Trox X-AIR-CP Manuale utente

Categoria
Termostati
Tipo
Manuale utente

Questo manuale è adatto anche per

X-AIRCONTROL
Zone control systems
Commissioning and service manual
Read the instructions prior to performing any task!
GB/en
A00000063012, 2, GB/en
© TROX GmbH 2017
TROX GmbH
Heinrich-Trox-Platz
47504 Neukirchen-Vluyn, Germany
Germany
Telephone: +49 2845 202-0
Fax: +49 2845 202-265
Email: E-mail: [email protected]
Internet: www.trox.de
11/2021
X-AIRCONTROL Zone control systems
2
About this manual
This manual enables operating or service personnel to
use the X-AIRCONTROL zone control system safely
and efficiently.
The manual must be kept near the zone control system
to be available for use at all times.
This manual is intended for use by qualified electricians
and network administrators.
It is essential that these individuals (
Ä
1.4 ‘Personnel
requirements’ on page 7 ) read and fully understand
this manual before starting any work. The basic prereq-
uisite for safe working is to comply with the safety notes
and all instructions in this manual.
The local regulations for health and safety at work and
the general safety regulations for the area of application
of the zone control system also apply.
Illustrations in this manual are mainly for information
and may differ from the actual design.
Other applicable documentation
In addition to these instructions, the following docu-
ments apply:
Order confirmation
Product drawings
Data sheets for components from other suppliers, if
any
Additional drawings, if any
X-AIRCONTROL operating manual
X-AIRCONTROL installation manual
X-CUBE operating manual
X-CUBE installation manual
X-CUBE compact operating manual
X-CUBE compact installation manual
Installation and commissioning manual for X-AIR-
CONTROL accessories
Volume flow controller installation manual
Volume flow controller operating manual
TROX Technical Service
To ensure that your request is processed as quickly as
possible, please keep the following information ready:
Product name
TROX order number
Delivery date
Brief description of the fault
Online www.troxtechnik.com
Phone +49 2845 202-400
Copyright
This document, including all illustrations, is protected by
copyright and pertains only to the corresponding
product.
Any use without our consent may be an infringement of
copyright, and the violator will be held liable for any
damage.
This applies in particular to:
Publishing content
Copying content
Translating content
Microcopying content
Saving content to electronic systems and editing it
Limitation of liability
The information in this manual has been compiled with
reference to the applicable standards and guidelines,
the state of the art, and our expertise and experience of
many years.
The manufacturer does not accept any liability for dam-
ages resulting from:
Non-compliance with this manual
Incorrect use
Operation or handling by untrained individuals
Unauthorised modifications
Technical changes
Use of non-approved replacement parts
The actual scope of delivery may differ from the infor-
mation in this manual for bespoke constructions, addi-
tional order options or as a result of recent technical
changes.
The obligations agreed in the order, the general terms
and conditions, the manufacturer's terms of delivery,
and the legal regulations in effect at the time the con-
tract is signed shall apply.
We reserve the right to make technical changes.
Warranty claims
The provisions of the respective general delivery terms
apply to warranty claims. For purchase orders placed
with TROX GmbH, these are the regulations in section
"Vl. Warranty claims" of the Delivery Terms of TROX
GmbH, see www.trox.de/en/ .
Supplemental directives
X-AIRCONTROL Zone control systems 3
1 Safety ................................................................ 6
1.1 Symbols used in this manual ..................... 6
1.2 Correct use ................................................ 6
1.3 System owner's responsibility ................... 7
1.4 Personnel requirements ............................ 7
1.5 Work area hazards .................................... 8
1.5.1 Electric shock hazard ............................. 8
1.5.2 Risks from rotating parts ........................ 8
1.5.3 Risks from hot surfaces .......................... 8
1.5.4 Health risk due to hygiene issues ........... 8
1.5.5 Incorrect troubleshooting ........................ 8
1.6 Personal protective equipment .................. 8
2 X-AIRCONTROL system description ........... 10
2.1 System variants ....................................... 10
2.1.1 Single room control (stand-alone) ........ 10
2.1.2 Control of up to 25 rooms ..................... 12
2.1.3 Control with 5 zone masters ................. 13
2.1.4 Control of up to 4 rooms with an X-
CUBE compact ..................................... 14
2.2 System components ................................ 15
2.2.1 Zone master ......................................... 15
2.2.2 Zone modules ....................................... 19
2.2.3 Room control panel X-AIR-CP-2T ........ 31
2.2.4 Room control panel X-AIR-CP-TS ........ 33
2.2.5 Sensors ................................................ 34
3 Setting up system components on the web-
server .............................................................. 45
3.1 Configuring the network access .............. 45
3.2 Start screen functions .............................. 46
3.3 Selecting a language ............................... 47
3.4 Logging in to the webserver .................... 48
3.5 Setting date and time on the webserver .. 49
3.6 Displaying the service screen .................. 49
3.7 Zone overview ......................................... 50
3.8 Configuring zone modules ....................... 51
3.8.1 Activating the device detection mode ... 51
3.8.2 Configuring actuators and sensors ....... 53
3.8.3 Setting the volume flow rate ................. 54
3.8.4 Checking the volume flow rate ............. 54
3.8.5 Setting up a supply branch ................... 55
3.8.6 Setting up an extract branch ................ 56
3.8.7 Zone grouping ...................................... 57
3.8.8 Hotel mode ........................................... 58
3.8.9 Setting zone values .............................. 58
3.8.10 Configuring the zone master .............. 65
3.8.11 Summer and winter compensation ..... 71
3.8.12 Network connection settings .............. 71
3.8.13 Firmware update ................................ 72
3.8.14 Displaying a zone overview ................ 73
4 Configuring system components on the
control panel .................................................. 74
4.1 Switching the control panel on ................ 74
4.2 Start screen functions .............................. 74
4.3 Setting up the X-AIR-CP-2T control panel
.................................................................. 76
4.3.1 Password entry ..................................... 76
4.3.2 Selecting a language ............................ 76
4.3.3 Setting the date .................................... 76
4.3.4 Setting the time .................................... 77
4.3.5 Showing or hiding the main menu ........ 77
4.4 Configuring a zone module ..................... 78
4.4.1 Setting the configuration mode ............. 78
4.4.2 Activating a frost or window contact ..... 78
4.4.3 Setting an override timeout .................. 79
4.4.4 Setting up schedules ............................ 79
4.4.5 Setting room data ................................. 82
4.4.6 Setting the volume flow rate for a room
............................................................... 82
4.4.7 Setting the screen saver activation time
............................................................... 83
4.4.8 Setting PI values .................................. 83
4.5 Using the zone module ............................ 84
4.5.1 Setting the volume flow rate ................. 84
4.5.2 Setting a temperature setpoint value .... 85
4.6 Viewing system settings .......................... 85
4.6.1 Viewing room air temperatures ............. 85
4.6.2 Viewing the volume flow rate for a room
............................................................... 86
4.6.3 Viewing system information .................. 86
4.6.4 Help ...................................................... 86
4.6.5 Displaying alarms ................................. 87
5 Commissioning X-AIRCONTROL ................. 88
5.1 Commissioning a stand-alone zone
module ..................................................... 88
5.2 Commissioning a zone module on a zone
master ...................................................... 88
6 Integrating X-AIRCONTROL with a central
BMS ................................................................. 90
7 Connecting X-AIRCONTROL to an air han-
dling unit (AHU) ............................................. 91
8 Setting up MP bus or Modbus actuators ..... 92
8.1 Addressing MP bus or Modbus actuators
.................................................................. 92
8.2 LEDs on MP bus or Modbus actuators .... 92
8.3 Configuring MP bus or Modbus actuators
.................................................................. 92
9 Troubleshooting ............................................ 96
9.1 Safe troubleshooting ............................... 96
9.2 Alarms displayed on the control panel .... 96
9.3 Alarms displayed on the webserver ...... 100
Table of contents
X-AIRCONTROL Zone control systems4
10 Wiring documents ....................................... 104
10.1 Zone master ........................................ 104
10.2 Zone module X-AIR-ZMO-MP ............. 105
10.3 Zone module X-AIR-ZMO-MOD .......... 106
10.4 Zone module X-AIR-ZMO-ANA ........... 107
11 Index.............................................................. 108
Table of contents
X-AIRCONTROL Zone control systems 5
1 Safety
1.1 Symbols used in this manual
Safety notes
Symbols are used in this manual to alert readers to
areas of potential hazard. Signal words express the
degree of the hazard.
Comply with all safety instructions and proceed carefully
to avoid accidents, injuries and damage to property.
DANGER!
Imminently hazardous situation which, if not avoided,
will result in death or serious injury.
WARNING!
Potentially hazardous situation which, if not avoided,
may result in death or serious injury.
CAUTION!
Potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
NOTICE!
Potentially hazardous situation which, if not avoided,
may result in property damage.
ENVIRONMENT!
Environmental pollution hazard.
Tips and recommendations
Useful tips and recommendations as well as informa-
tion for efficient and fault-free operation.
Specific safety notes
The following symbols are used in safety notes to alert
you to specific hazards:
Warning signs Type of danger
Warning – danger zone.
Additional markers
In order to highlight instructions, results, lists, refer-
ences and other elements, the following markers are
used in this manual:
Marker Explanation
1., 2., 3. ...
Step-by-step instructions
ðResults of actions
References to sections in this
manual and to other applicable
documents
Lists without a defined sequence
[Switch] Operating elements (e.g. push but-
tons, switches), display elements
(e.g. LEDs)
‘Display’ Screen elements (e.g. buttons or
menus)
1.2 Correct use
The X-AIRCONTROL zone control system consists of a
zone master and several zone modules plus sensors; it
is designed exclusively for the configuration, adjustment
and monitoring of ventilation and air conditioning sys-
tems in buildings and in individual rooms.
Incorrect use
WARNING!
Danger due to incorrect use!
Incorrect use of X-AIRCONTROL can lead to dan-
gerous situations.
Do not use the system as a replacement for
required regular inspections, i.e. do not skip
inspections that are stipulated in building regula-
tions.
Do not use the system for fire protection or
smoke extract purposes.
Do not use the system in rooms with explosive
gases.
Do not use the system in wet areas.
Do not use the system with sensors or accesso-
ries provided by others.
Do not use the signals of the volt-free outputs for
safety functions.
Safety
Correct use
X-AIRCONTROL Zone control systems6
1.3 System owner's responsibility
System owner
The system owner is a natural or legal person who for
commercial or business purposes owns or manages X-
AIRCONTROL or allows third parties to use or operate
it, but continues to bear legal responsibility for the safety
of users, staff or third parties while the product is in use.
System owner's obligations
The system is intended for commercial use. The system
owner is therefore subject to the legal obligations of
occupational health and safety regulations.
In addition to the safety notes in this manual, the appli-
cable regulations for safety, accident prevention and
environmental protection must also be complied with.
In particular:
The system owner must be aware of the applicable
occupational health and safety regulations and carry
out a risk assessment to determine any additional
hazards that may exist or result from the specific
working conditions at the installation location of X-
AIRCONTROL. The system owner has to create
operating instructions for X-AIRCONTROL that
reflect the results of this risk assessment.
The system owner has to ensure, throughout the
entire operating period of X-AIRCONTROL, that
these operating instructions conform to applicable
standards and guidelines; in case of any deviation,
the system owner has to adapt the instructions.
The system owner must name responsible persons
for commissioning and service of the system.
The system owner has to ensure that all individuals
who handle or use X-AIRCONTROL have read and
understood this manual.
The system owner must regularly provide training
for the personnel and inform them of any dangers.
The system owner must provide the employees with
the required personal protective equipment.
The system owner must have all safeguards tested
regularly to ensure that they are functional and com-
plete.
The system owner must observe the local fire regu-
lations.
1.4 Personnel requirements
Qualification
WARNING!
Danger of injury or risk of damage to property
due to insufficiently qualified individuals!
Insufficiently qualified individuals are not aware of
the risks involved in working with this system and its
components and are hence likely to put themselves
or others into danger, causing severe or fatal injuries.
Have any work carried out only by qualified per-
sonnel.
Keep insufficiently qualified individuals away
from the work area.
The work described in this manual has to be carried out
by individuals with the qualification, training, knowledge
and experience described below:
HVAC technician
HVAC technicians are individuals who have sufficient
professional or technical training in the field they are
working in to enable them to carry out their assigned
duties at the level of responsibility allocated to them and
in compliance with the relevant guidelines, safety regu-
lations and instructions. HVAC technicians are individ-
uals who have in-depth knowledge and skills related to
HVAC systems; they are also responsible for the profes-
sional completion of the work under consideration.
HVAC technicians are individuals who have sufficient
professional or technical training, knowledge and actual
experience to enable them to work on HVAC systems,
understand any potential hazards related to the work
under consideration, and recognise and avoid any risks
involved.
Network administrator
Network administrators design, install, configure and
maintain the IT infrastructure in companies or organisa-
tions.
Skilled qualified electrician
Skilled qualified electricians are individuals who have
sufficient professional or technical training, knowledge
and actual experience to enable them to work on elec-
trical systems, understand any potential hazards related
to the work under consideration, and recognise and
avoid any risks involved.
Any work has to be carried out by individuals who
can be expected to carry out their assigned duties
reliably. Individuals whose reaction time is delayed
due to alcohol, drugs or other medication must not
carry out any work.
Safety
Personnel requirements
X-AIRCONTROL Zone control systems 7
Passwords
Some software functions are password protected to pre-
vent unauthorised individuals from entering or changing
data (
Ä
3.4 ‘Logging in to the webserver’
on page 48 ,
Ä
4.3.1 ‘Password entry’
on page 76 ).
1.5 Work area hazards
1.5.1 Electric shock hazard
Electric current
DANGER!
Danger of death due to electric current!
Danger of electric shock! Do not touch any live com-
ponents! Damaged insulation or damaged parts are
a life threatening hazard.
Only skilled qualified electricians must work on
the electrical systems.
If the insulation is damaged, disconnect the
power supply immediately and have the insula-
tion repaired.
Before you start any service jobs, ensure that no
voltage is present.
Ensure that live parts do not come into contact
with moisture. Moisture can cause a short circuit.
1.5.2 Risks from rotating parts
Rotating parts
WARNING!
Risk of injury from rotating parts!
Rotating parts in the fan can cause serious injuries.
Before you start any service jobs, interrupt the
power supply.
Do not reach into the moving fan.
The fan does not stop immediately! Check that
no parts are moving once you have opened the
casing cover.
Do not open the casing cover while the fan is in
operation.
1.5.3 Risks from hot surfaces
Hot surfaces
WARNING!
Risk of burns from hot surfaces!
Skin contact with hot surfaces causes severe skin
burns.
Before you start any service jobs on the electric
duct heater, interrupt the power supply.
Wait for 10 minutes after you have pulled the
mains plug.
Before you start working, make sure that all sur-
faces have cooled down to ambient temperature.
1.5.4 Health risk due to hygiene issues
Hygiene issues
CAUTION!
Health risk due to hygiene issues!
When the unit is not used for several weeks, bac-
teriae and germs may start growing in the air filter
and in the recuperative heat exchanger.
Change the air filters and clean the recuperative
heat exchanger after lengthy idle periods.
Change filters and clean the recuperative heat
exchanger in the recommended intervals.
1.5.5 Incorrect troubleshooting
WARNING!
Risk of injury from incorrect troubleshooting!
Incorrect troubleshooting can cause serious injuries
and considerable damage to property.
In case of any error or fault on the ventilation
unit, first pull the mains plug.
Faults that cannot be rectified according to the
instructions in the ‘Troubleshooting’ section have
to be rectified by the TROX Technical Service.
Do not open the casing cover while the ventila-
tion unit is in operation.
1.6 Personal protective equipment
WARNING!
Health risk due to inadequate personal protective
equipment!
Ensure that personnel uses the correct personal
protective equipment for the location where the
zone control system is installed.
Safety
Personal protective equipment
X-AIRCONTROL Zone control systems8
Personal protective equipment is equipment that pro-
tects the user against health or safety risks at work.
The personal protective equipment (type etc.) required
for a job depends on the installation location and the
ambient conditions.
The system owner has to provide the correct personal
protective equipment for each commissioning and
service job.
If the system owner does not provide any personal pro-
tective equipment, at least the following equipment has
to be used:
Industrial safety helmet
Industrial safety helmets protect the head from falling
objects, suspended loads, and the effects of striking the
head against stationary objects.
Protective clothing
Protective clothing is close-fitting, with low tear resist-
ance, close-fitting sleeves, and no projecting parts. It
prevents entanglement in moving machinery.
Safety shoes
Safety shoes protect the feet against crushing, falling
parts, and from slipping on slippery ground.
Safety goggles
Safety goggles protect the eyes from flying particles and
liquid splashes.
Protective gloves
Protective gloves protect hands from friction, abrasions,
punctures and deep cuts.
Safety
Personal protective equipment
X-AIRCONTROL Zone control systems 9
2 X-AIRCONTROL system description
2.1 System variants
2.1.1 Single room control (stand-alone)
Fig. 1: Single room control
1 Zone module
2 Supply air / extract air control
3 Heating
4 Cooling
5 Room control panel
6 Sensors for temperature, humidity, CO2/VOC
7 Motion detector (PIR sensor)
Single room control is the smallest unit for X-AIRCONTROL. With this setup, one zone module controls one zone
(e.g. a room). Zone modules come in three variants. Make sure that each VAV terminal unit and controller fit the bus
system used for the zone module.
Zone modules
X-AIR-ZMO-ANA
(
Ä
2.2.2.3 ‘Zone module X-AIR-ZMO-ANA’ on page 28 )
X-AIR-ZMO-MP
(
Ä
2.2.2.1 ‘Zone module X-AIR-ZMO-MP’ on page 22 )
X-AIR-ZMO-MOD
(
Ä
2.2.2.2 ‘Zone module X-AIR-ZMO-MOD’ on page 25 )
Requirements
Installation on a standard 35 mm mounting rail (to DIN standard)
Casing suitable for the classification of the installation location
(
Ä
2.2.2.4 ‘Zone module X-AIR-ZMO-COVER’ on page 31 )
24 V AC supply voltage (by others)
No more than 3 zone modules connected to 1 power supply
Control panel X-AIR-CP-2T (2" touch panel)
(
Ä
2.2.3 ‘Room control panel X-AIR-CP-2T’ on page 31 )
X-AIRCONTROL system description
System variants > Single room control (stand-alone)
X-AIRCONTROL Zone control systems10
Application
Temperature control (heating/cooling)
Room temperature control / extract air temperature control
Volume flow rate control (temperature, humidity, CO2/VOC)
Room temperature control / extract air temperature control
Room humidity control / Extract air humidity control
Room/extract air/CO2 control or VOC control
Timer programmes
Week timer with up to 4 switching times per day
Real time clock
Additional functions
Window contact/dew point sensor or frost protection sensor
Motion detector (PIR sensor)
Operating modes
Automatic mode
Zones are automatically controlled based on measured values and based on demand.
Minimum volume flow rate
The set minimum volume flow rates are maintained. Temperature control by means of water-side valves is not
affected.
Maximum volume flow rate
The set maximum volume flow rates are maintained. Temperature control by means of water-side valves is not
affected.
X-AIRCONTROL system description
System variants > Single room control (stand-alone)
X-AIRCONTROL Zone control systems 11
2.1.2 Control of up to 25 rooms
Fig. 2: Control of up to 25 rooms
1 Zone master
2 Central BMS
3 Network access
4 X-AIRCONTROL software/webserver
5 Zone modules
You can connect up to 25 zone modules to a zone master ( Fig. 2 /1) and hence control them centrally. For system
commissioning and configuration you can use the webserver that is included in the zone master.
Requirements
Works only with X-AIR-ZMAS zone master
Configuration and commissioning with webserver using a personal computer or notebook
Control of several zones using the zone master as a higher-level interface for data exchange, configuration and
display
Up to 25 zone modules connected to one zone master (section)
Zone bus as daisy chain
Application
Same as stand-alone version,
Ä
10
Additional application functions
Override control for maximum or minimum volume flow rate
Duct pressure monitoring
Summer and winter compensation
Hotel mode
Zone grouping
Fire mode
Operating modes
Automatic mode
Zones are automatically controlled based on measured values and based on demand.
Minimum volume flow rate
The set minimum volume flow rates are maintained. Temperature control by means of water-side valves is not
affected.
Maximum volume flow rate
The set maximum volume flow rates are maintained. Temperature control by means of water-side valves is not
affected.
X-AIRCONTROL system description
System variants > Control of up to 25 rooms
X-AIRCONTROL Zone control systems12
2.1.3 Control with 5 zone masters
Fig. 3: Control with 5 zone masters
1 Central BMS
2 Air handling unit (Modbus RTU)
3 X-AIRCONTROL zone master
Requirement
No more than 5 zone masters, cascading
You can connect up to five X-AIRCONTROL zone masters to form a system. You then have to connect the zone
masters in a cascade between the 'Zone Master In' input and the 'Zone Master Out' output. You need to connect
each X-AIRCONTROL zone master to the same LAN (subnetwork) so that the web server acts as the common inter-
face.
Each of the five X-AIRCONTROL zone masters requires a separate IP address.
Example:
X-AIRCONTROL zone master IP address
Section 1 192.168.0.201 (factory setting)
Section 2 192.168.0.202
Section 3 192.168.0.203
Section 4 192.168.0.204
Section 5 192.168.0.205
X-AIRCONTROL system description
System variants > Control with 5 zone masters
X-AIRCONTROL Zone control systems 13
2.1.4 Control of up to 4 rooms with an X-CUBE compact
Fig. 4: Control of up to 4 rooms with an X-CUBE compact
1 X-CUBE compact air handling unit
2 Central BMS
3 Network access
4 X-AIRCONTROL software
5 Zone modules
You can use an X-CUBE compact air handling unit to control an X-AIRCONTROL system for up to 4 zones (rooms).
In such a case, X-CUBE control (AHU control system) provides the control input signals for fans, volume flow con-
trollers and peripheral components. You can interconnect up to 4 zone modules and control them individually. The X-
AIRCONTROL software allows you to configure X-CUBE compact and each zone module using the X-CUBE control
Ethernet interface. X-CUBE control is an integral part of the X-CUBE compact air handling unit.
The X-AIRCONTROL zone master function is included in X-CUBE control
Up to 4 zone modules of any type can be connected
Configuration is done using the integral webserver
Remote maintenance is possible (central BMS)
X-AIRCONTROL system description
System variants > Control of up to 4 rooms with an X-CUBE compact
X-AIRCONTROL Zone control systems14
2.2 System components
2.2.1 Zone master
Fig. 5: X-AIRCONTROL zone master
1 Supply voltage 24 V AC (G0/G)
2 Alarm inputs (DI1/DI2)
3 External activation and fire alarm (DI3/DI4)
4 Override control to maintain the volume flow rate
setpoint, either Vmin or Vmax (DI5/DI6)
5 Cooling circuit ('cooling flow') temperature sensor/
outdoor sensor (T1/T2)
6 Network interfaces (TCP/IP, BMS/Modbus AHU/
Zone Master Out)
7 Network interfaces (Modbus Out 1/Modbus Out 2/
Zone Master In)
8 Digital output signal 'B alarm' (DO5)
9 Digital output signal 'A alarm' (DO4)
10 Operation (DO3)
11 Activation of heating function (DO2)
12 Activation of cooling function (DO1)
13 Control signal for supply air fan/extract air fan/
cooling circuit (AO1/AO2/AO3)
14 Slot for SD card
Connections
Analogue output signals
(0 – 10 V)
(AO1, AO2, AO3)
Terminal
no.
AO1 (Fan Sup) 17 Control signal for a central supply air fan
AO2 (Fan Exh) 18 Control signal for a central extract air fan
AO3 (Pump Cool) 19 Control signal for the cooling circuit
(e.g. circulator pump)
16 GND
X-AIRCONTROL system description
System components > Zone master
X-AIRCONTROL Zone control systems 15
Digital output signals
(DO1, DO2, DO3, DO4, DO5)
Terminal
no.
DO1 (Cooling) 20 - 21 Activation of cooling function
DO2 (Heating) 22 - 23 Activation of heating function
DO3 (Operate) 24 - 25 Operation
DO4 (Alarm) 26 - 27 A alarm
DO5 (Alarm) 28 - 29 B alarm
Supply voltage
(G0/G)
Terminal
no.
G0 1 Supply voltage 24 V AC
G 2
Digital input signals
(DI1, DI2, DI3, DI4, DI5, DI6)
Terminal
no.
DI1 (Alarm Fan Sup) 3 Supply air fan alarm input
4 GND
DI2 (Alarm Fan Exh) 5 Extract air fan alarm input
DI3 (Ext. Enable) 6 External activation (e.g. signal from central BMS) that
enables zone controllers to work in auto mode
7 GND
DI4 (FIRE) 8 Fire alarm (override control of supply and extract air
flow controllers in the event of a fire)
DI5 (V
̇max) 9 Override control: volume flow controllers maintain Vmax
10 GND
DI6 (V
̇min) 11 Override control: volume flow controllers maintain Vmin
Temperature sensor connec-
tions
(T1, T2)
Terminal
no.
T1 (Cooling flow) 12 Temperature sensor of cooling circuit
13 GND
T2 (Outdoor) 14 Outdoor sensor
15 Not used
X-AIRCONTROL system description
System components > Zone master
X-AIRCONTROL Zone control systems16
SD interface Terminal
no.
SD card Slot for SD card
Communication interfaces Terminal
no.
TCP/IP, BMS Connection to a TCP/IP network (RJ45 socket)
Modbus AHU Connection to an air handling unit (RS485 socket)
Zonemaster Out Connection for cascading (only zone master)
Communication interfaces Terminal
no.
Modbus Out 1 'Zone Modbus Out' for the connection of zone modules
Modbus Out 2 'Zone Modbus Out' for the connection of zone modules
Zonemaster In Connection for cascading (only zone master)
Technical data
Dimensions and weight
Width 156 mm
Height 110 mm
Depth 58 mm
Weight 430 g
Electrical data
Supply voltage 24 V AC ±10%
Power consumption (master) 5 VA
(without any external sensors or actuators)
Cable diameter 1.5 mm2 max.
SD card SDHC, 8 GB max.
Network properties
IP address 192.168.0.201
(factory setting)
Subnet 255.255.255.0
(factory setting)
X-AIRCONTROL system description
System components > Zone master
X-AIRCONTROL Zone control systems 17
Network properties
TCP/IP connections RJ45 plug (8P8C)
10/100 Mbit Ethernet
Modbus communication 5 x RJ12 plugs (6P/6C)
Modbus Out1 / Out2: RS-485; 38.4 kBd
Modbus Master In / Master Out: RS-485; 38.4 kBd
Modbus AHU: RS-485; Baud rate: 4800 Bd, 9600 Bd, 19200 Bd, 38400 Bd; 8
data bits; parity: no/even/uneven; 1 or 2 stop bits; address: 1 - 240
Length of cable to modules Cable type: Telephone ribbon cable 6-core with RJ12 plugs (6P/6C)
100 m max.
Length of cable to master Cable type: Telephone ribbon cable 6-core with RJ12 plugs (6P/6C)
100 m max.
Inputs/outputs
Digital inputs
[DI1|DI2|DI3|DI4|DI5|DI6]
6 × pull-up with ground contact
Digital outputs
[DO1|DO2]
2 x max. 5 A/230 V
Digital outputs
[DO3|DO4|DO5]
3 x 5 A/30 V max.
Sensor inputs
[T1|T2]
2 x for PT1000
Analogue outputs
[AO1|AO2|AO3]
3 x 0 – 10 V DC
Max. load: 50 mA per output
Ambient conditions
Acceptable relative humidity
(rh) 10 – 90 %
(no condensation)
Max. temperature – operation -20 to +50 °C
Max. temperature – storage -30 to +70 °C
Protection level IP 20 (EN 60529)
X-AIRCONTROL system description
System components > Zone master
X-AIRCONTROL Zone control systems18
2.2.2 Zone modules
Connections found on all zone modules
Fig. 6: Zone module
1 Zone Modbus connection input
2 Supply voltage 24 V AC (In/G0/G0/Out)
3 Analogue input for setpoint value (┴/Offset/10 V DC
Out)
4 Digital input for window contact/frost protection
sensor/motion detector (PIR)
5 Zone Modbus connection output
6 Modbus sensor
7 7-segment display
The connections in Fig. 6 /1 – 6 and the 7-segment display ( Fig. 6 /7) are included in all zone modules and have the
same functions.
Connections
Communication interfaces Terminal
no.
Modbus sensor RJ12 socket Various sensors and room control panel X-AIR-CP-2T
Zone Modbus In RJ12 socket Connection to the zone master or to the preceeding
zone module
Supply voltage
(G0)
Terminal
no.
24 V AC In 1 Input for supply voltage 24 V AC
G0 2
G0 3 Output of supply voltage 24 V AC to the following zone
module
(up to 3 in series)
24 V AC Out 4
X-AIRCONTROL system description
System components > Zone modules
X-AIRCONTROL Zone control systems 19
Analogue input for setpoint
values
Terminal
no.
5 GND for analogue setpoint adjuster
Offset 6 Analogue input for setpoint value
10 V DC Out 7 Supply voltage for analogue setpoint adjuster, load:
10 mA max.
Digital input signals Terminal
no.
Windows/Frost 8 Digital input for window contact/frost protection sensor
9 GND for window contact/frost protection contact and
for motion detector (PIR)
PIR 10 Digital input for motion detector (PIR)
24 V DC Out 11 Supply voltage for motion detector (PIR)
Load: 100 mA max.
Communication interface Terminal
no.
Zone Modbus Out RJ12 socket Connection to the following zone module
Display elements
Each zone module includes a two-digit 7-segment display ( Fig. 6 /7). The 7-segment display indicates the status.
The table below shows the symbols.
Segments
Display Description
Zone module in section 1 (zone master 1)
Zone module in section 2 (zone master 2)
Zone module in section 3 (zone master 3)
Zone module in section 4 (zone master 4)
Zone module in section 5 (zone master 5)
No area number has been assigned by the zone master
X-AIRCONTROL system description
System components > Zone modules
X-AIRCONTROL Zone control systems20
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110

Trox X-AIR-CP Manuale utente

Categoria
Termostati
Tipo
Manuale utente
Questo manuale è adatto anche per

in altre lingue