Introduction / Introduzione
Thanks for choosing a Omega device.
The TXDIN401 converts a signal obtained from temperature sensors PT100,
PT1000 or NI100 (with a 2, 3 or 4 wires connection) into a current signal for
4..20mA loop (2 wires).
Main features are:
High accuracy;
16bit conversion;
Programmable by RFid (NFC);
Input -10..+70 mV;
2624 Word non-volatile memory (circular buer) for data-logging with
sampling time selectable by the user;
Possibility to rescale the output 4..20mA compared to temperature input value;
Field calibration to compensate eventual errors (Gain and Oset);
Compact dimensions;
The software RF Programmer (available for download on Omega website)
and the TX400-RFID allow:
- complete congurability of the device;
- download on PC of logged data;
- visualization/printing of the temperature - time trend
Grazie per aver scelto un prodotto Omega.
Lo strumento TXDIN401 converte un segnale di temperatura acquisito
attraverso sonde PT100, Ni100 con collegamento a 2, 3 o 4 li o TC in un
segnale normalizzato in corrente per loop 4..20 mA (tecnologia 2 li).
Le caratteristiche dello strumento sono:
Elevata precisione;
Conversione della misura a 16 bit;
Programmabilità via RFid (NFC);
Ingresso -10..+70 mV;
2624 Word di memoria non volatile (buer circolare) per data-logging con
tempo di campionamento impostabile dall’utente;
Possibilità di riscalare l’uscita 4..20mA rispetto all’ingresso in temperatura;
Taratura in campo per recuperare eventuali errori delle sonde (Gain e Oset);
Ridotto ingombro;
Tramite il software RF Programmer (scaricabile dal sito omega.com) e il
programmatore TX400-RFID, è possibile:
- congurare completamente il convertitore;
- scaricare sul pc il logging registrato;
- visualizzare e stampare la curva temperatura - tempo
1 Safety guide lines / Norme di sicurezza
Read carefully the safety guidelines and programming instructions contained in
this manual before using/connecting the device.
Only qualied personnel should be allowed to use the device and/or service it
and in accordance to technical data and environmental conditions listed in this
manual.
Do not dispose electric tools together with household waste material. In
observance European Directive 2002/96/EC on waste electrical and electronic
equipment and its implementation in accordance with national law, electric tools
that have reached the end of their life must be collected separately and returned
to an environmentally compatible recycling facility.
Prima di utilizzare il dispositivo, leggere con attenzione le istruzioni e le
misure di sicurezza contenute in questo manuale.
Lutilizzo / manutenzione è riservato a personale qualicato ed è da intendersi
esclusivamente nel rispetto dei dati tecnici e delle condizioni ambientali
dichiarate.
Non gettare le apparecchiature elettriche tra i riuti domestici.
Secondo la Direttiva Europea 2002/96/CE, le apparecchiature elettriche
esauste devono essere raccolte separatamente al ne di essere reimpiegate o
riciclate in modo eco-compatibile.
2 Dimensions / Dimensioni
DIN3880 1 Mod.
RUN
64 mm
Attacco a guida DIN EN50022
Din rail mounting guide EN50022
18 mm
90 mm
2
1
3
4
+
-
TC1 7
6
5
SUPPLY
6...32Vdc
+Vdc
Out
mA
B
B1
A1
A
RUN
RFID
TXDIN401
DIN Rail Mount TC/RTD Input
Transmitter RFID
For latest product manuals:
omegamanual.info
User’s Guide
Shop online at
omega.comSM
1 YEAR
2 YEAR
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period
of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace period to
the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s
customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department
will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by
OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY
does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling,
improper interfacing, operation outside of design limits, improper repair, or unauthorized modication. This
WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having
been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specication;
misapplication; misuse or other operating conditions outside of OMEGA’s control. Components in which wear is
not warranted, include but are not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA
neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use of its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specied and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability
of OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for consequential,
incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible.
This affords our customers the latest in technology and engineering. OMEGA is a registered trademark of
OMEGA ENGINEERING, INC.
© Copyright 2015 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied,
photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in
whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
FOR WARRANTY RETURNS, please have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product
was PURCHASED,
2. Model and serial number of the product under
warranty, and
3. Repair instructions and/or specic problems relative
to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA
for current repair charges. Have the following
information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the
repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specic problems
relative to the product.
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any
errors it contains, and reserves the right to alter specifications without notice.
Servicing North America:
U.S.A.: Omega Engineering, Inc., One Omega Drive, P.O. Box 4047, Stamford, CT 06907-0047 USA
Toll-Free: 1-800-826-6342 (USA & Canada only), Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only),
Tel: (203) 359-1660, Fax: (203) 359-7700
For Other Locations Visit omega.com/worldwide
M5588/0716
3 Technical Data / Dati tecnici
3.1 General data / Caratteristiche generali
1Operating range
Range funzionamento 6-32 Vdc
2
Current output
Uscita in corrente
4..20 mA (2 wires) / 4..20 mA (2 li)
3Functional insulation
Isolamento funzionale 1K Vac
4Output resolution
Risoluzione in uscita 2 μA
5Upper Linearity Limit
Limite linearità superiore f.s. + 5°C
6Lower Linearity Limit
Limite linearità inferiore f.s. - 5°C
7Failure output
Uscita guasto
selectable 21mA, 3,8mA or anyone
selezion. tra 21mA, 3,8mA o nessuno
8Current output protection
Protezione uscita in corrente
30 mA approx.
30 mA circa
9Rejection
Reiezione 50-60 Hz
10 Max transmission error
Max errore di trasmissione
greater between 0,1% f.s. or 0,2°C
maggiore tra 0,1% f.s. o 0,2°C
11 EMI < 0,5%
12 Cable resistance
Resistenza cavi max 20Ω
13 Temperature coecient
Coeciente di temperatura < 100 ppm
14 Sampling time
Tempo di campionamento 300 ms
15 Response time (10..90%)
Tempo di risposta (10..90%) approx. 600 ms
16 Sealing
Grado di protezione IP 20
17 Conformity
Normative CE, EN 61000-6-4, EN 61000-6-2
3.2 Thermo-mechanic features / Caratteristiche
termomeccaniche
1Operating temperature
Temp. di funzionamento -40..+85 °C
2Humidity
Umidità
30-90% @ 40°C (non condensing / non
condensante)
3
Storage temperature
Temperatura
magazzinaggio
- 4 0. .+105 °C
4Connections
Connessioni
screw pins
morsetti a vite
5Conductors section
Sezione conduttori 1 mm2
6Wires strip
Spelatura conduttori 8 mm
7Enclosure
Custodia nylon (PA66)
8Dimensions
Dimensioni 23 mm, Ø 45 mm
4 Input / Ingressi
PT100 Measuring range: -200..+600°C / Range di misura: -200..+600°C
Connection: 2, 3, 4 wires / Tecnica di collegamento: 2, 3, 4 li
Ni100 Measuring range: -60..+180°C / Range di misura: -60..+180°C
Connection: 2, 3, 4 wires / Tecnica di collegamento: 2, 3, 4 li
TC K Measuring range: -260..+1360°C / Range di misura: -260..+1360°C
TC S Measuring range: -40..+1760°C / Range di misura: -40..+1760°C
TC R Measuring range: -40..+1760°C / Range di misura: -40..+1760°C
TC J Measuring range: -200..+1200°C / Range di misura: -200..+1200°C
TC T Measuring range: -260..+400°C / Range di misura: -260..+400°C
TC N Measuring range: -260..+1280°C / Range di misura: -260..+1280°C
TC B Measuring range: +40..+1820°C / Range di misura: +40..+182C
TC E Measuring range: -260..+940°C / Range di misura: -260..+940°C
Input mV
Measuring range: -10..+70mV / Range di misura: -10..+70mV
4.1 Connections / Connessioni
Cables colors according to IEC60751 / Colorazioni cavi come da IEC60751
Pt100
Ni100
2 wire
6..32Vdc
4..20mA
RED
WHITE
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
WHITE
RUN
6..32Vdc
4..20mA
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
RUN
Pt100
Ni100
3 wire
6..32Vdc
4..20mA
RED
WHITE
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
WHITE
RUN
6..32Vdc
4..20mA
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
RUN
Pt100
Ni100
4 wire
6..32Vdc
4..20mA
RED
WHITE
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
WHITE
RUN
6..32Vdc
4..20mA
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
RUN
TC
6..32Vdc
4..20mA
RED
WHITE
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
WHITE
RUN
6..32Vdc
4..20mA
RUN
6..32Vdc
4..20mA
RED
RED
WHITE
RUN
5 Conguration / Congurazione
To congure this signal converter it is necessary to use a TX400-RFID and the
conguration software RF Programmer, available on www.omega.com. After
connecting the TX400-RFID via USB and activating the software, it is possible in
“EDIT” mode to congure the device selecting type of sensor, measuring range,
output for error signal and sampling frequency for the registration. The keys
WRITE” and “READ” allow to write and read data on the devices quickly and
easily.
On the lower side of the display a list of all programmed devices is showed; it can
be printed to conrm that the programming has been completed successfully.
La congurazione di questo convertitore di segnale richiede l’utilizzo di un
base programmatore (TX400-RFID) e del software di congurazione RF
Programmer scaricabile dal sito www.omega.com.
Dopo aver connesso tramite porta USB il TX400-RFID e attivato il software è
possibile con la modalità “EDIT” parametrizzare il dispositivo selezionando il
tipo di sensore, range di misura, uscita per segnalazione errore e la frequenza
di campionamento per la registrazione. Con i tasti “WRITE” e “READ” è
possibile scrivere e leggere i vari dispositivi velocemente e in modo agevole.
Nella parte bassa dello schermo appare la lista riassuntiva dei dispositivi
programmati, che può essere stampata per certicare la buona riuscita delle
operazioni.
6 Data Logger
This signal converter is provided with a datalogging function for the input signal.
Fixing the sampling time (1..3600 seconds) each time the loop 4..20mA powers the
device up, this will store the input value into a non-volatile memory. Through the
TX400-RFID it is possible to download / display / print all data.
Questo convertitore di segnale è provvisto di una capacità di storicizzazione
del segnale in ingresso. Fissando il tempo di campionamento (impostabile
tra 1 e 3600 sec.) ogni volta che il loop 4..20mA alimenterà il dipositivo
questo archivia il valore in ingresso su una memoria non volatile. Tramite il
TX400-RFID è possibile scaricare tutti i dati e presentarli a video o stamparli.