for slow moving objects with a low dielectric value such as in
the detection of plastic pellets. When this function is selected the teach and potentiometer
settings are optimized to low range scaling.
In this mode the “Filter Scaler” is set to 100.
2.6.4. Temperature alarm threshold
The temperature at which the temperature alarm will activate can be changed for the maximum and
minimum temperature. This means that the sensor will give an alarm if the maximum or minimum
temperature is exceeded. The temperatures can be set between -50 °C to +150 °C. The default
factory settings are, Low threshold -30 °C and high threshold +120 °C.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215

CARLO GAVAZZI CA18FAF08BPM1IO Manuale utente

Tipo
Manuale utente