Form CP-UD&APD Series-RHXG (4-16), P/N 201684R3, Page 1
Form CP-UD&APD Series-RHXG (4-16)
Obsoletes Form CP-UD&APD Series-RHXG (11-14)
Gasket Kit for Replacement Heat Exchanger
Description/
Application
To prevent damage during shipping or storage, gaskets for all Standard Power Vent &
Separated Combustion Unit Model replacement heat exchangers are shipped in a parts
bag and should be attached to the heat exchanger at the time of installation. All gaskets
are self-adhesive and cut to size.
Gasket Kit
Components
DANGER: The replacement heat exchanger should be installed by a
qualied service agency in compliance with all codes and requirements
of authorities having jurisdiction.
Improper installation could result in death, serious injury, and /or
property damage. The qualied agency performing this work assumes
responsibility for this installation.
Gasket Kit
Instructions
WARNING: Proper installation and sealing of the heat exchanger to the
heater is necessary for reliable and safe operation. Failure to properly
install could result in property damage, personal injury, and/or death.
Header Panel Gaskets - All Sizes
Refer to page 2, FIGURE 1 (shown on page 2) for Sizes 30-125 or FIGURE 2 for Sizes
150-400. Select the top, bottom, and side header panel gaskets and determine the position
of each. The gaskets go on the outer edges of the header panel. Line up holes in top and
side gaskets; ignore large holes in bottom gasket.
To apply, start at the end and gradually peel the backing from the gasket as it is adhered.
Repeat with each strip. The header panel gaskets are sealing gaskets and must cover the
full length of the surface.
Tube Support Gasket - Sizes 150, 175, 200, 225, 250, 300, 350, 400
Refer to page 2, FIGURE 2 (shown on page 2). The gasket strip extends across the top,
rear, and bottom of the tube support. To apply, start at the end and gradually peel the back-
ing from the gasket as it is adhered.
The tube support gasket is required to prevent vibration but is not a sealing gasket.
Model Size 30, 45 60, 75 100, 125 150, 175, 200 225 250 300, 350, 400
Gasket Kit P/N
201667 201668 201669 201670 201671 221214 201672
Components: Qty
Header Panel Gasket Top
and Bottom
2 194493, 5/8" x 21-3/8" long 194533, 1" x 35-23/64" long
Heater Panel Gasket
Front and Rear
2
194494, 5/8" x
12-5/8"
194495, 5/8" x
15-5/8"
194496, 5/8" x
23-5/8"
195986, 1" x
20-3/16"
195987, 1" x 26-3/16"
195988, 1" x
34-3/16"
Tube Support Gasket 1
201424, 1" x
89-7/32"
201425, 1" x 95-7/32"
201426, 1" x
103-7/32"
Orice, L Drill, Brass 1
208255*
*Orice change is required on Model UDAP, UDAS, UDBP and UDBS Size 250 using natural gas and manufactured prior to 1/07; see
the instruction sheet with the orice. If the replacement heat exchanger is for a Model UDAP, UDAS, UDBP, or UDBS Size 250 using
propane, the orice is not used and should be discarded.
APPLIES TO:
Standard Power Vent Unit Heaters:
Models UDAP, UDBP and ADP
Separated Combustion Unit Heaters:
Models UDAS and UDBS
Form CP-UD&APD Series-RHXG (4-16), P/N 201684R3, Page 2



















FIGURE 2 - Gasket
Locations for Sizes
150, 175, 200, 225,
250, 300, 350, 400
Sizes 150-400
require
installation of ve
gasket strips.
FIGURE 1 - Gasket
Locations for Sizes
30, 45, 60, 75, 100,
125
Sizes 30-125
require
installation of four
gasket strips.
Additional
Maintenance
Checks
Refer to the “Maintenance/Service” Section of the heater installation manual (Models
UDAP, UDAS or APD, Form I-APD & UDA Series; or Models UDBP and UDBS,
Form I-UDB). As part of the replacement heat exchanger installation, inspect and
clean the cabinet, burner, and vent system. Replace any components that are not
structurally sound.
If servicing a natural gas Size 250 on any Model unit heater, be sure to change the
burner orice. Follow the instuctions provided.
When installation of the replacement heat exchanger is complete, review the “Check
Installation and Startup Section” in the heater installation manual. Follow the instruc-
tions on the lighting instruction plate to restart the heater. CHECK ALL SAFETY
FEATURES FOR PROPER OPERATION.
Replacement Heat Exchanger Gasket Locations for Sizes 150 - 400
Replacement Heat Exchanger Gasket Locations for Sizes 30-125
Gasket Strip
Apply Header
Panel Front
Gasket
Apply Header
Panel Bottom Gasket
Apply Header
Panel Rear
Gasket
Apply Header
Panel Top
Gasket
Heat Exchanger
Header Panel
Specications & illustrations subject to change without notice of incurring obligatons.
©Nortek Global HVAC, LLC 2016. All rights reserved.
All marks are the property of their respective organizations.
O’Fallon, MO I Printed in U.S.A. (4/16)
Doc No D300515 (4-16) SKU 319E-0416 FORM CP-UD&APD Series-RHXG (4-16), PN 201684R3