RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the location of Fire and Burglary Detection Devices Help
Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in
the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of
the household as follows: For minimum protection, a smoke detector should be installed outside of each separate
sleeping area and on each additional floor of a multi-floor family living unit, including basements. The installation of
smoke detectors
in kitchens, attics (finished or unfinished), or in garages is not normally recommended.
For additional protection, the NFPA recommends that you install
heat
or
smoke detectors
in the living room,
dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements, and
attached garages.
In addition, we recommend the following:
Install a smoke detector inside every bedroom where a smoker sleeps.
Install a smoke detector inside every bedroom where someone sleeps with the door partly or completely closed.
Smoke could be blocked by the closed door. Also, an alarm in the hallway outside may not wake up the sleeper if
the door is closed.
Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air conditioners,
or humidifiers) are used.
Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
Install smoke detectors in any room where an alarm control is located, or in any room where alarm control
connections to an AC source or phone lines are made. If detectors are not so located, a fire within the room could
prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL
PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
BEDROOM
BDRM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
✪✪
BEDROOM
BEDROOM
TO
BR
LVNG RM
BASEMENT
KTCHN
.
CLOSED
DOOR
GARAGE
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
Recommendations for Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or commercial
premises. This includes skylights and upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be sent to the
alarm monitoring station in the event that the telephone lines are out of order (alarm signals are normally sent over the
phone lines, if connected to an alarm monitoring station).
i
Table of Contents
•••••••••••••••••••••••••••••••••••••••••••••••••
Table of Contents..................................................................................................................................................................... i
List of Figures ........................................................................................................................................................................iii
Conventions Used In This Manual ....................................................................................................................................iv
SECTION 1 Introduction ...................................................................................................................................................1–1
Features.............................................................................................................................................................................1–1
SECTION 2 Mounting and Wiring the Control............................................................................................................2–1
Cabinet and Lock ..............................................................................................................................................................2–1
Mounting the PC Board with RF Receiver.......................................................................................................................2–2
Wiring to Keypads.............................................................................................................................................................2–3
Sounder (Bell) Connections .............................................................................................................................................2–4
Wiring the AC Transformer..............................................................................................................................................2–5
Backup Battery .................................................................................................................................................................2–5
Earth Ground ....................................................................................................................................................................2–6
Hardwire Zones.................................................................................................................................................................2–7
4219/4229 Expansion Zones..............................................................................................................................................2–8
Installing the RF Receiver................................................................................................................................................2–9
Installing a 5800TM Module ............................................................................................................................................2–9
Installing the Transmitters............................................................................................................................................2–10
Jam Detection and Reporting.........................................................................................................................................2–10
About 5800 Series Transmitters.....................................................................................................................................2–10
Connecting Relay Modules .............................................................................................................................................2–12
Power Line Carriers........................................................................................................................................................2–13
Phone Line/Phone Module Connections.........................................................................................................................2–14
Long Range Radio Connections ......................................................................................................................................2–15
AAV Connections.............................................................................................................................................................2–15
SECTION 3 Programming Overview..............................................................................................................................3–1
About Programming..........................................................................................................................................................3–1
Entering Program Mode ...................................................................................................................................................3–1
Programming a Data Field...............................................................................................................................................3–1
Reviewing a Data Field/Erasing an Entry.......................................................................................................................3–2
Interactive Mode Programming (
56,
58,
80,
81, and
82) .....................................................................................3–2
Loading Factory Defaults .................................................................................................................................................3–2
Programming System Setup Fields..................................................................................................................................3–2
Exiting the Programming Mode.......................................................................................................................................3–2
SECTION 4 Zone Response Type Definitions ..............................................................................................................4–1
Zone Type Definitions .......................................................................................................................................................4–1
SECTION 5 Data Field Programming............................................................................................................................5–1
About Data Field Programming .......................................................................................................................................5–1
Programming Data Fields ................................................................................................................................................5–1
System Setup Fields (*20 - *30)........................................................................................................................................5–1
Zone Sounds and Timing (*31 - *39) ................................................................................................................................5–2
Dialer Programming (*40 - *52) .......................................................................................................................................5–3
Zone Assignment Alarm Report Codes
(
56 &
58).......................................................................................................5–5
To Program System Status and Restore Report Codes
(
59 –
76, &
89)...................................................................5–5
System Status Report Codes
(
59–
68) ..........................................................................................................................5–6
Restore Report Codes (
70–
76)......................................................................................................................................5–7
Daylight Saving Time (*77 & *78) ...................................................................................................................................5–7
Dynamic Signaling (*79)...................................................................................................................................................5–8
Output And System Setup (*80 - *82; *84, *85; *87 - *93)..............................................................................................5–8
Download Information (*94, *95) ...................................................................................................................................5–11
SECTION 6 Zone Programming ......................................................................................................................................6–1
About Zone Programming.................................................................................................................................................6–1
56 Zone Programming Procedures.................................................................................................................................6–1
58 Expert Programming Mode Procedures....................................................................................................................6–4
To Remove a Zone .............................................................................................................................................................6–5
To Delete a Transmitter Serial Number..........................................................................................................................6–6
To Enter and Duplicate Wireless Keys ............................................................................................................................6–6
ii
SECTION 7 Output Device Programming ....................................................................................................................7–1
Programming Options Defined.........................................................................................................................................7–1
Programming Output Relays and Powerline Carrier Devices........................................................................................7–2
SECTION 8 Zone Lists.......................................................................................................................................................8–1
About Zone List Menu Mode.............................................................................................................................................8–1
Zone List Displays.............................................................................................................................................................8–1
Cross Zoning - Zone List 04 ..............................................................................................................................................8–1
NIGHT-STAY - Zone List 05 ............................................................................................................................................8–2
SECTION 9 Alpha Descriptor Programming ...............................................................................................................9–1
About Alpha Descriptor Programming.............................................................................................................................9–1
Zone Descriptors................................................................................................................................................................9–1
Programming Zone Descriptors (Program Menu Mode
82) .........................................................................................9–1
Adding Custom Words/Numbers (not annunciated by the 4285/4286 VIP Module)......................................................9–3
SECTION 10 Remote Programming and Control (Downloading) .........................................................................10–1
About Remote Programming ..........................................................................................................................................10–1
Equipment Required.......................................................................................................................................................10–1
Initial Download..............................................................................................................................................................10–2
Remote Programming Commands..................................................................................................................................10–2
Remote Programming Advisory Notes ...........................................................................................................................10–2
SECTION 11 System Communication..........................................................................................................................11–1
Panel Communication with Central Station..................................................................................................................11–1
Report Code Formats ......................................................................................................................................................11–1
SECTION 12 System Operation.....................................................................................................................................12–1
Security Codes.................................................................................................................................................................12–1
Keypad Functions ...........................................................................................................................................................12–1
Setting the Real-Time Clock...........................................................................................................................................12–4
SECTION 13 Testing the System...................................................................................................................................13–1
Test Procedure.................................................................................................................................................................13–1
SECTION 14 Troubleshooting Guide ...........................................................................................................................14–1
SECTION 15 Specifications & Accessories .................................................................................................................15–1
Specifications...................................................................................................................................................................15–1
Accessories (Compatible Devices)...................................................................................................................................15–3
5800 RF System Wireless Transmitters .........................................................................................................................A–1
Transmitter Input Loop Identification............................................................................................................................A–1
Regulatory Agency Statements.......................................................................................................................................B–3
Warnings and Limitations................................................................................................................................................C–1
Summary of Connections........................................................................................................................Inside back cover
iii
List of Figures
•••••••••••••••••••••••••••••••••••••••••••••••••
Figure 1. Installing the Cabinet Lock ...................................................................................................................................2–1
Figure 2. Mounting the PC Board .........................................................................................................................................2–1
Figure 3. Mounting the PC Board and RF Receiver .............................................................................................................2–2
Figure 4. Using a Supplementary Power Supply .................................................................................................................2–3
Figure 5. Sounder Wiring (Supervised) ...............................................................................................................................2–4
Figure 6. Connections of 4300 Transformer to Panel ..........................................................................................................2–5
Figure 7. Wire Smoke Detector Connected to Zone 1 ..........................................................................................................2–7
Figure 9. Wiring Connections - 4219 Expansion Module .....................................................................................................2–8
Figure 10. Wiring Connections - 4229 Expansion/Relay Module ........................................................................................2–8
Figure 11. 5881/5882 RF Receiver (cover removed) .............................................................................................................2–9
Figure 12. 4204 Connections to Control Panel ...................................................................................................................2–12
Figure 13. 4285/4286 VIP Module Wiring Connections .....................................................................................................2–14
Figure 14. Connection of AAV Unit When Not Using a 4285/4286 VIP Module ..............................................................2–15
Figure 15. Connection of AAV Unit When Also Using a 4285 or 4286 VIP Module .........................................................2–15
iv
Conventions Used In This Manual
•••••••••••••••••••••••••••••••••••••••••••••••••
Before you begin using this manual, it is important that you understand the meaning of the following symbols:
U
L
A UL note that includes specific information that must be followed if you are installing this system in a UL
Listed application.
A note that includes specific information that must be followed if you are installing this system in a Canadian
UL Listed application..
A checked note includes information you should be aware of before continuing with the installation, and
which, if not observed, could result in operational difficulties.
This symbol warns of conditions that could seriously affect the operation of the system, or cause damage to
the system. Please read each warning carefully. This symbol also denotes warnings about physical harm to
the user.
PRODUCT MODEL NUMBERS:
Unless noted otherwise, references to specific model numbers represent ADEMCO
products.
1–1
SECTION 1
Introduction
•••••••••••••••••••••••••••••••••••••••••••••••••
The VISTA-15/VISTA-15CN control with the following major features :
Features
Basic Hardwired Zones
Provides 6 basic hardwired zones having the following characteristics:
EOLR supervision supporting N.O. or N.C. sensors
Programmable response time (10, 350, or 700 mS)
Up to sixteen 2-wire smoke detectors on zone 1
4-wire smoke or heat detectors on zones 2 through 6 (as many as can be powered from Auxiliary Power on the
control).
Optional Expansion Zones (26 total: up to 8 wired with 18 wireless, OR 26 wireless)
Wired Expansion
:
Supports up to 8 additional wired zones using a 4219 Expansion Module or 4229 Expansion/Relay Module. These zones
have the following characteristics:
EOLR supervision supporting N.O. or N.C. sensors
300-500mS normal response with an option for fast (10-15mS) response on loop A (first expansion zone).
Wireless Expansion:
Supports up to 26 wireless zones (fewer if using wired expansion zones).
Requires the use of a 5881 (5882 in Canada) type RF receiver,
as indicated below:
Receiver Model No. of Zones
5881L/5882L Up to 8
5881M/5882M Up to 16
5881H/5882H Up to 26
Requires the use of 5800 Series Wireless Transmitters.
Remote Keypads
Up to 4 of any of the following keypads may be used in the installation:
Fixed-word keypad: 6128, 6128RF
Alpha keypad: 6139 (2-line alphanumeric display)
Security Codes Supported
One Installer code for entire system (user 1)
One Master code for entire system (user 2)
12 Secondary User codes (users 3–14)
One Temporary code (user 15)
One Duress code (user 16).
Temporary Code: A special code that can be used to disarm and arm the system until the Master code is
entered.
Duress Code: An emergency code that, when entered by
any
user to disarm or arm the system, sends a
silent duress message to the Central Station.
Keypad Panic Features
Up to 3 programmable panic key functions provided
Designated as zones 95, 96, 99
Activated by wired and wireless keypads
Distinguished by subscriber ID number.
VISTA-15/VISTA-15CN Installation and Setup Guide
1–2
Zone Monitor Features
Provides automatic high loop resistance detection on hardwired zones 2–6, and displays a
CHECK
message for the
affected zone when the system is in the disarmed state.
Contains a Hardwire Short Detection circuit for zones 1-6
, and enabled in
30. Detecting a short in any wired zone,
it sends a sensor Trouble message to the Central Station when the system is in the disarmed state. At the same time
a
CHECK
message is displayed on the keypad.
Hardwire Short Detection is disabled on any zone programmed for FIRE (Zone type 09).
Either condition (high resistance or short) detected on any zone, prevents the system from being armed until the
offending condition is cleared. Conversely, when the system is armed, and these conditions occur, an alarm is
generated.
Exit Error False Alarm Prevention Features
Enables the system to determine the difference between an actual alarm and an alarm caused by leaving an
entry/exit or interior zone open after the Exit Delay expires. If not disarmed in time, an alarm sounds and an Exit
Error report is sent to the Central Station.
An exit alarm condition also occurs if an entry/exit or interior zone re-opens within 2 minutes after the end of an
Exit Delay.
The system provides an automatic Exit Delay Reset feature that allows the user to exit (fault), close the door
(restore the fault), then re-enter (fault again) the premises within the exit delay time period. Upon re-entering, a
new exit delay time period is begun with the keypad annunciating three rapid beeps. This feature only resets the
exit delay time once for each arming session.
Optional Output Relays and Powerline Carrier Devices (X10 type)
The VISTA-15/VISTA-15CN supports the following optional output relays and Powerline Carrier devices (X10 type):
Maximum of 4 output devices
Up to 4 relays using one 4204 Relay Module
Up to 2 relays using one 4229 Zone/Relay Module
Up to 4 Powerline Carrier devices (you must subtract the number of relay outputs actually used by the 4204 or 4229
modules, if used).
Actions are programmable to respond to zone activity or manual keypad entries.
Powerline Carrier devices require the use of the optional 4300 Transformer Module instead of the supplied
1321/1321CN AC Transformer.
Optional VIP Module
The VISTA-15/VISTA-15CN supports the ADEMCO 4285/4286 VIP Module
(refer to Section 8: 4285/4286 VIP
Module for further information).
Provides access to the system via on-premises or off-premises phones for arming, disarming, etc., plus control of
relay outputs and Powerline Carrier devices.
Paging Feature
If programmed, the paging feature allows certain system conditions to be reported to a pager. Up to 16 digits may be
programmed to be sent as a message to the pager. A 7-digit code following the programmed message indicates the type of
condition that has occurred.
Audio Alarm Verification (AAV) Option
Provides a programmable Audio Alarm Verification (AAV) option, which can be used in conjunction with an output
relay to permit voice dialog between an operator at the Central Station and a person at the premises.
This AAV option must be used with a relay unit, such as an Eagle Model 1250.
U
L
The AAV option may not be used in UL installations.
Optional Long Range Radio
Allows all messages that have been programmed to go to the primary telephone number to also be sent to any ECP-
operational radio (such as the 7835C, 7720PLUS, and 7820) for transmission to the Central Station.
Section 1: Introduction
1–3
Built-in Telephone Line Monitoring Option
You can monitor telephone line voltage to supervise the phone line connection. You must connect the panel to a
proper earth ground or you will get a false line cut indication if this feature is enabled.
The loss of the line can optionally cause a local display, or a display and trouble sound.
Event Logging
Keeps a record of up to 48 selected events in a history log. All control and readout from the log is done via ADEMCO
COMPASS software
only
.
Quick Arm Feature
Quick Arm may be programmed , allowing use of the [#] key in place of the security code for arming (Quick Arm will not
work unless the Master code has been programmed into the system).
Alarm Output Features
Provides a 12VDC, 2 amp output that can drive the compatible sounders listed in
Section 9:
External Sounders
(assuming a fully charged battery is connected).
Steady output for burglary/panic, or temporal pulse output (3 pulses – pause – 3 pulses – pause – 3 pulses . . .) for
fire.
Uses current-limiting circuitry for protection.
Provision for Bell supervision.
Optional Bell Supervision
Red jumper on control board, when cut, provides supervision of bell wiring (when bell is wired with EOL resistor, as
indicated in the instructions).
Chime/Chime by Zone
Chime, when on, normally sounds when any entry/exit or perimeter zone is faulted. However, a “chime by zone” option,
when programmed, allows only specific zones to chime if they are faulted when the system is in the chime mode.
Auxiliary Power Output Features
Provides 12VDC, 600mA maximum (500mA maximum for UL installations). Uses current-limiting circuitry for
protection.
Interrupts for smoke detector reset if 4-wire smoke detectors are used.
Programming
Programmed options are stored in electrically erasable, nonvolatile EEPROM memory (information can be
reprogrammed at any time and will not be lost in the event of a power loss).
The system can be uploaded, downloaded, or controlled via an IBM-compatible computer, COMPASS software, and a
modem specified by ADEMCO.
Keypad programming consisting of:; Data field programming and Interactive (menu) mode programming.
To program from a keypad, you must connect a 6139 2-line alpha keypad, but it need not stay in the system.
Communication Formats Supported
ADEMCO Low Speed
(Standard or Expanded)
Sescoa/Radionics (Standard or Expanded)
ADEMCO
Express
ADEMCO
Contact ID
Zone Descriptors
You can assign
alpha descriptors to all zones (only when using alpha keypads).
AC Power Supply
Uses 1321/1321CN, 110VAC plug-in transformer with 16.5VAC, 25VA output, unless Powerline Carrier devices (for
example, X10 type) are used, in which case a 4300 Transformer Module
must be used.
Backup Battery
Rechargeable (Sealed Lead Acid) 12VDC, 4AH-17.2AH. Refer to
Section 12: Final Power-Up
to calculate the actual
battery size needed.
VISTA-15/VISTA-15CN Installation and Setup Guide
1–4
2–1
SECTION 2
Mounting and Wiring the Control
•••••••••••••••••••••••••••••••••••••••••••••••••
This section describes the procedures for mounting and wiring this control and its peripheral devices. In the following
subsections, procedures are listed in the left column, while notes and pertinent explanations are provided in the right
column.
Cabinet and Lock
Notes
1. Mount the control cabininet to a sturdy wall in a
clean, dry area which is not readily accessible to
the general public using fasteners or anchors ( not
supplied) and the four cabinet mounting holes.
2. Remove cabinet door, then remove the lock
knockout from the door. Insert the key into the
lock. Position the lock in the hole, making certain
that the latch will make contact with the latch
bracket when the door is closed.
3. Insert the retainer clip into the retainer slots.
Position the clip as shown in order to permit easy
removal.
Use an ADEMCO No. N6277 Cam Lock and No.
N6277–1 Push-On Clip (Retainer Clip).
The cabinet can be closed and secured without a lock
by using 2 screws in the cover's edge.
CABINET DOOR BOTTOM
RETAINER
CLIP
RETAINER CLIP
(NOTE POSITION)
RETAINER
SLOTS
LOCKED
UNLOCKED
Figure 1. Installing the Cabinet Lock
Mounting the PC Board Alone
(No RF
Receiver)
Note
1. Hang two short mounting clips (provided) on the
raised cabinet tabs (see Detail B in Figure 2).
2. Insert the top of the circuit board into the slots at
the top of the cabinet. Make sure that the board
rests on the correct row (see Detail A).
3. Swing the base of the board into the mounting
clips and secure the board to the cabinet with the
accompanying screws (see Detail B).
Before installing the cabinet's contents, remove the metal
cabinet knockouts required for wiring entry. Do not
attempt to remove the knockouts after the circuit board
has been installed.
CABINET
+
+
CIRCUIT BOARD
CABINET
DETAIL B
SIDE VIEW
OF MOUNTING
CLIPS
DETAIL A
SIDE VIEW
OF BOARD
SUPPORTING
SLOTS
CIRCUIT
BOARD
V15-01-V0
Figure 2. Mounting the PC Board
VISTA-15/VISTA-15CN Installation and Setup Guide
2–2
Mounting the PC Board with RF Receiver
Notes
1. Remove the receiver board from its case, then
insert the top of the board into the slots at the top
of the cabinet, as shown in Figure 3, Detail A.
Make sure the board rests on the correct row of
tabs.
2. Swing the base of the board into the
mountingclips and secure it to the cabinet with
the accompanying screws.
3. Insert the top of the control’s board into the slot in
the clips and position two clips at the lower edge
of the board.
4. Swing this board into place nad secure with two
additional screws.
5. Insert grounding lugs (supplied with receiver)
through the top of the cabinet into the left-hand
terminals of the antenna blocks (at the upper edge
of the receiver board) and secure them to the
cabinet top with the screws provided, as shown in
Detail B.
6. Insert the receiver’s antennas through the top of
the cabinet, into the block’s right-hand terminals,
and tighten the screws.
Do not mount the cabinet on or near metal objects.
This decreases RF range and/or block RF
transmissions from wireless transmitters.
Do not locate the cabinet in an area of high RF
interference (revealed by frequent or prolonged
lighting of the LED in the receiver after it is
operational (random flicker is OK).
ANTENNA
MOUNT
(2 PLACES)
ANTENNA
(2)
SCREW
(2)
BLACK
MOUNTING
CLIP
RED
MOUNTING
CLIP
WHITE
MOUNTING
CLIP
GROUNDING
LUG
(2)
NOTE
A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN
INCLUDED IN YOUR INSTALLATION KIT.
USE THE APPROPRIATE CLIPS FOR MOUNTING.
IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USING
EITHER THE WHITE OR BLACK CLIPS, WHICHEVER ARE
INCLUDED IN THE CONTROL PANEL'S HARDWARE KIT.
DETAIL A
SIDE VIEW
OF BOARD -
SUPPORTING SLOTS
CIRCUIT
BOARD
CABINET
MOUNTING
CLIP
CABINET
MOUNTING
CLIP
CONTROL
CIRCUIT
BOARD
BOARD
SUPPORTING
SLOTS
RECEIVER CIRCUIT BOARD
++
AB
pc_mount-001-V1
DETAIL B
ANTENNA AND GROUNDING
LUG INSTALLATION
INSTALLATION WITH RECEIVER CIRCUIT BOARD
Figure 3. Mounting the PC Board and RF Receiver
Section 2: Mounting and Wiring the Control
2–3
Wiring to Keypads
Notes
1. Connect keypads to the control’s keypad terminals
as shown in the Summary of Connections
diagram.
2. Determine wire gauge using the Wiring Run
Chart below.
Supplementary Power (optional)
Connect as shown. Be sure to connect the negative (–)
terminal on the power supply unit to terminal 4 (AUX –)
on the control.
+
+
456 7
SUPPLEMENTARY
POWER SUPPLY
CONTROL TERMINAL STRIP
AUX.
AUX. DATA
IN
DATA
OUT
IMPORTANT:
MAKE THESE
CONNECTIONS
DIRECTLY TO
SCREW
TERMINALS AS
SHOWN.
TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE
TO KEYPAD YEL WIRE
TO KEYPAD GRN WIRE
TO KEYPAD BLK WIRE
TO KEYPAD RED WIRE
TO KEYPAD GRN WIRE
TO KEYPAD YEL WIRE
Figure 4. Using a Supplementary Power Supply
Fixed-Word Display: 6128, 6128RF
Alpha
Display
:
6139
Be sure the keypads are set to the non-addressable
mode (address 31).
Up to 4 keypads may be used in the system.
For single 4-wire runs, determine the current drawn
by all units, then refer to the Wiring Run Chart below
to determine the maximum wire length that can be
safely used for each wire size.
Use supplementary power if the control’s aux. Power
load for all devices exceeds 600mA.
Suggested power supplies:
487-12 supplies 12V, 250mA with battery backup
488-12 supplies 12V, 500mA with battery backup
U
L
Use a UL Listed, battery-backed supply for UL
installations. The battery supplies power to these keypads
in case of AC power loss. The battery-backed power
supply should have enough power to supply the keypads
with the UL required minimum standby power time.
Keypads powered from supplies that do not
have a backup battery
will not function
when AC power is lost. Therefore, be sure to
power at least one keypad from the control's
auxiliary power output.
Wiring Run Chart for Devices* Drawing Aux Power from the Control (12V+ & 12V–)
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Wire Size
50mA or less
100mA 300mA 500mA 600mA
#22 500 ft (152m) 250 ft (76m) 80 ft (24m) 50 ft (15m) 42 ft (13m)
#20 750 ft (228.6m) 380 ft (116m) 130 ft (39.6m) 80 ft (24m) 67 ft (20.4m)
#18 1300 ft (396m) 650 ft (198m) 220 ft (67m) 130 ft (39.6m) 115 ft (35m)
#16 1500 ft (457m) 1000 ft (305m) 330 ft (100.5m) 200 ft (70m) 170 ft (52m)
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, or 4285/4286 VIP Module.
Maximum wire lengths for any device that is home run to the control can also be determined from the Wiring Run Chart, based
on the current draw of that device alone
.
The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if
shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.
VISTA-15/VISTA-15CN Installation and Setup Guide
2–4
Sounder (Bell) Connections
Notes
1. Make sounder connections to alarm output
terminals 3 (+) and 4 (–). For supervised output,
continue with steps 2 and 3.
2. Cut the red Bell Supervision Jumper located
above terminals 2 and 3 on the control board.
3. Connect a 2k ohm resistor across the terminals of
the last sounder.
+
+
2
EXTERNAL ALARM
SOUNDER
TERMINALS ON
CONTROL BOARD
ALARM
OUTPUT
TERMINALS
V15-011-V0
3
4
CUT RED JUMPER ON CONTROL
BOARD TO ENABLE BELL
(SOUNDER) SUPERVISION.
2000
OHM
EOL
RESISTOR
IF BELL SUPERVISION IS ENABLED
(RED JUMPER ON CONTROL BOARD IS CUT),
CONNECT A 2000 OHM RESISTOR ACROSS THE
EXTERNAL SOUNDER AS SHOWN BY THE
DOTTED LINE.
DO NOT CONNECT THE RESISTOR AT THE
ALARM OUTPUT TERMINALS THEMSELVES!
OBSERVE
POLARITY
Figure 5. Sounder Wiring (Supervised)
This control complies with NFPA requirements for
temporal pulse sounding of the notification appliances.
Temporal pulse sounding for a fire alarm consists of: 3
pulses – pause –3 pulses – pause –3 pulses –etc.
The 12VDC sounder output activates when an alarm
occurs.
Total current drawn from this output cannot exceed 2
A (going beyond 2 A will overload the power supply, or
may cause the electronic circuit protecting the sounder
output to trip).
You must install a battery, since the battery supplies
this current.
U
L
Use only UL Listed sounding devices for UL
installations.
Bell supervision is required for fire alarm
installations.
The total current drawn from the alarm output and
the auxiliary power output, combined, cannot
exceed 600 mA. In addition, the sounding device
must be a UL Listed audible signal appliance rated
to operate in a 10.2-13.8 VDC voltage range, and
must be mounted indoors.
Section 2: Mounting and Wiring the Control
2–5
Wiring the AC Transformer
Notes
1321/1321CN Transformer
Connect the 1321/1321CN Transformer to terminals 1 and
2 on the control board. See wiring table at the right for
wire gauge to use.
4300 Transformer
(required If Using Powerline Carrier devices)
1. Connect terminals
1, 3 (AC), and 2 (Ground) to control
board terminals 1, 2, and 25, respectively (see
Figure 5
).
See wiring
table
at the right for wire gauge to use.
2. Wire the other three terminals (Sync, Data, Com) on
the 4300 Transformer. Wires from these terminals must
be connected to a 9-pin connector on the control board
(using a
4142TR Cable
supplied with the 4300
Transformer), as shown In
Figure 5
. These particular
wires can be 24-gauge or larger, and can be run along with
the AC and ground wires to the control panel.
123456789
9-PIN CONNECTOR
ON CONTROL BOARD
BLACK
BLUE
BROWN
GREEN
RED
WHITE
YELLOW
GRAY
VIOLET
4142TR CABLE
1
2
3
4
56
125 2
AC
Earth
Ground
AC
Sync
Data
Com
4300 TRANSFORMER/INTERFACE
TERMINALS
ON CONTROL
BOARD
Figure 6. Connections of 4300 Transformer to Panel
Use caution when wiring the transformer to the
control panel to guard against blowing the fuse inside
the transformer (the fuse is nonreplaceable).
Wiring to the AC transformer must not exceed 250
feet using 16-gauge wire. The voltage reading between
terminals 1 and 2 of the control must not fall below
16.5VAC, or an
AC LOSS
message is displayed.
Do not plug the transformer into the AC outlet while
making any wiring connections to the control. As a
safety precaution, always power down the control
when making such connections.
Wirng Table
Distance from control Wire Gauge
Up to 50 feet #20
50 to 100 feet #18
100 to 250 feet #16
Backup Battery
Notes
1.
Place the 12-volt backup battery in the control
cabinet.
2.
After all connections to the control are completed,
connet the red and black flying leads on the
control board to the battery. Do not attach these
leads to the battery terminals until all
connections are completed.
U
L
Use a 4AH battery or larger for UL installations.
Refer to chart below to calculate the actual battery size
needed.
Table 1.
Auxiliary Device Current Draw Worksheet
DEVICE CURRENT # UNITS TOTAL CURRENT
6128 Keypad 30mA
6139 Keypad 100mA
5881/5882 RF Receiver 35mA
4219 Zone Expander 35mA
4204 Relay Unit
15/180mA
4229 Zone Expander/Relay Unit
35/100mA
4285 VIP Module 160mA
4286 VIP Module 300mA
*
*
*
TOTAL =
Current available from Aux. terminals = 600mA max (500mA max for UL installations)**
* If you are using hardwire devices such as PIRs, refer to the specifications for that particular unit's current draw.
VISTA-15/VISTA-15CN Installation and Setup Guide
2–6
** In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output
combined
must not exceed
600mA.
Figures are for relays OFF/relays ON.
Earth Ground
Notes
Metal Cold Water Pipe
:
Use a noncorrosive metal strap (copper is recommended)
firmly secured to the pipe to which the ground lead is
electrically connected and secured.
AC Power Outlet Ground:
Available from 3-prong, 120VAC, power outlets only. To
test the integrity of the ground terminal, use a 3-wire
circuit tester with neon lamp indicators, such as the
UL
Listed
Ideal Model 61-035
, or equivalent, available at most
electrical supply stores.
The designated earth ground terminal (25) must be
terminated in a good earth ground for the lightning
transient protective devices in this product to be effective.
The examples of good earth grounds listed at the left are
available at most installations.
Section 2: Mounting and Wiring the Control
2–7
Hardwire Zones
Notes
Wiring Burglary and Panic Devices to Zones 1–6
1. Connect sensors/contacts to the hardwired zone terminals
(8 through 17).
2. Connect closed-circuit devices in series in the high (+) side
loop. The EOL resistor must be connected in
series
with the
devices, following the last device.
3. Connect open-circuit devices in parallel across the loop.
The 2000-ohm EOLR must be connected
across
the loop
wires at the last device.
Wiring 2-Wire Smoke Detectors to Zone 1
1. Connect 2-wire smoke detectors across zone 1 terminals 8
(+) and 9 (–). Observe proper polarity when connecting the
detectors.
2. If an
EOL resistor
is presently connected across zone 1
terminals, remove it.
The EOL resistor must be
connected across the loop wires at the last detector.
ZONE 1
2-WIRE SMOKE
DETECTOR
UL NOTE:
IN UL INSTALLATIONS, ONLY ZONE 1
MAY BE USED FOR FIRE.
SMOKE
2000 OHMS
2k EOLR
8
9
Figure 7. Wire Smoke Detector Connected to Zone 1
If the EOLR is not at the end of the loop, the zone
will not be properly supervised, and the system
may not respond to an open-circuit on the zone.
The alarm current provided by zone 1 supports only
one smoke detector in the alarmed state.
U
L
In UL installations, only zone 1 may be used as
a fire zone. In addition, an ADEMCO Model 610–7 must
be used as the end-of-line resistor at the last detector.
COMPATIBLE 2-WIRE SMOKE DETECTORS
Detector Type System Sensor
Model No.
Photoelectric w/heat sensor, direct
wire
2300TB, 2400TH
Photoelectric, direct wire 2400
Photoelectric 2451 w/B401B base
Photoelectric w/heat sensor 2451TH w/B401B
base
Ionization, direct wire 1400
Ionization 1451 w/B401B base
Photoelectric duct detector 2451 w/DH400 base
Ionization duct detector 1451D w/DH400
base H
Low-profile, photoelectric, w/135°F
thermal
2100T
Low-profile, ionization type, direct wire 1100
Wiring 4-Wire Smoke/Combustion Detectors on Zones
2-6
1. Connect 12-volt power for the detectors from Auxiliary
Power terminals 4 and 5 (which interrupts power for fire
alarm reset). Observe proper polarity when connecting
detectors.
2. Connect detectors (including heat detectors, if used) across
terminals of the zone selected (zones 2-6 may be used). All
detectors must be wired in parallel.
+
+
2000
OHMS
EOLR
HEAT
DETECTOR
HEAT
DETECTOR
ZONES 2-6
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B
VIOLET
4-WIRE SMOKE
OR COMBUSTION
DETECTORS
TO HI SIDE OF
SELECTED
TO LO SIDE OF
SELECTED
AUX PWR
OUTPUT
TERMINALS
5
4
+
+
BLK
+
Figure 8. Wire Smoke Detector Connections (Zones 2–6
)
Remove 2000 ohm EOL resistor if connected across
the selected zone terminals. You must connect the
EOL resistor across the loop wires at the last
detector.
To supervise power, we recommend the use of a
System Sensor
No. A77-716B
Supervisory Module.
Compatible 4-Wire Smoke/Combustion
Detectors
System Sensor
1412
4-wire ionization products of
combustion detector
System Sensor
2412
4-wire photoelectric smoke
detector
System Sensor
2412TH
4-wire photoelectric smoke
detector w/135
°
F (57
°
C) heat
detector
System Sensor
A77716B
EOL relay module (supervisory
module for wired 4-wire fire zone).
System Sensor
2112/24T
low-profile 4-wire photoelectric
smoke detector w/135
°
F (57
°
C)
heat detector
VISTA-15/VISTA-15CN Installation and Setup Guide
2–8
4219/4229 Expansion Zones
Notes
1. Connect the module to the control's keypad terminals.
2 .
Set the 4219 or 4229's
DIP switch
for device
address
“1” (switch 2 in the OFF position and switches 3, 4, 5 in the
ON position). Switch 1 determines expansion zone A's
response time (ON = normal response, OFF = fast
response).
You can add 8 wired EOLR zones to the basic control's
6 zones, for a total of 14 wired zones, by using a 4219
Wired Expansion Unit or 4229 Wired Expansion/Relay
Unit.
Connected a 1000 ohm
EOL resistor
across the
terminals of unused expansion zones on the
4219
or
4229
Module).
4219
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4
3
2
1
ZONES
A
B
C
D
F
GH
TAMPER JUMPER
POSITION IN CABINET
(NOT TAMPER PROTECTED)
REMOTE
TAMPER PROTECTED
TB1
TB2
4-PIN CONSOLE PLUG
(CONNECTIONS SAME AS TB2)
1
2
3
4
DATA OUT
TO CONTROL
DATA IN FROM
CONTROL
TERMINATE EACH PROGRAMMED
ZONE WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S LOOP RESISTANCE:
300 OHMS + EOL)
5
8
11
REED
(TAMPER)
SWITCH
2
E
1
3
4 6
7
9
10
12
DIP SWITCH FOR SETTING
ADDRESS AND ZONE A
RESPONSE TIME
Figure 9. Wiring Connections - 4219 Expansion Module
BRN
GRN
BLK
(–) GROUND
RED
(+) 12VDC
YEL
4
3
2
1
ZONES
A
B
C
D
F
GH
DIP SWITCH FOR SETTING
ADDRESS AND ZONE A
RESPONSE TIME
TAMPER JUMPER
POSITION IN CABINET
(NOT TAMPER PROTECTED)
REMOTE
TAMPER PROTECTED
TB1
4229
TB2
WHT
GRY
VIO
BLK
YEL
ORG
NO
NC
C
GND
NO
NC
C
RLY
2
RLY
1
RELAYS SHOWN
DE-ENERGIZED
RELAY
CONNECTOR
RELAY
2
RELAY
1
(TERM 6)
(TERM 4)
(TERM 5)
(TERM 7)
NO C NC
TERMINALS ON
CONTROL PANEL
1
2
3
4
DATA OUT
TO CONTROL
DATA IN FROM
CONTROL
5
8
11
REED
(TAMPER)
SWITCH
2
E
1
3
4 6
7
9
10
12
TERMINATE EACH PROGRAMMED
ZONE WITH 1000 OHM (1K)
END-OF-LINE RESISTOR
(EACH ZONE'S LOOP RESISTANCE:
300 OHMS + EOL)
4229 ADDRESS SETTINGS
SWITCH
NUMBER
("—" means "OFF")
0
1
123456789101112131415
2
ON
ON ON ON ON ON ON ON ON
3
ON ON ON ON ON ON ON ON
4
ON ON ON ON ON ON ON ON
5
ON ON ON ON ON ON ON ON
12345
OFF ON
4-PIN
CONSOLE
PLUG
EITHER OR BOTH
CAN BE USED
SWITCH SHOWN
FOR ADDRESS "0"
Figure 10. Wiring Connections - 4229 Expansion/Relay Module
Section 2: Mounting and Wiring the Control
2–9
Installing the RF Receiver
Notes
1. Set the receiver's DIP switch for device address “00”, as
described in its instructions (all switches to the left, the
“off” position).
2. Mount the receiver noting that the RF receiver can
detect signals from transmitters within a nominal range of
200 feet.
3. Connect the receiver's wire harness to the control's
keypad terminals. Plug the connector at the other end of
the harness into the receiver. Refer to the installation
instructions provided with the receiver for further
installation procedures regarding antenna mounting, etc.
You must use one of the following receivers:
RF Receiver No.of Zones
5881L/5882L Up to 8
5881M/5882M Up to 16
5881H/5882H Up to 26
If you are using a 5804BD, 5827, or 5827BD Wireless
Keypad with the system, you must program a House
ID Code (01-31) in field
24 to establish proper
communication, and the keypad must be set to the
same ID. House ID 00 disables all wireless keypads.
Note the following if the receiver is mounted remotely.
Place the RF receiver in a high, centrally located area
for best reception.
Do not locate the receiver or transmitters on or near
metal objects. This decreases range and/or block
transmissions.
Do not locate the receiver in an area of high
RF
interference (revealed by frequent or prolonged
lighting of the LED in the receiver; random flicker is
OK).
The RF receiver must be at least 10 feet from any
remote keypads to avoid interference from the
microprocessors in those units.
MOUNTING
HOLES
INTERFERENCE
INDICATOR
LED
CIRCUIT BOARD
DIP
SWITCH
ANTENNAS
(INSERT IN
RIGHT-HAND
TERMINALS)
YELLOW
RED
BLACK
GREEN
WIRING OPENING
KNOCKOUT AREA
FOR SURFACE WIRING
TO CONTROL'S
REMOTE KEYPAD
CONNECTION
POINTS.
5882
LOCATION
TO RELEASE CIRCUIT BOARD,
REMOVE SCREWS AND
BEND BACK TABS
NOTE
CIRCUIT BOARD IS MOUNTED IN
CONTROL'S CABINET. GROUNDING
LUGS (2) PROVIDED
MUST
BE INSERTED
IN LEFT-HAND TERMINALS OF ANTENNA
BLOCKS AND SECURED TO CABINET.
(SEE RECEIVER'S AND CONTROL'S
INSTRUCTIONS)
SOCKET
PLUG
MODEL NO. IS INDICATED ON CIRCUIT BOARD
5881-003-V0
Figure 11. 5881/5882 RF Receiver (cover removed)
Installing a 5800TM Module
Notes
1. Mount the 5800TM next to the RF receiver (between 1
and 2 feet from the receiver’s antennas) using its
accompanying mounting brackets. Do not install within
the control cabinet.
2. Connect the 5800TM to the control panel’s keypad
connection terminals as shown on the Summary of
Connections diagram.
3. For additional information refer to the 5800TM’s
instructions.
Use this module is necessary only if you are using one
or more 5827BD Wireless Bi-directional Keypads,
5804 or 5804BD Transmitters (wireless keys).
Do not cut any of the jumpers on the 5800TM when
using it with the VISTA-15/VISTA-15CN.
VISTA-15/VISTA-15CN Installation and Setup Guide
2–10
Installing the Transmitters
Notes
1. To be sure of the transmitter’s signal at the
proposed mounting location is adequate, perform
a Go/No Go Test, described in the
Testing the
System
section.
2. Install transmitters in accordance with the
instructions provided with each.
3. Set 5827 transmitters to the programmed House
ID, using its DIP switches.
Refer to the table of compatible devices at the back of
this manual.
U
L
The 5802MN, 5802MN2, 5804, 5804BD, 5814,
5816TEMP, 5819, 5819S(WHS & BRS), 5827BD, and
5850 transmitters are not intended for use in UL
installations.
Transmitter Battery Life
Batteries in the wireless transmitters may last from 4 to 7 years, depending on the environment, usage, and the
specific wireless device being used. Factors such as humidity, extreme temperatures, as well as large
temperature variations may all reduce the actual battery life in a given installation.
The wireless system can identify a true low-battery situation, thus allowing the dealer or user of the system time
to arrange a change of battery and maintain protection for that given point within the system.
Some transmitters (e.g., 5802, 5802CP, and 5804) contain long-life but nonreplaceable batteries, and no battery
installation is required. At the end of their life, the complete unit must be replaced (and a new serial number
enrolled by the control).
Button-type transmitters (such as 5801, 5802, 5802MN/MN2, 5802CP, and 5804) should be periodically tested for
battery life.
The 5802MN and 5804 Button Transmitters have replaceable batteries.
Do not install batteries in wireless transmitters until you are ready to enroll the transmitters during system
programming. After enrolling, batteries need not be removed.
Jam Detection and Reporting
When field
22, option 4 (in Data Field Descriptions) is selected, a 5800 series receiver detecting a jam condition sends
an
E344
(RF Receiver Jam Detect) Contact ID report to the Central Station. At the same time, a
Rcvr Jam
(alpha
keypads) or
CHECK 90
(fixed-word keypads) message alternates with the present system message on the keypad. When
the jam condition is cleared, a
Restore
message is sent to the CS. Entering a code and OFF restores the keypad display.
The default for this option is 0 (disabled).
Normal use of a 5827 wireless keypad may cause a false RF jam message to be displayed in system
s
that have been programmed for RF Jam Detection.
About 5800 Series Transmitters
Programming Wireless Zones
5800 Series transmitters have built-in serial numbers that you must “enroll” into the system using the
56 or
58 Zone
Programming mode, or input to the control via the downloader. 5800 Series transmitters (except 5827, described
separately) do not have DIP switches.
Program each transmitter's zone number into the system using
56 or
58 mode (see
Section 16: Zone
Programming
). Some transmitters, such as the 5816 and 5817, can support more than one “zone” (referred to as loops
or inputs). On the 5816, for example, the wire connection terminal block is loop 1, the reed contact is loop 2. Each loop
must be assigned a different zone number.
U
L
The 5816 and 5817 transmitters do not have EOL supervision of their loop wiring. Therefore, for UL
Household Burglary installations, the loop wiring may not exceed 3 feet.
For button transmitters (RF “keys”), such as the 5801, 5804, and 5804BD, you must assign a unique zone number to
each individual button used on the transmitter. Each button on the transmitter also has a predesignated loop or input
number, which is automatically displayed on the keypad.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96

ADEMCO Security System VISTA-15CN Installation And Setup Manual

Categoria
Sistemi di controllo accessi di sicurezza
Tipo
Installation And Setup Manual
Questo manuale è adatto anche per

in altre lingue