ADEMCO Security System VISTA-15CN Guida d'installazione

Categoria
Sistemi di controllo accessi di sicurezza
Tipo
Guida d'installazione

Questo manuale è adatto anche per

K3892V1 4/00
9,67$
9,67$&1
6HF XULW\6\VWHP
,QVWDOODWLRQDQG6HWXS*XLGH
*
®
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation & Setup Guide
ii
www.PDF-Zoo.com
iii
RECOMMENDATIONS FOR PROPER PROTECTION
The Following Recommendations for the location of Fire and Burglary Detection
Devices Help Provide Proper Coverage for the Protected Premises.
Recommendations for Smoke and Heat Detectors
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations
contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms
and areas of the household as follows: For minimum protection, a smoke detector should be installed
outside of each separate sleeping area and on each additional floor of a multi-floor family living unit,
including basements. The installation of smoke detectors in kitchens, attics (finished or unfinished), or
in garages is not normally recommended.
For additional protection, the NFPA recommends that you install heat or smoke detectors in the living
room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms,
basements, and attached garages.
In addition, we recommend the following:
Install a smoke detector inside every bedroom where a smoker sleeps.
Install a smoke detector inside every bedroom where someone sleeps with the door partly or
completely closed. Smoke could be blocked by the closed door. Also, an alarm in the hallway outside
may not wake up the sleeper if the door is closed.
Install a smoke detector inside bedrooms where electrical appliances (such as portable heaters, air
conditioners, or humidifiers) are used.
Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet (12 meters) long.
Install smoke detectors in any room where an alarm control is located, or in any room where alarm
control connections to an AC source or phone lines are made. If detectors are not so located, a fire
within the room could prevent the control from reporting a fire or an intrusion.
THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR
TEMPORAL PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES.
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
BEDROOM
BDRM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
✪✪
BEDROOM
BEDROOM
TO
BR
LVNG RM
BASEMENT
KTCHN
.
CLOSED
DOOR
GARAGE
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
Recommendations for Proper Intrusion Protection
For proper intrusion coverage, sensors should be located at every possible point of entry to a home or
commercial premises. This includes skylights and upper windows in a multi-level building.
In addition, we recommend that radio backup be used in a security system so that alarm signals can still be
sent to the alarm monitoring station in the event that the telephone lines are out of order (alarm signals are
normally sent over the phone lines, if connected to an alarm monitoring station).
www.PDF-Zoo.com
iv
Table of Contents
••••••••••••••••••••••••••••••••••••••••••••••••••
Conventions Used In This Manual............................................................................................................... viii
SECTION 1. Introduction...............................................................................................................................1–1
Description.......................................................................................................................................................1–1
Features............................................................................................................................................................1–1
SECTION 2. Installing the Control ..............................................................................................................2–1
Mounting the Cabinet .....................................................................................................................................2–1
Installing the Lock (if used)............................................................................................................................2–1
Mounting the Control's Circuit Board Alone in the Cabinet........................................................................2–2
Mounting Control and RF Receiver Circuit Boards Together in the Cabinet .............................................2–3
Standard Phone Line Connections.................................................................................................................2–4
Wiring the AC Transformer............................................................................................................................2–5
Installing the Backup Battery ........................................................................................................................2–6
Earth Ground Connections .............................................................................................................................2–6
SECTION 3. Installing Remote Keypads.....................................................................................................3–1
Keypads That May Be Used............................................................................................................................3–1
Wiring to the Keypads.....................................................................................................................................3–1
Mounting the Keypads....................................................................................................................................3–2
Supplementary Power for Additional Keypads .............................................................................................3–2
Preliminary Checkout Procedure ...................................................................................................................3–3
SECTION 4. Basic Hardwired Zones 1–6 ....................................................................................................4–1
Installing the Hardwired Zones......................................................................................................................4–1
Programming Hardwired Zones .....................................................................................................................4–4
Checkout Procedure for Hardwired Zones.....................................................................................................4–4
SECTION 5. Wired Zone Expansion.............................................................................................................5–1
Installing Zone Expansion Units....................................................................................................................5–1
Connections and Setup....................................................................................................................................5–1
Programming Wired Expansion Zones...........................................................................................................5–3
Checkout Procedure for Wired Expansion Zones ..........................................................................................5–3
SECTION 6. Wireless Expansion (5800 System)........................................................................................6–1
About Wireless Expansion ..............................................................................................................................6–1
Installing the 5881/5882 Receiver ..................................................................................................................6–2
Installing the 5800TM Module .......................................................................................................................6–3
Jam Detection and Reporting .........................................................................................................................6–3
About 5800 Series Transmitters.....................................................................................................................6–3
Installing 5800 Series Transmitters...............................................................................................................6–7
SECTION 7. Relay Outputs & Powerline Carrier Devices.....................................................................7–1
About Relays and Powerline Carrier Devices................................................................................................7–1
4204 and 4229 Relay Modules ........................................................................................................................7–1
Powerline Carrier Devices ..............................................................................................................................7–3
Programming Relay Outputs..........................................................................................................................7–4
SECTION 8. 4285 & 4286 VIP Module ..........................................................................................................8–1
About the 4285 & 4286 VIP (Voice Interactive Phone) Module....................................................................8–1
Installing the VIP Module...............................................................................................................................8–1
Programming the 4285/4286 VIP Module......................................................................................................8–4
Checking 4285/4286 VIP Module Operation..................................................................................................8–4
SECTION 9. External Sounders....................................................................................................................9–1
Compatible Sounders.......................................................................................................................................9–1
NFPA Requirements........................................................................................................................................9–1
Sounder Connections and Power....................................................................................................................9–2
Sounder Supervision .......................................................................................................................................9–2
Testing the Sounder ........................................................................................................................................9–2
www.PDF-Zoo.com
Table of Contents
v
SECTION 10. Long Range Radio ................................................................................................................10–1
About Long Range Radio...............................................................................................................................10–1
Wiring Connections .......................................................................................................................................10–1
Dynamic Signaling Feature..........................................................................................................................10–2
SECTION 11. Audio Alarm Verification (AAV) Unit ..............................................................................11–1
About Audio Alarm Verification ...................................................................................................................11–1
Wiring Connections .......................................................................................................................................11–1
SECTION 12. Final Power-Up .....................................................................................................................12–1
Earth Ground Connections ...........................................................................................................................12–1
AC Power-Up .................................................................................................................................................12–1
Connecting the Backup Battery....................................................................................................................12–1
Battery Tests..................................................................................................................................................12–2
SECTION 13. Mechanics of Programming ...............................................................................................13–1
About Programming ......................................................................................................................................13–1
Entering Program Mode................................................................................................................................13–2
Programming a Data Field............................................................................................................................13–2
Reviewing a Data Field/Erasing an Entry...................................................................................................13–2
Interactive Mode Programming (
56,
58,
80,
81, and
82)................................................................13–2
Loading Factory Defaults..............................................................................................................................13–3
Programming System Setup Fields..............................................................................................................13–3
Exiting the Programming Mode ...................................................................................................................13–3
SECTION 14. Zone Response Type Definitions.......................................................................................14–1
Zone Type Definitions....................................................................................................................................14–1
SECTION 15. Data Field Descriptions.......................................................................................................15–1
Descriptions of System Data Fields..............................................................................................................15–1
SECTION 16. Zone Programming...............................................................................................................16–1
About Zone Programming.............................................................................................................................16–1
56 Zone Programming Procedures.............................................................................................................16–1
58 Expert Programming Mode Procedures ...............................................................................................16–4
To Remove a Zone..........................................................................................................................................16–6
To Delete and Replace a Transmitter Serial Number.................................................................................16–7
To Enter and Duplicate Wireless Keys ........................................................................................................16–7
SECTION 17. Output Device Programming.............................................................................................17–1
Programming Options Defined.....................................................................................................................17–1
Programming Output Relays and Powerline Carrier Devices....................................................................17–3
SECTION 18. Zone Lists................................................................................................................................18–1
About Zone List Menu Mode.........................................................................................................................18–1
Zone List Displays .........................................................................................................................................18–1
Cross Zoning - Zone List 04...........................................................................................................................18–2
NIGHT-STAY - Zone List 05.........................................................................................................................18–2
SECTION 19. Alpha Descriptor Programming........................................................................................19–1
About Alpha Descriptor Programming.........................................................................................................19–1
Zone Descriptors............................................................................................................................................19–1
Programming Zone Descriptors (Program Menu Mode
82) .....................................................................19–1
Adding Custom Words/Numbers (not annunciated by the 4285/4286 VIP Module).................................19–3
SECTION 20. Remote Programming and Control (Downloading).....................................................20–1
About Remote Programming.........................................................................................................................20–1
Equipment Required .....................................................................................................................................20–1
Initial Download............................................................................................................................................20–2
Remote Programming Commands................................................................................................................20–2
Remote Programming Advisory Notes.........................................................................................................20–2
SECTION 21. System Communication.......................................................................................................21–1
Panel Communication with Central Station................................................................................................21–1
Report Code Formats.....................................................................................................................................21–1
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation & Setup Guide
vi
SECTION 22. System Operation .................................................................................................................22–1
Security Codes ...............................................................................................................................................22–1
Keypad Functions..........................................................................................................................................22–2
Setting the Real-Time Clock.........................................................................................................................22–6
SECTION 23. Testing the System ...............................................................................................................23–1
Test Procedure...............................................................................................................................................23–1
SECTION 24. Troubleshooting Guide........................................................................................................24–1
SECTION 25. Specifications & Accessories..............................................................................................25–1
Specifications .................................................................................................................................................25–1
Accessories (Compatible Devices).................................................................................................................25–3
APPENDIX A 5800 RF System Wireless Transmitters............................................................................A–1
Transmitter Input Loop Identification..........................................................................................................A–1
APPENDIX B Regulatory Agency Statements..........................................................................................B–1
APPENDIX C Warnings and Limitations ..................................................................................................C–1
Index.............................................................................................................................................................Index-1
Programming Form .................................................................................................................................... Insert
www.PDF-Zoo.com
vii
List of Figures
••••••••••••••••••••••••••••••••••••••••••••••••••
Figure 1. Installing the Cabinet Lock..................................................................................................................2–1
Figure 2. Mounting the PC Board........................................................................................................................2–2
Figure 3. Mounting the PC Board and RF Receiver Together in the Cabinet..................................................2–3
Figure 4. Telephone Line Connections................................................................................................................2–4
Figure 5. Connections of 4300 Transformer to the Control Board ....................................................................2–5
Figure 6. Keypad Connections to the Control Board..........................................................................................3–2
Figure 7. Using a Supplementary Power Supply for Keypads ..........................................................................3–3
Figure 8. 2-Wire Smoke Detector Connected to Zone 1......................................................................................4–2
Figure 9. 4-Wire Smoke Detector Connections (Zones 2–6)...............................................................................4–3
Figure 10. Wiring Connections - 4219 Expansion Module.................................................................................5–2
Figure 11. Wiring Connections - 4229 Expansion/Relay Module.......................................................................5–2
Figure 12. 5881/5882 RF Receiver (cover removed)............................................................................................6–2
Figure 13. 4229 Connections to Control..............................................................................................................7–2
Figure 14. 4204 Connections to Control..............................................................................................................7–3
Figure 15. 4300 Transformer Wiring Connections.............................................................................................7–4
Figure 16. 4285/4286 VIP Module Wiring Connections .....................................................................................8–3
Figure 17. Typical Sounder Wiring......................................................................................................................9–2
Figure 18. Bell Supervision Wiring .....................................................................................................................9–2
Figure 19. Long Range Radio Connections .......................................................................................................10–1
Figure 20. Connection of AAV Unit When Not Using a 4285/4286 VIP Module ............................................11–2
Figure 21. Connection of AAV Unit When Also Using a 4285 or 4286 VIP Module.......................................11–2
Figure 22. VISTA-15/VISTA-15CN Summary of Connections..................................................Inside Back Cover
www.PDF-Zoo.com
viii
Conventions Used In This Manual
••••••••••••••••••••••••••••••••••••••••••••••••••
Before you begin using this manual, it is important that you understand the meaning of the following
symbols:
U
L
A UL note that includes specific information that must be followed if you are installing this system
in a UL Listed application.
A note that includes specific information that must be followed if you are installing this system in a
Canadian UL Listed application..
A checked note includes information you should be aware of before continuing with the
installation, and which, if not observed, could result in operational difficulties.
This symbol warns of conditions that could seriously affect the operation of the system, or cause
damage to the system. Please read each warning carefully. This symbol also denotes warnings
about physical harm to the user.
Enter Zone Num.
(00 = Quit)
You may program many system options by responding to alpha keypad display
prompts. These prompts are shown in a double-line box.
00
When programming the system, data fields are indicated by a “star” (
) followed
by the data field number.
PRODUCT MODEL NUMBERS: Unless noted otherwise, references to specific model numbers represent
ADEMCO products.
www.PDF-Zoo.com
1–1
SECTION 1
Introduction
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Description
Features
•••••••••••••••••••••••••••••••••••••••••••••••••
Description
The VISTA-15/VISTA-15CN is a security system control that supports up to 32 zones,
including six basic hardwired zones (1 through 6) and a maximum of 26 expansion zones.
These expansion zones may include up to eight hardwired zones, or up to 26 wireless zones if
hardwired zones are not used. Three separate keypad-activated zones are also provided.
Features
Basic Hardwired Zones
Provides 6 basic hardwired zones having the following characteristics:
EOLR supervision
supporting
N.O. or N.C. sensors
Programmable response time (10, 350, or 700 milliseconds)
Up to sixteen 2-wire smoke detectors on zone 1
4-wire smoke or heat detectors on zones 2 through 6 (as many as can be powered from
Auxiliary Power on the control).
Optional Expansion Zones (26 total: up to 8 wired with 18 wireless, OR 26 wireless)
Wired Expansion
:
Supports up to 8 additional wired zones using a 4219 Expansion Module or 4229
Expansion/Relay Module. These zones have the following characteristics:
EOLR supervision supporting N.O. or N.C. sensors
300-500mSec normal response with an option for fast (10-15mSec) response on loop A (first
expansion zone).
Wireless Expansion:
Supports up to 26
wireless
zones (fewer if using wired expansion zones).
Requires the use of a
5881 (5882 in Canada)
type RF receiver,
as indicated below:
Receiver Model No. of Zones
5881L/5882L Up to 8
5881M/5882M Up to 16
5881H/5882H Up to 26
Requires the use of 5800 Series Wireless Transmitters.
Remote Keypads
Up to 4 of any of the following keypads may be used in the installation:
Fixed-word keypad: 6128, 6128RF
Alpha keypad: 6139 (2-line alphanumeric display)
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation and Setup Guide
1–2
Security Codes Supported
One Installer code for entire system (user 1)
•One Master code
for entire system
(user 2)
12 Secondary User
codes
(users 3–14)
One Temporary code (user 15)
One Duress code (user 16).
Temporary Code: A special code that can be used to disarm and arm the system until the Master
code is entered.
Duress Code: An emergency code that, when entered by
any
user to disarm or arm the system,
sends a silent duress message to the Central Station.
Keypad Panic Features
Up to 3 programmable panic key functions provided
Designated as zones 95, 96, 99
Activated by wired and wireless keypads
Distinguished by subscriber ID number.
Zone Monitor Features
• Provides automatic high loop resistance detection on hardwired zones 2–6, and displays a
CHECK
message for the affected zone when the system is in the disarmed state.
• Contains a Hardwire Short Detection circuit for zones 1-6
, and enabled in
30.
Detecting a
short in any wired zone, it sends a sensor Trouble message to the Central Station when the
system is in the disarmed state. At the same time a
CHECK
message is displayed on the
keypad.
Hardwire Short Detection is disabled on any zone programmed for FIRE (Zone type 09).
Either condition (high resistance or short) detected on any zone, prevents the system from
being armed until the offending condition is cleared. Conversely, when the system is armed,
and these conditions occur, an alarm is generated.
Exit Error False Alarm Prevention Features
• Enables the system to determine the difference between an actual alarm and an alarm
caused by leaving an entry/exit or interior zone open after the Exit Delay expires. If not
disarmed in time, an alarm sounds and an Exit Error report is sent to the Central Station.
An exit alarm condition also occurs if an entry/exit or interior zone re-opens within 2
minutes after the end of an Exit Delay.
The system provides an automatic Exit Delay Reset feature that allows the user to exit
(fault), close the door (restore the fault), then re-enter (fault again) the premises within the
exit delay time period. Upon re-entering, a new exit delay time period is begun with the
keypad annunciating three rapid beeps. This feature only resets the exit delay time once
for each arming session.
Optional Output Relays and Powerline Carrier Devices (X10 type)
The VISTA-15/VISTA-15CN
supports the following optional output relays and Powerline
Carrier devices (X10 type):
Maximum of 4 output devices
Up to 4 relays using one
4204
Relay Module
Up to 2 relays using one
4229
Zone/Relay Module
Up to 4 Powerline Carrier devices (you must subtract the number of relay outputs actually
used by the 4204 or 4229 modules, if used).
Actions are programmable to respond to zone activity or manual keypad entries.
Powerline Carrier devices require the use of the optional 4300 Transformer Module instead of the
supplied 1321/1321CN AC Transformer.
www.PDF-Zoo.com
Section 1 - Introduction
1–3
Optional VIP Module
The VISTA-15/VISTA-15CN supports the ADEMCO 4285/4286 VIP Module (refer to
Section 8: 4285/4286 VIP Module for further information).
Provides access to the system via on-premises or off-premises phones for arming, disarming,
etc., plus control of relay outputs and Powerline Carrier devices.
Paging Feature
If programmed, the paging feature allows certain system conditions to be reported to a pager.
Up to 16 digits may be programmed to be sent as a message to the pager. A 7-digit code
following the programmed message indicates the type of condition that has occurred.
Audio Alarm Verification (AAV) Option
Provides a programmable Audio Alarm Verification (AAV) option, which can be used in
conjunction with an output relay to permit voice dialog between an operator at the Central
Station and a person at the premises.
This AAV option must be used with a relay unit, such as an Eagle Model 1250.
U
L
The AAV option may not be used in UL installations.
Optional Long Range Radio
Allows all messages that have been programmed to go to the primary telephone number to
also be sent to any ECP-operational
ra
dio (such as the 7835C, 7720PLUS, and 7820) for
transmission to the Central Station.
Built-in Telephone Line Monitoring Option
You can monitor telephone line voltage to supervise the phone line connection. You must
connect the panel to a proper earth ground or you will get a false line cut indication if this
feature is enabled.
The loss of the line can optionally cause a local display, or a display and trouble sound.
Event Logging
Keeps a record of up to 48 selected events in a history log. All control and readout from the
log is done via ADEMCO COMPASS software
only
.
Quick Arm Feature
Quick Arm may be programmed , allowing use of the [#] key in place of the security code for
arming (Quick Arm will not work unless the Master code has been programmed into the
system).
Alarm Output Features
Provides a 12VDC, 2
amp
output that can drive the compatible sounders listed in
Section 9:
External Sounders
(assuming a fully charged battery is connected).
Steady output for burglary/panic, or
temporal
pulse output (3 pulses – pause – 3 pulses –
pause – 3 pulses . . .) for fire.
Uses
current
-limiting circuitry for protection.
• Provision for Bell supervision.
Optional Bell Supervision
Red jumper on control board, when cut, provides supervision of bell wiring (when bell is
wired with EOL resistor, as indicated in the instructions).
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation and Setup Guide
1–4
Chime/Chime by Zone
Chime, when on, normally sounds when any entry/exit or perimeter zone is faulted. However,
a “chime by zone” option, when programmed, allows only specific zones to chime if they are
faulted when the system is in the chime mode.
Auxiliary Power Output Features
Provides 12VDC, 600mA maximum (500mA maximum for UL installations). Uses current-
limiting circuitry for protection.
Interrupts for smoke detector reset if 4-wire smoke detectors are used.
Programming
Programmed options are stored in electrically erasable, nonvolatile EEPROM memory
(information can be reprogrammed at any time and will not be lost in the event of a power
loss).
The system can be uploaded, downloaded, or controlled via an IBM-compatible computer,
COMPASS software, and a
modem specified by ADEMCO.
Keypad programming consists of:
Data field programming
Interactive (menu) mode programming.
To program from a keypad, you must connect a 6139 2-line alpha keypad, but it need not stay in
the system.
Communication Formats Supported
ADEMCO Low Speed
(Standard or Expanded)
Sescoa/
Radionics (Standard or Expanded)
ADEMCO
Express
•ADEMCO
Contact ID
Zone Descriptors
You can assign
alpha descriptors to all zones (only when using alpha keypads).
AC Power Supply
Uses
1321/1321CN
, 110VAC plug-in transformer with 16.5VAC, 25VA output, unless
Powerline Carrier devices
(for example,
X10 type) are used, in which case a 4300
Transformer Module
must be used.
Backup Battery
Rechargeable (Sealed Lead Acid) 12VDC, 4AH-17.2AH. Refer to
Section 12: Final Power-
Up
to calculate the actual battery size needed.
www.PDF-Zoo.com
2–1
SECTION 2
Installing the Control
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Mounting the Cabinet
Installing the Lock
Mounting the Control's Circuit Board Alone in
the Cabinet
Mounting the Control and RF Receiver Circuit
Boards Together
Standard Phone Line Connections
Wiring the AC Transformer
Installing the Backup Battery
Earth Ground Connections
••••••••••••••••••••••••••••••••••••••••••••••••••
Mounting the Cabinet
Use fasteners or anchors (not supplied) to mount the control cabinet to a sturdy wall in a
clean, dry area that is not readily accessible to the general public. Four mounting holes are
provided at the back of the cabinet.
If an RF receiver is being used and you intend to mount its PC board within the cabinet, note
the following:
Do not mount the cabinet on or near metal objects. This decreases RF range and/or block
RF transmissions from wireless transmitters.
Do not locate the cabinet in an area of high RF interference (revealed by frequent or
prolonged lighting of the LED in the receiver after it is operational (random flicker is OK).
Installing the Lock (if used)
Use an ADEMCO No. N6277 Cam Lock and No. N6277–1 Push-On Clip (Retainer Clip).
NOTE:
The cabinet can be closed and secured without a lock by using 2 screws in the cover's
edge.
To install the lock, perform the following steps:
1. Remove the cabinet door. It is easily
removed for servicing and is easily re-
installed.
2. Remove the lock knockout from the
control cabinet door. Insert the key into
the lock. Position the lock in the hole,
making certain that the latch will make
contact with the latch bracket when the
door is closed.
3. Hold the lock steady and insert the
retainer clip into the retainer slots.
Position the clip as illustrated in order to
permit easy removal.
CABINET DOOR BOTTOM
RETAINER
CLIP
RETAINER CLIP
(NOTE POSITION)
RETAINER
SLOTS
LOCKED
UNLOCKED
Figure 1. Installing the Cabinet Lock
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation and Setup Guide
2–2
Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring
entry. Do not attempt to remove the knockouts after the circuit board has been installed.
Mounting the Control's Circuit Board Alone in the Cabinet
To mount the circuit board alone in the cabinet, follow these steps:
1. Hang two short
mounting
clips (provided) on the raised cabinet tabs (see Detail B in
Figure 2).
2. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that
the board rests on the correct row (see Detail A).
3. Swing the base of the board into the mounting clips and secure the board to the cabinet
with the accompanying screws (see Detail B).
CABINET
+
+
CIRCUIT BOARD
CABINET
DETAIL B
SIDE VIEW
OF MOUNTING
CLIPS
DETAIL A
SIDE VIEW
OF BOARD
SUPPORTING
SLOTS
CIRCUIT
BOARD
V15-01-V0
Figure 2. Mounting the PC Board
www.PDF-Zoo.com
Section 2 - Installing the Control
2–3
Mounting Control and RF Receiver Circuit Boards Together in the Cabinet
To mount the control and RF receiver boards together in the cabinet, do the following:
1.
Hang two short (black) mounting clips (provided with receiver) on the raised cabinet tabs,
as shown in Detail B in Figure 3
.
2.
Insert the top of the receiver board (removed from its own case as described in its
instructions) into the slots at the top of the cabinet, as shown in Detail A in Figure 3
.
Make sure that the board rests on the correct row of tabs, as shown.
3.
Swing the base of the board into the mounting clips and secure it to the cabinet with the
accompanying screws (see Detail B).
4.
Insert the top of the control's board into the slot in the clips and position two long (red)
clips at the lower edge of the board (see Detail C).
5.
Swing this board into place and secure it with two additional screws.
6.
Insert grounding lugs (supplied with the receiver) through the top of the cabinet into the
left-hand terminals of the antenna blocks (at the upper edge of the receiver board). Secure
the grounding lugs to the cabinet top with the screws provided, as shown in Detail D.
7.
Insert the receiver's antennas through the top of the cabinet, into the blocks' right-hand
terminals, and tighten the screws.
8.
Refer to
Section 6: Wireless Expansion (5800 System)
for receiver setup and wiring
instructions.
MOUNTING
CLIP
CABINET
DETAIL D
ANTENNA AND GROUNDING LUG INSTALLATION
ANTENNA
MOUNT
(2 PLACES)
ANTENNA
(2)
SCREW
(2)
MOUNTING
CLIP
CONTROL
CIRCUIT
BOARD
BOARD
SUPPORTING
SLOTS
HOLES FOR ANTENNAS
AND GROUNDING LUGS
RECEIVER CIRCUIT BOARD
(See Detail D)
++
++
RCVR BRD
DETAIL A
SIDE VIEW
OF BOARD
SUPPORTING SLOTS
DETAIL B
SIDE VIEW
OF MOUNTING
CLIP
DETAIL C
SIDE VIEW
OF MOUNTING
CLIP
GROUNDING
LUG
(2)
V15-02-V0
CIRCUIT BOARD
CABINET
Figure 3. Mounting the PC Board and RF Receiver Together in the Cabinet
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation and Setup Guide
2–4
Standard Phone Line Connections
The wiring connections shown here are not applicable if the 4285/4286 VIP Module is used. Refer
to
Section 8: 4285/4286 VIP Module
for information regarding phone line connections, which are
different than those shown here.
Connect incoming phone line and handset wiring to the main terminal block via an RJ31X
jack (CA38A jack in Canada) as follows and as shown in Figure 4.
Term. 21: Local Handset (TIP – Brown*)
Term. 22: Local Handset (RING – Gray*)
Term. 23: Incoming Phone Line (TIP – Green*)
Term. 24: Incoming Phone Line (RING – Red*)
* Colors of wires in Direct Connect Cord.
TERMINALS
ON CONTROL
EARTH GROUND
INCOMING TELECOM LINE
Handset
TIP
RING
RJ31X JACK
(CA38A in
CANADA)
PLUG
DIRECT
CONNECT
CORD
TIP
RING
GROUND
PREMISES
PHONES
{
{
BROWN (TIP)
GREY (RING)
GREEN (TIP)
RED (RING)
21 22 23 24 25
Incoming
Telecom Line
IMPORTANT!
IF THE PANEL IS NOT CONNECTED TO A
PROPER EARTH GROUND, YOU MAY GET
FALSE TELEPHONE LINE CUT INDICATIONS
(IF THE TELEPHONE LINE MONITOR HAS
BEEN PROGRAMMED IN FIELD 92).
Figure 4. Telephone Line Connections
www.PDF-Zoo.com
Section 2 - Installing the Control
2–5
Wiring the AC Transformer
1321/1321CN Transformer
Wire the 1321/1321CN Transformer to terminals 1 and 2 on the control board. See wiring
table below to determine wire gauge.
Use caution
when wiring the transformer to the control panel to guard against blowing the
fuse inside the transformer (the fuse is nonreplaceable).
4300 Transformer
If you are going to use a
4300 Transformer
Interface (required if Powerline Carrier devices
are used), connect the 4300 Transformer’s terminals as follows:
1.
Connect terminals
1, 3 (AC), and 2 (Ground) to control board terminals 1, 2, and 25,
respectively (see
Figure 5
). See
table
below to determine wire gauge to use.
WIRING TABLE
Distance of Transformer
From the Control Panel
Wire Gauge
to Use
Up to 50 feet # 20
50-100 feet # 18
100-250 feet # 16
Wiring to the AC transformer must not exceed 250 feet using 16-gauge wire. The voltage reading
between terminals 1 and 2 of the control must not fall below 16.5VAC, or an
AC LOSS
message is
displayed.
Do not plug the transformer into the AC outlet until you are instructed to do so later in the manual.
2.
Wire the other three terminals (Sync, Data, Com) on the 4300 Transformer. Wires from
these terminals must be connected to a 9-pin connector on the control board (using a
4142TR Cable
supplied with the 4300 Transformer), as shown in
Figure 5
. These
particular wires can be 24-gauge or larger, and can be run along with the AC and ground
wires to the control panel.
123456789
9-PIN CONNECTOR
ON CONTROL BOARD
BLACK
BLUE
BROWN
GREEN
RED
WHITE
YELLOW
GRAY
VIOLET
4142TR CABLE
1
2
3
4
56
125 2
AC
Earth
Ground
AC
Sync
Data
Com
4300 TRANSFORMER/INTERFACE
TERMINALS
ON CONTROL
BOARD
Figure 5. Connections of 4300 Transformer to the Control Board
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation and Setup Guide
2–6
Installing the Backup Battery
If necessary, refer to Section 12: Final Power-Up for information regarding battery size to
use.
Do not attach the connector cable to the battery terminals until you are instructed to do so later in
the manual.
Install the backup battery as follows:
1. Place the 12-volt backup battery in the control cabinet.
2. Attach red and black wires on the battery connector cable as follows:
a. Red to the positive (
+
) battery terminal
on the control board
(see
Figure 22.
VISTA-15/VISTA-15CN Summary of Connections
for location, if necessary).
b. Black to the negative (
) battery terminal
on the control board.
U
L
Use a 4AH battery or larger for UL installations. Refer to
Section 12: Final Power-Up
to calculate
the actual battery size needed.
Earth Ground Connections
The designated earth ground terminal (25) must be terminated in a good earth ground for
the lightning transient protective devices in this product to be effective. The following are
examples of good earth grounds available at most installations:
Metal Cold Water Pipe:
Use a noncorrosive metal strap (copper is recommended) firmly
secured to the pipe to which the ground lead is electrically connected and secured.
AC Power Outlet Ground:
Available from 3-prong, 120VAC, power outlets only. To test the
integrity of the ground terminal, use a 3-wire circuit tester with neon lamp indicators, such
as the
UL
Listed
Ideal Model 61-035
, or equivalent, available at most electrical supply stores.
www.PDF-Zoo.com
3–1
SECTION 3
Installing Remote Keypads
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Keypads That May Be Used
Wiring to the Keypads
Mounting the Keypads
Supplementary Power for Additional Keypads
Preliminary Checkout Procedure
••••••••••••••••••••••••••••••••••••••••••••••••••
Keypads That May Be Used
Up to 4 keypads may be used in the system, independent of auxiliary power considerations
(you may need to use an auxiliary power supply if the 600mA aux. output is exceeded).
The following keypad models may be used:
Fixed-Word Display: 6128, 6128RF
•Alpha
Display
:
6139.
Be sure the keypads are set to the non-addressable mode (address 31).
Wiring to the Keypads
To wire keypads to the control, perform the following steps:
1. Determine wire gauge by referring to the
Wiring Run Chart
below.
For devices (keypads, RF receivers, zone expander, etc.) connected to a single 4-wire run,
determine the current drawn by all units connected to the single wire run, then refer to
the Wiring Run Chart below to determine the maximum wire length that can be safely
used for each wire size. Current draw for all devices can be found in Section 25:
Specifications & Accessories
.
NOTE: Refer to Table 1. AUXILIARY DEVICE CURRENT DRAW WORKSHEET in
Section 12: Final Power-Up to obtain the current draw for all keypads.
Maximum wire lengths for any device that is home run to the control can also be determined from
the Wiring Run Chart, based on the current draw of that device alone.
Wiring Run Chart for Devices* Drawing Aux Power
from the Control (12V+ & 12V–)
TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN
Wire
Size
50mA or less 100mA 300mA 500mA 600mA
#22 500 ft (152m) 250 ft (76m) 80 ft (24m) 50 ft (15m) 42 ft (13m)
#20 750 ft (228.6m) 380 ft (116m) 130 ft (39.6m) 80 ft (24m) 67 ft (20.4m)
#18 1300 ft (396m) 650 ft (198m) 220 ft (67m) 130 ft (39.6m) 115 ft (35m)
#16 1500 ft (457m) 1000 ft (305m) 330 ft (100.5m) 200 ft (70m) 170 ft (52m)
* Includes Keypads, RF Receivers, Zone Expander/Relay Units, or 4285/4286 VIP Module.
www.PDF-Zoo.com
VISTA-15/VISTA-15CN Installation and Setup Guide
3–2
The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor
cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on
the data lines when quad cable is used.
2. Run field wiring from the control to the keypads (using standard 4-conductor twisted wire
cable of the wire gauge determined in step 1).
3.
Connect
remote
keypads
to terminals 4, 5, 6, and 7 on the control board, as shown in
Figure 6.
5
6
7
4
TERMINALS ON
CONTROL PANEL
BLACK
RED
GREEN
YELLOW
KEYPAD
Figure 6. Keypad Connections to the Control Board
Mounting the Keypads
To mount the keypads, perform the following steps:
1. Make sure the
addressable keypad(s)
are set to non-addressable mode (address 31), which
is the factory default setting. Refer to the instructions provided with the keypad for
address setting procedure.
2. Mount the keypads at a height that is convenient for the user. Refer to the instructions
provided with the keypad for mounting procedure.
You can either surface mount or flush mount keypads (using an appropriate Trim Ring
Kit:
6139TRK
). Refer to the mounting instructions and template included with the keypad
and/or trim ring kit for specific information.
Supplementary Power for Additional Keypads
The VISTA-15/VISTA-15CN control provides 600mA for powering keypads (up to 4) and
other devices from the auxiliary power output. The backup battery supplies power to these
keypads in the event that AC power is lost.
When the
control’s
auxiliary power load for all devices exceeds 600mA, you can power
additional keypads from a regulated 12VDC power supply (e.g.,
487-12
supplies 12V, 250mA;
488-12
supplies 12V, 500mA). Use a
UL
Listed, battery-backed supply for UL installations.
The 487-12/488-12
power
supplies have a backup battery that can power these keypads in the
event of AC power loss to the main supply.
Keypads powered from supplies that do not have a backup battery
will not function
when AC
power is lost. Therefore, be sure to power at least one keypad from the control's auxiliary power
output.
Connect the additional keypads as shown in
Figure 7
, using the keypad wire colors shown. Be
sure to observe the current ratings for the power supply used.
www.PDF-Zoo.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132

ADEMCO Security System VISTA-15CN Guida d'installazione

Categoria
Sistemi di controllo accessi di sicurezza
Tipo
Guida d'installazione
Questo manuale è adatto anche per