Lince 5197-SPAA240340 Istruzioni per l'uso

Tipo
Istruzioni per l'uso

Questo manuale è adatto anche per

SPOTLED
cod. SPSA240140 - SPSA240340 - SPAA240140 - SPAA240340 - SPBA240140 - SPBA240340 - SPLA240040
1
IP40
EN 60598-1, EN 60598-2-2, EN 60598-2-22, EN 55015, EN 61547, EN 61000-3-2,
EN 61000-3-3, EN 61347-1, EN 61347-2-7, EN 62471
2
Ø76mm
34
5
SPOTLED
BATTERY
SA
LIXIT srl - Registered office: Via dei Lavoratori, 10 - 63076 Monteprandone (AP) - ITALY
Production site: Via dell’Industria, 16 - 63078 Spinetoli (AP) – ITALY
DCGILXIESPOTLED-R141
INICOM
SPSA240340
SPSA240140
12 h
100%
Maintained
Non-Maint.
6 h
1 h 3,2 V - 1,5 Ah N-M / M
LiFePO4
lm
Non-Maint.
300
300
2 x 3,2 V - 1,5 Ah3 h N-M / M
lm
Maintained
220
220
SPAA240340
SPAA240140
12 h
6 h
1 h 3,2 V - 1,5 Ah N-M / M
300
300
2 x 3,2 V - 1,5 Ah3 h N-M / M 220
220
SPBA240340
SPBA240140
12 h
6 h
1 h 3,2 V - 1,5 Ah N-M / M
300
300
2 x 3,2 V - 1,5 Ah3 h N-M / M 220
220
SPLA240040
-
- - --300
-
-
-
AVVERTENZE
- La sorgente luminosa è di tipo LED non sostituibile.
- Rischio fotobiologico: RG1 a 150 cm (con lente simmetrica);
RG1 a 200 cm (con lente asimmetrica).
- Sostituire la batteria quando non si raggiunge l'autonomia
nominale dopo il corrispondente periodo di ricarica.
- Per l'eventuale sostituzione di batterie o altre riparazioni,
rivolgersi ad un centro di assistenza tecnica autorizzato e
richiedere l'utilizzo di ricambi originali. Il mancato rispetto di
quanto sopra può compromettere la sicurezza
dell'apparecchio.
- Il prodotto contiene batterie ricaricabili LiFePO4 che devono
essere smaltite negli appositi cassonetti.
SEGNALAZIONI LED
VERDE FISSO: presenza rete, nessuna anomalia.
VERDE LAMPEGGIANTE: test in corso.
ROSSO FISSO: lampada guasta o batteria scollegata.
ROSSO LAMPEGGIANTE: batteria guasta.
VERDE LUNGO ALTERNATO A ROSSO IMPULSIVO: test
disabilitati, lampada inibita.
Solo per apparecchi con supervisione su BUS
VERDE-ROSSO ALTERNATI LENTI: monitor bus attivo.
VERDE-ROSSO ALTERNATI VELOCI: localizzazione attivata.
PERIODICITA' DEI TEST AUTOMATICI (escluso cod.
SPSA240140 - SPSA240340 - SPLA240040).
TEST FUNZIONALE (20 sec): ogni 14 giorni
TEST DI AUTONOMIA (durata della batteria): ogni 28 giorni
Solo per apparecchi self-test
PROCEDURA DI SINCRONIZZAZIONE TEST FUNZIONALI
E DI AUTONOMIA
- Verificare che l'apparecchio sia alimentato da rete elettrica
230Vac.
- Aprire il contatto tra i morsetti “C” e “I”.
- Richiudere il contatto tra i morsetti “C” e “I”.
Nota: questa procedura va effettuata su ogni lampada.
Esempio: se si vuole che la lampada esegua i test nella
mattinata di lunedì, l’operazione va fatta di lunedì in un orario
diurno (es. ore 9:00).
In alternativa:
- Verificare che gli apparecchi siano alimentati da rete elettrica
230Vac.
- Disabilitare i test tramite l’apertura delll'interruttore di
inibizione o tramite comando OFF con INICOM.
- Aspettare 10 secondi.
- Riabilitare i test tramite la chiusura dell'interruttore di
inibizione o tramite comando ON con INICOM.
WARNING
- The light source is a non-replaceable LED.
- Photobiological risk: RG1 at 150 cm (with symmetrical lens);
RG1 at 200 cm (with asymmetrical lens).
- Replace the battery when the nominal duration is not reached
after the corresponding charging period.
- For eventual replacement of batteries or any other repairs,
contact an authorized service centre for assistance and
request the use of original spare parts. Failure to comply with
this recommendation could affect device safety.
- The product contains LiFePO4 rechargeable batteries that
must be disposed of in the appropriate bins.
LED SIGNALS
SOLID GREEN: mains present, no anomaly.
FLASHING GREEN: test in progress.
SOLID RED: lamp fault or battery disconnected.
FLASHING RED: battery fault.
STEADY GREEN ALTERNATING TO PULSING RED: tests
disabled, lamp inhibited.
Only for supervised devices connected to the BUS
GREEN-RED ALTERNATING TO SLOW: bus monitor active.
GREEN-RED ALTERNATING TO FAST: localization activated.
FREQUENCY OF AUTOMATIC TESTS (excluding cod.
SPSA240140 - SPSA240340 - SPLA240040).
FUNCTIONAL TEST (20 sec): every 14 days
AUTONOMY TEST (battery duration): every 28 days
For self-testing devices only
SYNC PROCEDURE FOR FUNCTIONAL AND AUTONOMY
TESTS
- Ensure that the unit is powered by the 230 Vac mains.
- Remove the short between the contact “C” and “I”.
- Resume the short between the contact “C” and “I”.
Note: this procedure must be carried out on each lamp.
Example: if you want the lamp to perform the tests on
Monday mornings, the operation should be done on Monday
during the day time (e.g. 09:00).
Alternatively:
- Check that the devices are powered by the 230Vac mains.
- Disable the tests by opening the inhibition switch or OFF
command with INICOM.
- Wait 10 seconds.
- Re-enable the tests by closing the inhibition switch or ON
command with INICOM.
www.lixit.it+39 0736 499951 +39 0735 704912 [email protected]
F1 N F2R C I
- - +
F1 N F2R C I
- - +
F1 N F2R C I
- - +
F1 N F2R C I
- - +
Senza comando.
With no control.
+
__ BUS
Supervisione da BUS.
BUS supervised.
+
__
Con comando di inibizione.
With inhibit control.
Con comando del modo di riposo.
With rest mode control.
C
R
INICOM
cod. SPBA****** cod. SPSA****** - SPAA****** cod. SPSA****** - SPAA****** cod. SPSA****** - SPAA******
230V ~
N
SE
Non-Maintained
SA con comando
Maintained with control
230V ~
N
230V ~
SA permanente
Maintained without control
230V ~
N
F1 N F2R C I
- - +
F1 N F2R C I
- - +
F1 N F2R C I
- - +
6
7
LENTE ASIMMETRICA
Asymmetrical Lens
1.0lx
2.0lx
3.0lx
H= 3m
15.5m
16.7m
18.5m
LENTE SIMMETRICA
Symmetrical Lens
0.5lx
14m
H= 3m
8
9
COME CAMBIARE LENTE
How to change lens
230V~
VERDE / GREEN
dbac
a=50mm (min.) b=50mm (min.) c=50mm (min.) d=150mm (min.)
  • Page 1 1
  • Page 2 2