LG ARNU07GL4G4 Manuale utente

Categoria
Condizionatori d'aria a sistema split
Tipo
Manuale utente
Original instruction
INSTALLATION MANUAL
AIR
CONDITIONER
P/NO : MFL68507211
Rev.00_042819
www.lg.com
Copyright © 2019 LG Electronics Inc. All Rights Reserved.
РУССКИЙ ЯЗЫК
УКРАÏНСЬКА
ҚАЗАҚ ТІЛІ
БЕЛАРУСКАЯ МОВА
OʻZBEK TILI
ITALIANO
ESPAÑOL
FRANÇAIS
DEUTSCH
ΕΛΛΗΝΙΚΆ
ČEŠTINA
N
E
D
E
R
L
AND
S
POLSKI
LIMBA ROMÂNĂ
ENGLISH
ARNU05GL4G4 ARNU07GL4G4 ARNU09GL4G4 ARNU12GL5G4
ARNU15GL5G4 ARNU18GL5G4 ARNU21GL6G4 ARNU24GL6G4
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
Ceiling Concealed Duct - Low Static
[
Representative
] LG Electronics Inc. EU Representative : LG Electronics European Shared
Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Tianjin Appliances Co.,Ltd.
No.09, JinWei Road,Beichen District,Tianjin,300402.P.R.China
2 Indoor Unit
Ceiling Concealed Duct - Low Static Type Indoor Unit Installation Manual
TABLE OF CONTENTS
Four type "A" screws
Connecting cable
Pipes: Gas side
Liquid side
(Refer to Product
Data)
Insulation materials
Additional drain pipe
Level gauge
Screw driver
Electric drill
Hole core drill
Flaring tool set
Specified torque wrenches
(different depending on model No.)
Spanner.......Half union
A glass of water
Screw driver
Hexagonal wrench
Gas-leak detector
Vacuum pump
Gauge manifold
Owner's manual
Thermometer
Features...................................3
Safety Precautions.................4
Installation...............................9
Selection the best location....9
Ceiling opening dimension
and hanging bolt location....10
Indoor Unit Installation.........11
Wiring Connection ...............11
Checking the Drainage .......12
Indoor Unit Drain Piping......13
Dip Switch Setting ...............15
Group Control Setting .........16
Model Designation ..............21
Airborne Noise Emission ....21
Limiting concentration .........21
How to Set E.S.P?................22
Installation Requirements
Required Parts Required Tools
Installation Manual 3
Feature
ENGLISH
Features
Name Drain hose Clamp metal
Washer for
hanging bracket
Clamp
(Tie Wrap)
Insulation for
fitting
Quantity
1 EA 2 EA 8 EA 4 EA 1 SET
Shape
(Other)
Owner's manual
Installation manual
for gas pipe
for liquid pipe
Installation Tool
Air Outlet Vents
Air Filter
Control Box
Air Intake Vents
Wired Remote Controller
Safety Precautions
4 Indoor Unit
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be
followed.
Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified
by the following indications.
WARNING
CAUTION
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance
on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an
Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric
shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Be cautious when unpacking and installing the product.
The following symbols are displayed on indoor and outdoor units.
Read the precautions in this manual
carefully before operating the unit.
This appliance is filled with flammable
refrigerant (R32)
This symbol indicates that the Operation
Manual should be read carefully.
This symbol indicates that a service
personnel should be handling this
equipment with reference to the
Installation Manual.
Installation Manual 5
Safety Precautions
ENGLISH
- Sharp edges could cause injury. Be especially careful of the case
edges and the fins on the condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service
Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing
property damage, product failure, and personal injury.
• Do not turn on the breaker or power under condition that front panel,
cabinet, top cover, control box cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or
air purge. Do not compress air or Oxygen and Do not use Flammable
gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Operation
• Do not let the air conditioner run for a long time when the humidity is
very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or
damaged during operation.
- There is risk of fire or electric shock.
• Do not place anything on the power cable.
- There is risk of fire or electric shock.
• Do not plug or unplug the power supply plug during operation.
- There is risk of fire or electric shock.
• Do not touch(operate) the product with wet hands.
- There is risk of fire or electrical shock.
• Do not place a heater or other appliances near the power cable.
- There is risk of fire and electric shock.
• Do not allow water to run into electric parts.
- It may cause
There is risk of fire, failure of the product, or electric shock.
• The appliance shall be stored in a well-ventilated area where the room
size corresponds to the room area as specified for operation.(for R32)
Safety Precautions
6 Indoor Unit
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
• Do not use the product in a tightly closed space for a long time.
- Oxygen deficiency could occur.
• When flammable gas leaks, turn off the gas and open a window for
ventilation before turn the product on.
- Do not use the telephone or turn switches on or off. There is risk of
explosion or fire.
• If strange sounds, or small or smoke comes from product. Turn the
breaker off or disconnect the power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane.
If possible, remove the product from the window before the hurricane
arrives.
- There is risk of property damage, failure of product, or electric shock.
• Do not open the inlet grill of the product during operation.
(Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
• When the product is soaked (flooded or submerged), contact an
Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a
stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the product.
- There is risk of electric shock.
• When the product is not be used for a long time, disconnect the power
supply plug or turn off the breaker.
- There is risk of product damage or failure, or unintended operation.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
• When mechanical connectors are reused indoors, sealing parts shall
be renewed.(for R32)
• When flared joints are reused indoors, the flare part shall be refabricated.
(for R32)
Installation Manual 7
Safety Precautions
ENGLISH
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of
product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor
unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt
spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the
condenser and evaporator fins, could cause product malfunction or
inefficient operation.
Operation
• Do not expose the skin directly to cool air for long periods of time.
(Don't sit in the draft.)
- This could harm to your health.
• Do not use the product for special purposes, such as preserving foods,
works of art, etc. It is a consumer air conditioner, not a precision
refrigeration system.
- There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow.
- It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic parts of
the product.
• Any person who is involved with working on or breaking into a refrigerant
circuit should hold a current valid certificate from an industry-accredited
assessment authority, which authorises their competence to handle refr-
igerants safely in accordance with anindustry recognised assessment
specification.(for R32)
Safety Precautions
8 Indoor Unit
• Do not touch the metal parts of the product when removing the air filter.
They are very sharp!
- There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units)
- There is risk of personal injury and failure of product.
• Always insert the filter securely. Clean the filter every two weeks or
more often if necessary.
- A dirty filter reduces the efficiency of the air conditioner and could
cause product malfunction or damage.
• Do not insert hands or other objects through the air inlet or outlet while
the product is operated.
- There are sharp and moving parts that could cause personal injury.
• Do not drink the water drained from the product.
- It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning or maintaining the product.
- Be careful and avoid personal injury.
• Replace the all batteries in the remote control with new ones of the
same type. Do not mix old and new batteries or different types of
batteries.
- There is risk of fire or explosion.
• Do not recharge or disassemble the batteries. Do not dispose of
batteries in a fire.
- They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it
well with clean water. Do not use the remote if the batteries have
leaked.
- The chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor.
Do not use the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health hazards.
• Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of
other skilled personnel shall be carried out under the supervision of
the person competent in the use of flammable refrigerants. (for R32)
Installation Manual 9
Installation
ENGLISH
Installation
Indoor unit
Install the air conditioner in the location that satisfies the fol-
lowing conditions.
• The place shall easily bear a load exceeding four times the
indoor unit’s weight.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
• The place shall easily connect with the outdoor unit.
• The place where the unit is not affected by an electrical
noise.
• The place where air circulation in the room will be good.
• There should not be any heat source or steam near the
unit
Confirm the positional relationship between the unit and
suspension bolts.
• Installation the ceiling opening to clean the filter or service
under the product.
Selection of the best location
A(Min)
Inspection hole
(600 x 600)
Control box
H=20 or more
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
Side view
(unit: mm)
600
600
B
B(Min)
(Unit: mm)
Top view
Air outlet
Air outlet
(Unit: mm)
Capacity (kBtu/h) A B
5/7/9 600 800
12/15/18 600 1000
21/24 600 1200
- The appliance shall be installed, operated and stored in a room
with a floor area larger than the minimum area.
- Use the graph of table to determine the minimum area.
Minimum floor area
0
100
200
300
400
500
600
Amin (m
2
)
m (kg)
0 1.224 2 3 4 5 6 7 8
Floor standing
Wall mounted
Ceiling mounted
(for R32)
Ceiling
Service Space
A
B
10 Indoor Unit
Installation
Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and duct to absorb
unnecessary vibration.
• Apply a filter Accessory at air return hole.
Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
• A place where the unit will be leveled and that can support
the weight of the unit.
• A place where the unit can withstand its vibration.
• A place where service can be easily performed.
POSITION OF SUSPENSION BOLT
(Unit:mm)
Dimension
Capacity(kBtu/h)
A B C D E F G H I J
L4
733 772 338 460 36 190 20 660 148 700
L5
933 972 338 460 36 190 20 860 148 900
L6
1133 1172 338 460 36 190 20 1060 148 1100
C
E
G
D
F
I
A
J
B
M10 Nut
M10 washer
X 4
X 4
M10 Nut
M10 washer
X 4
X 8
H
Drainage hole
POSITION OF CONSOLE BOLT
- m : Total refrigerant amount in the system
- Total refrigerant amount : factory refrigerant charge + additional refrigerant amount
- Amin : minimum area for installation
Floor location
m (kg) Amin (m
2
)
< 1.224
-
1.224
12.9
1.4 16.82
1.6 21.97
1.8 27.80
2 34.32
2.2 41.53
2.4 49.42
2.6 58.00
2.8 67.27
3 77.22
3.2 87.86
3.4 99.19
3.6 111.20
3.8 123.90
4 137.29
4.2 151.36
4.4 166.12
Floor location
m (kg) Amin (m
2
)
4.6 181.56
4.8 197.70
5 214.51
5.2 232.02
5.4 250.21
5.6 269.09
5.8 288.65
6 308.90
6.2 329.84
6.4 351.46
6.6 373.77
6.8 396.76
7 420.45
7.2 444.81
7.4 469.87
7.6 495.61
7.8 522.04
Wall mounted
m (kg) Amin (m
2
)
< 1.224
-
1.224
1.43
1.4 1.87
1.6 2.44
1.8 3.09
2 3.81
2.2 4.61
2.4 5.49
2.6 6.44
2.8 7.47
3 8.58
3.2 9.76
3.4 11.02
3.6 12.36
3.8 13.77
4 15.25
4.2 16.82
4.4 18.46
Wall mounted
m (kg) Amin (m
2
)
4.6 20.17
4.8 21.97
5 23.83
5.2 25.78
5.4 27.80
5.6 29.90
5.8 32.07
6 34.32
6.2 36.65
6.4 39.05
6.6 41.53
6.8 44.08
7 46.72
7.2 49.42
7.4 52.21
7.6 55.07
7.8 58.00
Ceiling Mounted
m (kg) Amin (m
2
)
< 1.224
-
1.224
0.956
1.4 1.25
1.6 1.63
1.8 2.07
2 2.55
2.2 3.09
2.4 3.68
2.6 4.31
2.8 5.00
3 5.74
3.2 6.54
3.4 7.38
3.6 8.27
3.8 9.22
4 10.21
4.2 11.26
4.4 12.36
Ceiling Mounted
m (kg) Amin (m
2
)
4.6 13.50
4.8 14.70
5 15.96
5.2 17.26
5.4 18.61
5.6 20.01
5.8 21.47
6 22.98
6.2 24.53
6.4 26.14
6.6 27.80
6.8 29.51
7 31.27
7.2 33.09
7.4 34.95
7.6 36.86
7.8 38.83
Installation Manual 11
Installation
• Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceil-
ing.
• Insert the set anchor and washer onto the sus-
pension bolts for locking the suspension bolts
on the ceiling.
Mount the suspension bolts to the set anchor firmly.
• Secure the installation plates onto the suspen-
sion bolts (adjust level roughly) using nuts,
washers and spring washers.
1 Set anchor
Old building New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
Connect the wires to the terminals on the control board individually according to the outdoor unit connec-
tion.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor
unit respectively.
Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump
model, put the 0.75mm
2
cable(thinner cable) on the clamp and tighten it with a plastic clamp to
the other boss of the control panel.
Wiring Connection
Indoor Unit Installation
CAUTION : Tighten the nut and bolt
to prevent unit falling.
WARNING : Make sure that the screws of the terminal are free from looseness.
CAUTION : The Power cord connected to the unit should be selected according
to the following specifications.
Terminal Block Indoor Terminal Block Indoor
INDOOR POWER INPUT
Outdoor unit
Indoor unit
Central controller
Outdoor unitIndoor unit
12V
Installation
12 Indoor Unit
1. Remove the Air Filter.
2. Check the drainage.
• Spray one or two glasses of water upon the
evaporator.
Ensure that water flows drain hose of indoor
unit without any leakage.
Checking the Drainage
.
CAUTION
(for R32)
• When mechanical connectors are reused indoors, sealing parts shall be renewed.
• When flared joints are reused indoors, the flare part shall be re-fabricated.
Installation Manual 13
Installation
CAUTION
Ceiling
Drain Pump use
Drainage hole
Front of view
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 19mm.
• The unit must be horizontal or declined to the drain hose connected when finished
installation.
Drain piping must have down-slope (1/50 to 1/100): be sure
not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra
force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor
unit is 32mm.
• Be sure to install heat insulation on the drain piping.
Piping material: Polyvinyl chloride pipe VP-25 and
pipe fittings
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
• Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring
is complete.
When the test is complete, connect the
flexible drain hose to the drain port on the
indoor unit.
Heat insulation material: Polyethylene foam with thick-
ness more than 8 mm.
Drain test
Upward
routing
not allowed
Pipe clamp
Maintenance
drain port
Indoor unit
Drain Piping
Feed water
Drain Pump
Drain pan
Flexible drain hose
Main
drain pipe
Glue the joint
Drain
port
Drain hose connection
Use the clip
Installation
14 Indoor Unit
CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As
for the method of wiring, be guided by the circuit diagram posted on the inside
of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable
to come loose from vibrations to which the unit is subjected during the course
of transportation. Check them and make sure that they are all tightly fastened.
(If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the
rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specifi-
cation. (Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point, fuse breaking, distur-
bance by the normal function of an overload protection device.
• Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)
Installation Manual 15
Installation
Dip Switch Setting
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
CAUTION
Function Description Setting Off Setting On Default
SW1 Communication N/A (Default) - - Off
SW2 Cycle N/A (Default) - - Off
SW3 Group Control
Selection of Master or
Slave
Master Slave Off
SW4
Dry Contact
Mode
Selection of Dry
Contact Mode
Wired/Wireless remote
controller
selection of Manual or Auto
operation Mode
Auto Off
SW5 Installation
Fan continuous
operation
Continuous operation Re-
moval
- Off
SW6 Heater linkage N/A - - Off
SW7
Ventilator link-
age
Selection of Ventilator
linkage
Linkage Removal Working
Off
Vane selection
(Console)
Selection of up/down
side Vane
Up side + Down side Vane
Up side Vane
Only
Region selec-
tion
Selection tropical re-
gion
General model
Tropical
model
SW8 Etc. Spare - - Off
1. Indoor Unit
2. Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automatically
with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
※ Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch 7 segment
Outdoor Unit PCB Outdoor Unit DIP Switch
Installation
16 Indoor Unit
Group Control Setting
Master
GND
Signal
12 V
LGAP Network System
Master Slave Slave Slave
Display Error Message
Only connect serial signal and GND lines
between indoor units.
or
1. Group Control 1
Wired remote controller 1 + Standard Indoor Units
Some products have no DIP switch on PCB. It is possible to set indoor units to Master or Slave by
using the wireless remote controller instead of DIP switch.
For the details of the setting, please refer to the manual of the wireless remote controller.
1. It is possible to 16 indoor units(Max.) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote
controller.
It is possible to control the other indoor units except the error units.
DIP Switch in PCB
Master Setting
- No. 3 Off
Slave Setting
- No. 3 On
Indoor Unit DIP Switch
Installation Manual 17
Installation
GND
Signal
12 V
LGAP Network System
Master Master Slave Slave
Donʼt connect serial 12V line
or
Display Error Message
Master Master
It is possible to connect indoor units since Feb. 2009.
It can be the cause of malfuctions when there is no setting of master and slave.
In case of Group Control, it is possible to use following functions.
- Selection of operation, stop or mode
- Temperature setting and room temperature check
- Current time change
- Control of flow rate (High/Middle/Low)
- Reservation settings
It is not possible to use some functions.
It is possible to control 16 indoor units(Max.) with the master wired remote control.
Other than those, it is same with the Group Control 1.
2. Group Control 2
Wired remote controllers + Standard Indoor Units
Installation
18 Indoor Unit
GND
Signal
12 V
LGAP Network System
MN
Master
Slave
Display Error Message
Master
FAU
Slave
FAU
Master
or
Master Master
Display Error Message
FAU
Standard Standard
FAU FAU
Standard Standard
FAU
* FAU : Fresh Air Intake Unit
Standard: Standard Indoor Unit
In case of connecting with standard indoor unit and Fresh Air Intake Unit, separate Fresh Air
Intake Unit with standard units. (N, M ≤ 16) (Because setting temperature are different.)
Other than those, it is same with Group Control 1.
3. Group Control 3
Mixture connection with indoor units and Fresh Air Intake Unit
Installation Manual 19
Installation
LGAP Network System
Master
Slave
GND
Signal
12 V
or
Display Error Message
Master
Slave
Slave
Slave
4. 2 Remote Control
Wired remote controller 2 + Indoor unit 1
1. It is possible to connect two wired remote controllers (Max.) with one indoor unit.
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired
remote controller.
6. There isnʼt limits of indoor unit function.
Installation
20 Indoor Unit
5. Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA +Wired remote controller
Indoor unit 1 EA +Wired remote controller 2EA
PZCWRCG3 cable used for connection
PZCWRC2 cable used for connection
Slave
Mas te r
Mas te r
PZCWRCG3
Mas te r S lav e
PZCWRC2
• Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum
cable usage.
CAUTION
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331

LG ARNU07GL4G4 Manuale utente

Categoria
Condizionatori d'aria a sistema split
Tipo
Manuale utente

in altre lingue