ETC
®
Installation Guide
Unison Paradigm
®
P-TS7 Rack Panel
P-TS7 Rack Panel Page 1 of 4 Electronic Theatre Controls, Inc.
Corporate Headquarters
3031 Pleasant View Road, P.O. Box 620979, Middleton, Wisconsin 53562-0979 USA
Tel +608 831 4116
Fax +608 836 1736
London, UK
Unit 26-28, Victoria Industrial Estate, Victoria Road, London W3 6UU, UK
Tel +44 (0)20 8896 1000
Fax +44 (0)20 8896 2000
Rome, IT
Via Pieve Torina, 48, 00156 Rome, Italy
Tel +39 (06) 32 111 683
Fax +44 (0)20 8896 2000
Holzkirchen, DE
Ohmstrasse 3, 83607 Holzkirchen, Germany
Tel +49 (80 24) 47 00-0
Fax +49 (80 24) 47 00-3 00
Hong Kong
Rm 1801, 18/F, Tower 1 Phase 1, Enterprise Square, 9 Sheung Yuet Road, Kowloon Bay, Kowloon, Hong Kong
Tel +852 2799 1220
Fax +852 2799 9325
Service:
(Americas) service@etcconnect.com
(UK) service@etceurope.com
(DE) techserv-hoki@etcconnect.com
Web:
www.etcconnect.com
Copyright © 2015 ETC. All Rights Reserved.
Product information and specifications subject to change.
7184M2190
Rev A
Released 2015-01
ETC intends this document to be provided in its entirety.
Overview
The Unison Paradigm
®
P-TS7 Touchscreen can be installed in an equipment rack using a rack panel,
which is shipped separately. It is powered by either LinkPower with auxiliary power or by PoE (Power
over Ethernet 802.3af).
• Echelon
®
LinkPower
®
(LinkConnect) control network using Belden 8471 (or approved equal) and
24 Vdc Auxiliary power (two 16 AWG 1.5mm
2
) wires.
• PoE (Power Over Ethernet 802.3af) using Category 5 cable (or approved equal).
Control wiring should only be installed and terminated by a qualified technician and should follow
standard wiring installation practices. Leave approximately 10 inches (254mm) of wiring in the backbox
for connection and to allow slack for future service needs. For more information about terminating CAT5
cable, refer to the ETC Ethernet Cat5 Termination Kit Setup Guide.
Install Collar in Rack Panel
Installation should follow local codes and standard practices. Ensure that all wiring is installed correctly.
The touchscreen is supplied with an installation kit which includes the necessary hardware and
electrical supplies.
Step 1: Slide the collar into the rack panel.
Step 2: Install and tighten four M4 x 20mm collar mount screws through the collar and into the
rack panel.
Paradigm Touchscreen Model
Model Description
P-TS7-RM Paradigm Touchscreen Rack Panel
Note:
It is important to orient the rack panel with the cutout on the right side to provide better
cable access between the touchscreen and the Termination PCB.
In addition, the collar should be installed with the stamped arrow (
) pointing up.