Thank you for purchasing this Samsung air conditioner.
Before operating this unit, please read this manual carefully and retain it for future
reference.
2
Disassembly and Reassembly
Repairs must be carreid out by trained professional.
For any repairs, please contact our service provider or independent qualified professional.
AE200RNW*EG / AE260RNW*EG / AE260RNW*GG
No Parts Procedure Remark
1 Electrical
equipment parts
1) Remove ** screws from the Cabinet.
(Use + Screw Driver)
2) Remove the 4 screws and then
separate the Cover Control Box part.
(Use + Screw Driver)
3) Remove the Power, Pump, 3way valve,
Flow sensor, Booster Heater, Back-up
Heater, Sensor connector of Assy PCB.
3
No Parts Procedure Remark
4) Remove the 3 screws from the front
part..
5) Remove the 2 screw and then open the
cover in the middle position of water tank
6)Remove the wire of the thermostat and
booster heater
4
Disassembly and Reassembly
No Parts Procedure Remark
2 Expansion Vessel 7) Remove the 2 screw from the front
parts
8) Separate the pipe connected expansion
vessel by 2 nut joints.
3 Pump 9) Disconnect power and communication
connection
10) Separate the pipe connected Pump by
2 nut joints.
4 Flow sensor 11) Separate the pipe connected flow sen
-
sor by 2 bracket holder.
5
No Parts Procedure Remark
5 Back up Heater 12) Remove the 4 screw front the cabi top
parts
13) Separate the pipe connected Back up
heater by 2 nut joints.
6 3way Valve 14) Separate the pipe connected 3way
valve by 3 bracket holder
7 Anode bar 15) Separate the pipe connected anode
bar by 1 nut joint from top of the tank
6
Disassembly and Reassembly
No Parts Procedure Remark
8 Plate Heat
Exchanger
16) Remove the 2 screw from the bracket valve
17) Remove the 2 screw front the cabi top sub
18) Separate the pipe connected Assy plate
heat exchanger by 2 nut joint
7
COMMISSION REGULATION (EU) No 813/2013
I)
A Model(s) : AE040RXEDEG / AE200RNWSEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
5 kW P
Seasonal space heating
energy efficiency
s
127 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 4,4 kW
-
 COPd
(S)
2,10 -
 Pdh 2,7 kW  COPd
(S)
3,10 -
 Pdh 1,7 kW  COPd
(S)
4,46 -
 Pdh 1,9 kW  COPd
(S)
5,72 -
T Tj = bivalent temperature Pdh 4,4 kW T Tj = bivalent temperature COPd
(S)
2,10 -
U
Tj = operation limit
temperature
Pdh 4,2 kW U
Tj = operation limit
temperature
COPd
(S)
1,51 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 0,8 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 2400 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/58 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
120 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 853 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
8
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE060RXEDEG / AE200RNWSEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
6 kW P
Seasonal space heating
energy efficiency
s
129 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 5,3 kW
-
 COPd
(S)
2,00 -
 Pdh 3,2 kW  COPd
(S)
3,23 -
 Pdh 2,1 kW  COPd
(S)
4,47 -
 Pdh 1,9 kW  COPd
(S)
5,72 -
T Tj = bivalent temperature Pdh 5,3 kW T Tj = bivalent temperature COPd
(S)
2,00 -
U
Tj = operation limit
temperature
Pdh 5,0 kW U
Tj = operation limit
temperature
COPd
(S)
1,80 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 1,1 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 2580 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/60 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
120 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 853 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
9
A Model(s) : AE090RXEDEG / AE200RNWSEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
8 kW P
Seasonal space heating
energy efficiency
s
127 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 7,1 kW
-
 COPd
(S)
1,76 -
 Pdh 4,3 kW  COPd
(S)
3,23 -
 Pdh 2,8 kW  COPd
(S)
4,62 -
 Pdh 2,6 kW  COPd
(S)
5,88 -
T Tj = bivalent temperature Pdh 7,1 kW T Tj = bivalent temperature COPd
(S)
1,76 -
U
Tj = operation limit
temperature
Pdh 4,9 kW U
Tj = operation limit
temperature
COPd
(S)
1,35 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 3,1 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 3960 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/64 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
119 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 860 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
10
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE040RXEDEG / AE260RNWSEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
5 kW P
Seasonal space heating
energy efficiency
s
127 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 4,4 kW
-
 COPd
(S)
2,10 -
 Pdh 2,7 kW  COPd
(S)
3,10 -
 Pdh 1,7 kW  COPd
(S)
4,46 -
 Pdh 1,9 kW  COPd
(S)
5,72 -
T Tj = bivalent temperature Pdh 4,4 kW T Tj = bivalent temperature COPd
(S)
2,10 -
U
Tj = operation limit
temperature
Pdh 4,2 kW U
Tj = operation limit
temperature
COPd
(S)
1.51 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 0,8 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 2400 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/58 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
123 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1362 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
11
A Model(s) : AE060RXEDEG / AE260RNWSEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
6 kW P
Seasonal space heating
energy efficiency
s
129 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 5,3 kW
-
 COPd
(S)
2,00 -
 Pdh 3,2 kW  COPd
(S)
3,23 -
 Pdh 2,1 kW  COPd
(S)
4,47 -
 Pdh 1,9 kW  COPd
(S)
5,72 -
T Tj = bivalent temperature Pdh 5,3 kW T Tj = bivalent temperature COPd
(S)
2,00 -
U
Tj = operation limit
temperature
Pdh 5,0 kW U
Tj = operation limit
temperature
COPd
(S)
1,80 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 1,1 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 2580 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/60 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
123 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1362 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
12
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE090RXEDEG / AE260RNWSEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
8 kW P
Seasonal space heating
energy efficiency
s
127 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 7,1 kW
-
 COPd
(S)
1,76 -
 Pdh 4,3 kW  COPd
(S)
3,23 -
 Pdh 2,8 kW  COPd
(S)
4,62 -
 Pdh 2,6 kW  COPd
(S)
5,88 -
T Tj = bivalent temperature Pdh 7,1 kW T Tj = bivalent temperature COPd
(S)
1,76 -
U
Tj = operation limit
temperature
Pdh 4,9 kW U
Tj = operation limit
temperature
COPd
(S)
1,35 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 3,1 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 3960 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/64 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
128 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1309 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
13
A Model(s) : AE090RXEDGG / AE260RNWSGG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
8 kW P
Seasonal space heating
energy efficiency
s
127 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 7,1 kW
-
 COPd
(S)
1,76 -
 Pdh 4,3 kW  COPd
(S)
3,23 -
 Pdh 2,8 kW  COPd
(S)
4,62 -
 Pdh 2,6 kW  COPd
(S)
5,88 -
T Tj = bivalent temperature Pdh 7,1 kW T Tj = bivalent temperature COPd
(S)
1,76 -
U
Tj = operation limit
temperature
Pdh 4,9 kW U
Tj = operation limit
temperature
COPd
(S)
1,35 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 3,1 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 3960 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/64 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
128 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1309 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
14
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE050RXYDEG / AE200RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
5 kW P
Seasonal space heating
energy efficiency
s
125 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 4,4 kW
-
 COPd
(S)
2,16 -
 Pdh 2,7 kW  COPd
(S)
3,17 -
 Pdh 1,7 kW  COPd
(S)
4,03 -
 Pdh 1,7 kW  COPd
(S)
4,73 -
T Tj = bivalent temperature Pdh 4,4 kW T Tj = bivalent temperature COPd
(S)
2,16 -
U
Tj = operation limit
temperature
Pdh 4,2 kW U
Tj = operation limit
temperature
COPd
(S)
2,00 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 0,8 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 3060 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/61 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
115 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 890 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
15
A Model(s) : AE080RXYDEG / AE200RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
8 kW P
Seasonal space heating
energy efficiency
s
126 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 7,1 kW
-
 COPd
(S)
1,90 -
 Pdh 4,3 kW  COPd
(S)
3,11 -
 Pdh 2,8 kW  COPd
(S)
4,55 -
 Pdh 2,4 kW  COPd
(S)
5,77 -
T Tj = bivalent temperature Pdh 7,1 kW T Tj = bivalent temperature COPd
(S)
1,90 -
U
Tj = operation limit
temperature
Pdh 6,8 kW U
Tj = operation limit
temperature
COPd
(S)
1,66 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 1,2 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 3960 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/63 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
115 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 890 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
16
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE120RXYDEG / AE200RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
12 kW P
Seasonal space heating
energy efficiency
s
138 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 10,6 kW
-
 COPd
(S)
2,16 -
 Pdh 6,5 kW  COPd
(S)
3,45 -
 Pdh 4,2 kW  COPd
(S)
4,57 -
 Pdh 4,4 kW  COPd
(S)
6,12 -
T Tj = bivalent temperature Pdh 12,0 kW T Tj = bivalent temperature COPd
(S)
1,96 -
U
Tj = operation limit
temperature
Pdh 12,0 kW U
Tj = operation limit
temperature
COPd
(S)
1,96 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -10  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup - kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 5940 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
44/64 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
110 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 930 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
17
A Model(s) : AE160RXYDEG / AE200RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
16 kW P
Seasonal space heating
energy efficiency
s
138 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 14,2 kW
-
 COPd
(S)
2,06 -
 Pdh 8,6 kW  COPd
(S)
3,31 -
 Pdh 5,5 kW  COPd
(S)
5,23 -
 Pdh 4,5 kW  COPd
(S)
6,57 -
T Tj = bivalent temperature Pdh 14,2 kW T Tj = bivalent temperature COPd
(S)
2,06 -
U
Tj = operation limit
temperature
Pdh 14,0 kW U
Tj = operation limit
temperature
COPd
(S)
1,82 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 2,0 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 7080 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
44/66 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile L AV Water heating energy efficiency
wh
110 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 930 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
18
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE080RXYDEG / AE260RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
8 kW P
Seasonal space heating
energy efficiency
s
126 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 7,1 kW
-
 COPd
(S)
1,90 -
 Pdh 4,3 kW  COPd
(S)
3,11 -
 Pdh 2,8 kW  COPd
(S)
4,55 -
 Pdh 2,4 kW  COPd
(S)
5,77 -
T Tj = bivalent temperature Pdh 7,1 kW T Tj = bivalent temperature COPd
(S)
1,90 -
U
Tj = operation limit
temperature
Pdh 6,8 kW U
Tj = operation limit
temperature
COPd
(S)
1,66 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 1,2 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 3960 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
40/63 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
123 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1362 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
19
A Model(s) : AE120RXYDEG / AE260RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
12 kW P
Seasonal space heating
energy efficiency
s
138 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 10,6 kW
-
 COPd
(S)
2,16 -
 Pdh 6,5 kW  COPd
(S)
3,45 -
 Pdh 4,2 kW  COPd
(S)
4,57 -
 Pdh 4,4 kW  COPd
(S)
6,12 -
T Tj = bivalent temperature Pdh 12,0 kW T Tj = bivalent temperature COPd
(S)
1,96 -
U
Tj = operation limit
temperature
Pdh 12,0 kW U
Tj = operation limit
temperature
COPd
(S)
1,96 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -10  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup - kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 5940 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
44/64 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
117 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1432 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
20
COMMISSION REGULATION (EU) No 813/2013
I)
ECODESIGN REQUIREMENTS FOR HEAT PUMP SPACE HEATERS AND HEAT PUMP COMBINATION HEATERS
II)
A Model(s) : AE160RXYDEG / AE260RNWMEG
B Air-to-water heat pump : yes
C Water-to-water heat pump : no
D Brine-to-water heat pump : no
E Low-temperature heat pump : no
F Equipped with a supplementary heater : yes
G Heat pump combination heater : yes
H
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low-temperature heat pump, parameters shall be
declared for low-temperature application.
I Parameters shall be declared for average climate conditions.
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
Item
(J)
Symbol
(K)
Value
(L)
Unit
(M)
N
Rated heat output
(*)
Prated
(o)
16 kW P
Seasonal space heating
energy efficiency
s
138 %
Q
Declared capacity for heating for part load at indoor temperature 20 °C and
outdoor temperature T j
R
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
-
 Pdh 14,2 kW
-
 COPd
(S)
2,06 -
 Pdh 8,6 kW  COPd
(S)
3,31 -
 Pdh 5,5 kW  COPd
(S)
5,23 -
 Pdh 4,5 kW  COPd
(S)
6,57 -
T Tj = bivalent temperature Pdh 14,2 kW T Tj = bivalent temperature COPd
(S)
2,06 -
U
Tj = operation limit
temperature
Pdh 14,0 kW U
Tj = operation limit
temperature
COPd
(S)
1,82 -
V
For air-to-water heat pumps

Pdh - kW V
For air-to-water heat pumps

COPd
(S)
- -
W Bivalent temperature Tbiv -7  X
For air-to-water heat pumps:
Operation limit temperature
TOL -10 
Y
Cycling interval capacity for
heating
Pcych - kW Z Cycling interval efficiency COPcyc
(AA)
- -
AB Degradation co-efficient
(**)
Cdh 0,9 - AC
Heating water operating limit
temperature
WTOL - 
AD Power consumption in modes other than active mode AE Supplementary heater
AF Off mode P
OFF
0,022 kW N Rated heat output
(*)
Psup 2,0 kW
AG Thermostat-off mode P
TO
0,022 kW
AJ Type of energy input Electrical
(AK)
AH Standby mode P
SB
0,022 kW
AI Crankcase heater mode P
CK
0,000 kW
AL Other items AL Other items
AM Capacity control variable
(AN)
AO
For air-to-water heat pumps :
Rated air flow rate, outdoors
- 7080 m
3
/h
(AP)
AQ
Sound power level, indoors/
outdoors
L
WA
44/66 dB
AS
For water-/brine-to-water
heat pumps: Rated brine or
water flow rate, outdoor heat
exchanger
- - m
3
/h
(AP)
AR Emissions of nitrogen oxides NOx - mg/kWh
AT For heat pump combination heater AT For heat pump combination heater
AU Declared load profile XL AV Water heating energy efficiency
wh
117 %
AW Daily electricity comsumption Q
elec
- kWh AX Daily fuel consumption Q
fuel
- kWh
AY Annual electricity consumption AEC 1432 kWh AY Annual electricity consumption AEC - GJ
AZ Contact details
Samsung Electronics, PO Box 12987, Blackrock, Co. Dublin, Ireland
or Blackbushe Business Park, Yateley, Gu46 6GG, UK
BA
(*)
For heat pump space heaters and heat pump combination heaters, the rated that output Prated is equal to the design load for heating Pdesignh, and the rated heat output of a supplementary heater
Psup is equal to the supplementary capacity for heating sup(Tj).
BB
(**)
If Cdh is not determined by measurement then the default degradation coefficient is Cdh = 0,9.
BC
1)
Precautions as described in the installation/user manual must be taken when assembling, installing and maintaining this product.
BD
2)
If you are a professional looking for information on non-destructive disassembly, dismantling and battery removability, please send an email to: [email protected]om
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52