12
Congure the system
EM24 E1 - Instruction manual | CARLO GAVAZZI Controls SpA
Settings from EM24 E1
General settings
The available settings depend on the application set.
Page title Sub-menu Description Values Default value
Cng PASS - Change password From 0 to 9999 0
APPLiCAt Application tYP.A
tYP.b
tYP.C
tYP.d
tYP.E
tYP.F
tYP.G
tYP.H
tYP.H
User USEr 1 User From 0 to 9999 1
USEr 2 From 0 to 9999 2
USEr 3 From 0 to 9999 3
dHCP - DHCP enabling oFF/on oFF
IP Addr IP o.-.-.- IP address From 000 to 255 192
IP -.o.-.- From 000 to 255 168
IP -.-.o.- From 000 to 255 1
IP -.-.-.o From 000 to 255 10
SUb SUb o.-.-.- Subnet mask From 000 to 255 255
SUb -.o.-.- From 000 to 255 255
SUb -.-.o.- From 000 to 255 255
SUb -.-.-.o From 000 to 255 0
GAtE GAtE o.-.-.- Default gateway From 000 to 255 192
GAtE -.o.-.- From 000 to 255 168
GAtE -.-.o.- From 000 to 255 1
GAtE -.-.-.o From 000 to 255 1
Port - MODBUS TCP port 502
SELECtor SELEC. 1 Page displayed according to selector
position among the available pages for
each application (see”Frontal selector”
on page 15)
From 1 to 28 1
SELEC. 2 From 1 to 28 25
SELEC. 3 From 1 to 28 28
SELEC.LoC From 1 to 28 3
SYS - System 3P.n
3P.1
2P
1P
3P
Note: MID (PFA, PFB): only 3P.n
3P.n
Ut rAtio - Voltage transformer ratio (VT) AV5: from 1 to 6975
AV2: N/A
1
Ct rAtio - Current transformer ratio (CT) AV5: from 1 to 6975
AV2: N/A
1
P int.ti - Dmd integration time (min) From 1 to 30 15
FiLtEr.S - Interval of lter intervention with respect
to full scale (%)
From 0 to 100 2
FiLtEr.Co - Filter coefcient From 1 to 32 2
End - Exit and save - -
Note: the Ut rAtio is available for compatibility with other versions, even though the AV5 version is not meant to be used with voltage transformers. It should
be therefore set to 1.