Haier AP60KS1ERA Operation Manual And Installation Manual

Categoria
Condizionatori d'aria a sistema split
Tipo
Operation Manual And Installation Manual

Questo manuale è adatto anche per

OPERATION MANUAL AND INSTALLATION MANUAL
Please read this manual carefully before installation.
Keep this operation manual for future reference.
CABINET TYPE AIR CONDITIONER
–¨ 1.000
0150508963 C
OPERATION MANUAL AND INSTALLATION MANUAL
Please read this manual carefully before installation.
Keep this operation manual for future reference.
English
Contents
Cautions
Parts and Functions
Operation
Energy Saving
Maintenance
Troubleshooting
Indoor & Outdoor Unit Connection
Installation Procedure
3
5
7
9
10
11
14
15
CABINET TYPE AIR CONDITIONER
–¨ 1.000
3
Cautions
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air
conditioner in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable
materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of
an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the
pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and
contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to
the environment.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping
bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling. Consult
your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services
nearest to your house.
Safety Instructions and Warnings
Before starting the air conditioner, read the information given in the User's Guide carefully. The User's Guide contains very
important observations relating to the assembly, operation and maintenance of the air conditioner.
The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following
instruction.
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Installation shall be done by professional people, don't install unit by yourself.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on
the power cord. Always grip plug firmly and pull straight out from the outlet.
All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of
danger for the user of the air conditioner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes
with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant
spurts out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet
and swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
This appliance is not intended for use by persons (including children) with reducedphysical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by
a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
4
Cautions
The machine is adaptive in following situation
Applicable ambient temperature range:
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC. Please check the circuit diagram
about the fuse replaced.
The wiring method should be in line with the local wiring standard.
The power cable and connecting cable are self-provided. All the cables shall have got the local authentication certificate.
The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should be no less
3mm. Such means for disconnection must be incorporation in the fixed wiring.
The waste battery shall be disposed properly.
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
46/26 C
10/6 C
27 C
15 C
24/18 C
Specifications
The refrigerating circuit is leak-proof.
5
Parts and Functions
–¨ 1.000
6
Parts and Functions
Electrical heating is not available.
Fan only function
(This model has not this function.)
(This model has not this function.)
7
Operation
8
Operation
(This model has not this function.)
Keep proper room temperature
Too cold or too warm is no good to your health, and power
consumption will be increased as well.
Air filter should be periodically cleaned
If air filter is clogged, it will cause poor cooling and heating
efficiency, higher power consumption and even problem
may occur. In cooling operation, water will flow out.
Use Timer effectively
You may use Timer mode to keep a comfortable room temp.
when you wake up or come home from outside.
Avoid direct sunlight and air flow Adjust air flow properly
Proper temp.
8:00
5:00
AM
PM
ON
OFF
9
Energy Saving
Don't spray any paint or insecticide on the unit.Don't splash water directly on indoor unit.
This will cause damage or even fire accident.
This could be
very dangerous
Disconnect power supply Don't touch it with wet hand Don't wash with hot water or solvent to
clean the unit
10
Maintenance
Pull it out from top as shown in Fig.
Wash it with clean water and install it after complete dry.
Air filter cleaning
Use water or vacuum cleaner to clean it. If it is extremely dirty,
wash it with neutral detergent or soap water.
Don't use hot water over 40 C, as this may cause damage to air filter.
Wipe air filter carefully.
Caution:
After season maintenance
Before season maintenance
Let the unit run in Fan mode for half a day in a fine weather to dry completely the unit inside.
Turn off the unit and pull out power plug. Otherwise, there might be certain power consumption
even if the unit is stopped.
Clean air filter and indoor unit, cover outdoor unit after cleaning.
Check if there are obstacles at inlet and outlet of indoor and outdoor unit, whick will reduce unit
efficiency.
Don't fail to attach air filter after making sure it is cleaned. Dust will enter into unit causing
damages or faults if it is running without air filter.
To protect compressor at start, please connect external power supply to the unit 12 hrs prior to
starting. Also please keep the power supply switch ON during the whole season.
Clean it with warm and wet cloth or with neutral detergent, then wipe it dry with clean and soft cloth.
If air conditioner is very dirty, clean it with cloth soaked in neutral detergent, then wipe off the detergent with clean water.
Don't use water higher than 40 C, which will cause discoloring and deformation.
Don't use insecticide or other chemical detergents.
Indoor and outdoor cleaning
11
Troubleshooting
Followings are not problems
Sound of water flowings are not
problems.
Sound of cracking is heard.
Smells are generated.
During operation, white fog or
steam comes out of indoor unit.
In cooling operation, unit switches to fan
operation.
Unit will not restart after stop.
No outlet air or fan speed can't be changed
in dry mode.
In heating operation, water or steam are
blown out of indoor unit.
In heating operation, indoor fan won't stop
even if unit is stopped.
During unit start and operation or at stop, a swishing or gurgling noise may
be heard. This noise is generated by refrigerant flowing in the system.
During unit operation, a cracking noise may be heard. This noise is generated
by the casing expanding or shrinking because of temperatuer changes.
This is because the system circulates smells from the interior air such as
the smell of cigarettes or the painting on the unit.
When unit is running at places like restaurant where dense edible oil fumeis
always exist, this will happen.
To prevent frost from accumulating on indoor heat exchanger, unit will switch
to fan operation for a while and then resume cooling operation.
Though ON/OFF button is set to ON, the unit won't resume cooling, dry or
heating operation in 3 min after it is stopped, this is because of
3-min-delay protection circuit.
Unit will reduce fan speed repeatedly and automatically if room temp. is too
low in dry operation.
This occurs when frost accumulated on the outdoor unit is removed.
(during defrosting operation)
After unit stops, indoor fan will go on running until indoor unit cools down.
Please wait 3 minutes
Won't start?
Before asking services, please firstly check your unit according to following.
If your unit still can't work properly after above mentioned checks, or following problems occur, please stop it immediately
and contact your dealer.
Fuses or circuit breakers often blow out.
Water comes out in cooling/dry operation.
Operation is abnormal or sound is heard.
12
Troubleshooting
Are operation controlls adjusted
correctly as specified?
Are horizontal louvers at up position (in heating mode)?
Poor cooling or heating
Is air filter too dirty?
Any doors or windows left open?
Are there any obstacles at inlet or outlet
grill?
Proper
temp
Is there any direct sunlight in the room?
Poor cooling
If there are unexpected heat sources
in the room?
Too many people in the room?
Air conditioner won't start.
Is power supply switch turned on?
Power supply switch
is not set at ON.
Is city power supply normal?
Is leakage current breaker activated?
This is very dangerous, please
disconnect power supply immediately
and contact your dealer.
Power
failure?
13
Troubleshooting
E
E
E
E
14
Indoor & Outdoor Unit Connection
E
E
E
E
E
E
Tools necessary
1. Screw driver
2. Hacksaw
3. 70mm dia. hole core drill
4. Spanner (dia. 22, 36mm)
5. Spanner (16, 18, 22, 36mm)
6. Pipe cutter
7. Flaring tool
8. Knife
9. Nipper
10. Gas leakage detector or soap water
11. Measuring tape
12. Reamer
13. Refrigerant oil
Installation accessories
Following parts shall be field supplied
Before installation
Installation of outdoor unit
Try to bring the packed unit to the installation place.
When it is inevitable to unpack the unit, be careful not to damage the unit. Wrap it with nylon etc.
After unpacking, be sure to put it with the front side of the unit facing up.
When delivering, don't hold plastic parts like inlet and outlet grill etc.
Selection of outdoor unit installation place
Place strong enough to support the unit and will not cause vibration and noise.
Place where discharged wind and noise doesn't cause a nuisance to the neighbors.
Place where is less affected by rain or direct sunlight and is sufficiently ventilated,
or to install a shield.
Place with enough space for smooth air flow.
Fixing of the outdoor unit
Fix outdoor unit using M10 bolt to concrete floor horizontally.
If installed on the wall or on top of a roof, bracket should be fixed securely
to resist earthquake or storms.
Use rubber pad during installation against unit vibration.
Delivery
Facing up
over 10cm
over
10cm
over
15cm
over 60cm
over 30cm
15
Installation Procedure
Installation Procedure
Part name
Adhesive tape
Pipe clip
Connecting hose
Insulation material
Putty
Drain hose
Installation Preparation
Outdoor Unit
16
Installation Procedure
Indoor Unit
Installation of indoor unit
Place where it is easy to route drainage pipe and outdoor piping.
Place away from heat source and with less direct sunlight.
Place where cool and warm air could be delivered evenly to every corner of the room.
Place near power supply socket. Leave enough space around the unit (refer to installation drawings).
Wall hole should be decided according to installtion place
and piping direction. (refer to installation drawings)
3.Fixing of indoor unit
INDOOR SIDE OUTDOOR SIDE
wall hole
wall thickness
( Cross section of wall hole )
70mm
With the unit set up vertically, fix the fitting metal to the unit
with screws, then fix the fitting metal to the wall with cement
nail and washer, as shown right:
Selection of indoor unit installation place
1.Position of the wall hole
Drill a hole of 70mm dia. with a little slope towards outside.
Install piping hole cover and seal it with putty after installation.
2.Making a wall hole
Moreover, if wanting to fix the unit more firmly, you should
fix the bottom panel to the ground with concrete bolts, as
shown right:
330
2- 10 hole
Screw
Fitting metal
Cement nail
Fitting hole
Bottom Panel
4- 14 hole 30 depth
260
130
79202
(202)
(79)
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down
waves in drain hose.
If humidity is high, drain pipe( especially in room and indoor unit ) must
be covered with insulation material.
Indoor unit
Slope
Good
Up
Down
Bad
Connect the connecting pipe and inlet / outlet liquid pipe according to the piping method.
Vacuumizing
Discharge the air out of the indoor unit and the refrigerant pipe by vacuumizing.
Fasten all the nuts of the indoor and outdoor pipes to make these parts out of leakage.
Under the condition of the complete close of the indoor and outdoor valve center (both liquid and gas side), dismount
the service valve cap. Vacuumizing through the charge mouth of the service valve.
After vacuumizing, fasten the service valve and dismount the cap of the big and small stop valve, then loosen the stop
valve center completely and fasten the big and small stop valve.
Pipe cutting and flaring
Be sure to carry out deburring after pipe cutting with a pipe cutter.
Insert flaring tool to make a flare.
A
Flaring tool
17
Installation Procedure
Piping Connection
Piping connection of indoor unit
1.Arrangement of piping and drainage pipe
Cut away, with a hammer or a saw, the lid for piping according to
piping direction.
According to the piping method, connect the piping on indoor unit with union of
connecting pipe.
Arrange the piping as per the wall hole and bind drain hose, connecting electric
cable and piping together with polyethylene tape.
Insert the bound piping, connecting electric cable and drain hose through wall hole
to connect with outdoor unit.
Insulation material
Copper tube
Drain hose
Connecting electric
cable for indoor and
outdoor unit
Apply refrigerant oil at half union and flare nut.
To bend a pipe, give the roundness as large as possible not to crash the pipe.
When connecting pipe, hold the pipe centre to centre then screw nut on by hand, refer to Fig.
Be careful not to let sundries, such as sands enter the pipe.
Forced fastening without centering may damage the threads and cause a gas leakage.
Pipe dia.
Dimension A
Liquid pipe
Gas pipe
1.0 ~ 1.8(mm)
1.4 ~ 2.2(mm)
9.52mm (3/8")
19.05mm (3/4")
Fastening torque
32.7-39.9N.m
97.2-118.6N.m
Correct
Lean Damaged flare Crack Partial Too outside
Incorrect
After opening inlet grill, you will see a control box as shown in the
Fig. Remove the cover before wiring work.
Connecting method
2.Arrangement of drain hose
Piping connection of outdoor unit.
(1)
(2)
(3)
control box
SLEEP
ON/OFF
MODE
FAN
SET
TEMP
HUMI
HEALTH
TIMER
TEMP+ TEMP- HEALTH
18
Installation Procedure
Electrical wiring
Note:
Electrical wiring must be done by qualified person.
The power supply connects from the outdoor unit.
The connecting cable and power cable are self-provided.
Use copper wire only.
Air conditioner must use an exclusive line (over 30A)
When installing air conditioner in a wet place, try to use a circuit breaker against current leakage.
When installing in other places, use circuit breaker as far as possible.
The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should be no less
than 3 mm.
Such means for disconnection must be incorporation in the fixed wiring
Wiring of indoor unit
Insert the cable from outside the wall hole where piping already exist.
Pull it out from front.
Loosen terminal screws and insert cable end fully into terminal block,
then tighten it.
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
Wiring of outdoor unit
Insert the cable from inside the wall hole where piping already exists.
Pull it out from front.
Loose terminal screw and insert cable end fully into terminal block,
then tighten it.
Pull the cable gently to make sure it is tight.
Replace cover after wiring.
OK NO
terminal block
table clamp
Note:
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal blocks. Incorrect wiring may
damage air conditioner's controller or cause operation failure.
The parameter of connecting cable is H05RN-F 4G 2.5mm
2
.
The parameter of the power cable should be over H07RN-F 5G 4.0mm
2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102

Haier AP60KS1ERA Operation Manual And Installation Manual

Categoria
Condizionatori d'aria a sistema split
Tipo
Operation Manual And Installation Manual
Questo manuale è adatto anche per

in altre lingue