| 18 DKRCE.PI.RL0.G7.ML
Installation Guide | ERC 213
Parameter Name - ERC 213 Code Min Max Unit
App. 0
(Def.)
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
Others o--
Delay of outputs
at startup
o01 0 600 min 5 5 5 5 5 5 5
DI1 configuration
oFF=not used, Sdc=status display output,
doo=door alarm with resumption, doA=door
alarm without resumption, SCH=main
switch, nig=day/ night mode, rFd=reference
displacement, EAL=external alarm, dEF=defrost,
Pud=pull-down, Sc=condenser sensor
o02 oFF Sc oFF oFF oFF oFF oFF oFF oFF
Serial address o03 0 247 0 0 0 0 0 0 -
Password o05 no 999 no no no no no no no
Sensor type selection
n5=NTC 5 K, n10=NTC 10 K,
Ptc=PTC, Pt1=Pt1000
o06 n5 Pt1 n10 n10 n10 n10 n10 n10 -
Display resolution
0.1=steps of 0.1 °C
0.5=steps of 0.5 °C,
1.0=steps of 1.0 °C
o15 0.1 1.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1
Relay 1 counter
(1 count=100 cycles of operation)
o23 0 999 0 0 0 0 0 0 -
Relay 2 counter
(1 count=100 cycles of operation)
o24 0 999 0 0 0 0 0 0 -
Relay 3 counter
(1 count=100 cycles of operation)
o25 0 999 0 0 0 0 0 0 -
DI2 configuration
oFF=not used, Sdc=status display output,
doo=door alarm with resumption, doA=door
alarm without resumption, SCH=main switch,
nig=day/night mode, rFd=reference
displacement, EAL=external alarm, dEF=defrost,
Pud=pull-down
o37 oFF Pud oFF oFF oFF oFF oFF oFF oFF
Predefined applications o61 AP0 AP6 AP0 AP1 AP2 AP3 AP4 AP5 -
Note: hidden parameters are greyed out
ENGLISH