EM511 - User manual | 30/05/2023 | CARLO GAVAZZI Controls SpA 19
Input, output and communication
Digital input
The digital input can perform four functions:
Function Description Parameters
Tariff management Digital input used to manage the tariff
Digital input status Tariff
Open Tariff 1
Closed Tariff 2
-
Remote status Digital input is used to check the status via Modbus or M-Bus.
Digital input status Register 300h
Open 0
Closed 1
-
Partial meters start/stop Digital input is used to enable/disable the reset of partial meters
Digital input status Partial meter
Open Disabled (in pause)
Closed Enabled
-
Partial meter reset Digital input is used to enable/disable the increasing of partial meters
Digital input status Action
Open No action
Closed After 3 seconds, reset partial meters
-
Digital output (version O1)
The digital output can perform two functions:
Function Description Parameters
Alarm Output associated with the alarm Output state when no alarm is active
Pulse output Pulse transmission output for imported active
energy consumptions.
lLinked energy (kWh+, kWh-)
lPulse weight
lPulse duration
Modbus RTU port (version S1)
Modbus RTU communication port is used to transmit data to a Modbus master.
For further information about Modbus RTU communication refer to the communication protocol.
M-Bus port (version M1)
M-Bus communication port is used to transmit data to a M-Bus master (Carlo Gavazzi SIU-MBM or any third party M-Bus master).
For further information about M-Bus communication refer to the communication protocol.