Hitachi PLC Getting Started

Tipo
Getting Started
No. Contents Page
1 Introduction 2
2 Hitachi PLC 4
3 Technical Specifications 10
4 Setting up 11
5 Configuration 13
6 Wiring 16
7 Programming 17
Getting Started
Hitachi PLC
1
Powerful Hitachi PLC
Programming Compatibility
Programming is fully compatible from the smallest PLC (MICRO-EH) to the biggest one (Big-H
series).
2 communication ports
2 communication ports can be used flexibly as programming, HMI communication and general
purpose port for bar code reader or intelligent sensors or scales.
(Note : MICRO-EH does not support the general purpose port.)
Easy programming
Hitachi provides two different programming software.
1) Pro-H : IEC61131-3 standard, Multiprogramming languages.
2) LADDER EDITOR for Windows : Easy ladder programming editor
(The both in one CD package)
High speed micro processor
EH-150 and MICRO-EH has a 32 bits RISC microprocessor called Super H.
Compact size
The compact PLC has more capabilities with high reliability, and saves more space and cost.
Open network
EH-150 series has Profibus DP master/slave modules and DeviceNet master/slave modules,
which will increase application range.
Flexible product line up
Digital I/O (normal / high density), analog I/O (V, I, PT100/1000), high speed counter, positioning,
several communication modules are available.
Solution for total automation system
Hitachi provides many options besides PLC as follows.
- Operator panel EH-HMI series
- Remote I/O system EH-RIO series
- Frequency inverters L/SJ100 and L300P/SJ300 series.
2
1. Introduction
What is a PLC?
“PLC” stands for Programmable Logic Controller. PLC is an industrial controller, which enables the
control of many devices and signals easily and flexibly. The PLC is “Programmable” by PC or hand
held programming unit. The PLC’s basically work in 3 steps : reading input data, calculating in the
CPU and writing output data according to user program in the PLC.
How it works?
The PLC has a CPU. The CPU executes (scans) a user program. When the CPU reaches the end of
the program, the CPU will return to the program top and execute again, this process is continuous. In
every cycle, input data is read, and output data is written once each.
Input and output data is effective once in a scan.
This is called “
Refresh Processing
”.
* Scan time (cycle time) depends on your program. (Normally 5 to 30ms.)
Time
1 cycle
Program Scanning
Read Input data Write Output data
System processing
and Communication
1 cycle
1 cycle
Input
- Switches
- Sensors
- Encoders, etc.
PLC
Output
- Valves
- Relays
- Alarms, etc.
CPU
OutputInput
Calculating
Program
3
Basic flow
Download from PC to CPU
The program is stored in
FLASH memory of CPU
Start the PLC by PC or
RUN switch on the PLC
PLC starts operation according to the user program.
RUN
Program
CPU module
PLC
CPU module
FLASH memory
Program
Program memory (SRAM)
Data memory (SRAM)
Retentive Data memory
(SRAM)
Micro processor
FLASH memory keeps the
program after power OFF.
CPU module
FLASH memory
Program memory (SRAM)
Data memory (SRAM)
Retentive Data memory
(SRAM)
Micro processor
Input
Output
ç ç ç
è è è
Programming on PC
Programming software
required (see page 1)
4
2. Hitachi PLC
System design
Hitachi has a compact type PLC MICRO-EH and modular type PLC EH-150.
n MICRO-EH
I/O modules
(+ terminal cover)
Base unit
CPU module
Power supply module
Expansion connector
LED indication
Terminal block
n
EH-150
Input terminal
Output terminal
Communication port 2
(RS-422/485)
Expansion
connector
LED indication
RUN/STOP
switch
Potentiometer
× 2
Communication
Port 1
è RUN
(RS-232C)
Communication port 1 (RS-232C/422*/485*)
Communication port 2 (RS-232C)
RUN/STOP switch
Reset button
Error LED
RUN LED
Battery
é
* : Supported by CPU308/316/448
5
Binary, decimal and hexadecimal code
Before going into the Hitachi PLC details, it is important to understand the numbering system of the
PLC. Electric devices like PLCs can handle only digital data. The minimum unit of digital data is a
bit. 1 bit has two states, 0 or 1.
4 bits can give us 16 different values because of 2
4
as below left.
Since 4 bits of data is not easy to handle, the data is translated to hexadecimal code 0 to F as above
right. One hexadecimal code (= 4 bits) can express 16 different values.
4 hexadecimal codes have 65,535 values (= 16
4
). This unit (4 hexadecimal codes = 16 bits) is called
as Word. Normally Hitachi PLC handles binary data and word data.
This is a comparison table of one Word in binary, decimal and hexadecimal expressions.
2 10 16 2 10 16
0000 0000 0000 0000 0 H 0000 0000 0000 0011 1111 63 H 003F
0000 0000 0000 0001 1 H 0001 0000 0000 0100 0000 64 H 0040
0000 0000 0000 0010 2 H 0002
0000 0000 0000 0011 3 H 0003 0000 0000 1111 1111 255 H 00FF
0000 0000 0000 0100 4 H 0004 0000 0001 0000 0000 256 H 0100
0000 0000 0000 0101 5 H 0005
0000 0000 0000 0110 6 H 0006 0000 0011 1111 1111 1023 H 03FF
0000 0000 0000 0111 7 H 0007 0000 0100 0000 0000 1024 H 0400
0000 0000 0000 1000 8 H 0008
0000 0000 0000 1001 9 H 0009 0000 0111 1111 1111 2047 H 07FF
0000 0000 0000 1010 10 H 000A 0000 1000 0000 0000 2048 H 0800
0000 0000 0000 1011 11 H 000B
0000 0000 0000 1100 12 H 000C 0000 1111 1111 1111 4095 H 0FFF
0000 0000 0000 1101 13 H 000D 0001 0000 0000 0000 4096 H 1000
0000 0000 0000 1110 14 H 000E
0000 0000 0000 1111 15 H 000F 0111 1111 1111 1111 32767 H 7FFF
0000 0000 0001 0000 16 H 0010 1000 0000 0000 0000 32768 H 8000
0000 0000 0001 1111 31 H 001F 1111 1111 1111 1111 65535 H FFFF
0000 0000 0010 0000 32 H 0020
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Binary code
Hexadecimal code
4 bits
16 values
0
1
0
0
1
2
E
F
Word
0
1
or
6
I/O data types
Hitachi PLCs handles the following I/O.
Bit
(for Digital data, etc)
Word
(for Analog data, etc)
Double Word
Input X ¨¨¨¨ [D] WX ¨¨¨ [H] DX ¨¨¨ [H]
External
I/Os
Output Y ¨¨¨¨ [D] WY ¨¨¨ [H] DY ¨¨¨ [H]
Normal memory R ¨¨¨¨ [H] WR ¨¨¨ [H] DR ¨¨¨ [H]
Shared memory M ¨¨¨¨ [H] WM ¨¨¨ [H] DM ¨¨¨ [H]
Link memory L ¨¨¨¨ [H] WL ¨¨¨ [H] DL ¨¨¨ [H]
Timer (TD,SS, etc.) TD ¨¨¨ [D] - -
Counter (CU, etc.) CU ¨¨¨ [D] - -
Edge detection á DIF ¨¨¨ [D] - -
Internal
I/Os
Edge detection â DFN ¨¨¨ [D] - -
Note : [D] ... Decimal (ex. 00,01,...,09,10,...,15,16,17,18,19,20,21,...)
[H] ... Hexadecimal (ex. 00,01,...,09,0A,0B,...0F,10,11,...1F,20,21,...)
n
Bit, Word and Double Word
Double Word consists of 2 Words, and 1 Word consists of 16 bits as below.
n
External I/O
External I/Os (X, Y, WX, WY, etc.) are direct addresses for each digital input/output module or analog
input/output module. Please note bit I/Os X and Y are decimal expression.
(WX/WY can be used as access command or data for high function modules like the counter
module.)
X
0
WX 0
X
1
X
2
X
13
X
14
X
15
X
16
WX 1
X
17
X
18
X
29
X
30
X
31
X
32
WX 2
X
33
X
34
X
45
X
46
X
47
DX 0
DX 1
DX 2
B
i
t
15
B
i
t
14
B
i
t
13
B
i
t
12
B
i
t
11
B
i
t
10
B
i
t
9
B
i
t
8
B
i
t
7
B
i
t
6
B
i
t
5
B
i
t
4
B
i
t
3
B
i
t
2
B
i
t
1
B
i
t
0
Word (16 bits)
B
i
t
15
B
i
t
14
B
i
t
13
B
i
t
12
B
i
t
11
B
i
t
10
B
i
t
9
B
i
t
8
B
i
t
7
B
i
t
6
B
i
t
5
B
i
t
4
B
i
t
3
B
i
t
2
B
i
t
1
B
i
t
0
Double Word (32 bits)
Example : WR 0 = H1234, WR 1 = H5678 è DR 0 = H5678 1234
WR 1 WR 0
7
n
Internal I/O
Internal I/O (R, WR, M, WM, etc.) means data memory. This data memory area can be read or
written freely for flags, parameters, set point values or calculation depending on your program.
* Refer to the chapter Programming for further information about TD, CU, DIF and DFN.
Note : R and WR/DR are physically separated memory areas.
[ M, L ]
Note : M, WM and DM are in one common memory area. (L/WL/DL as well.)
WR 0
WR 1 WR 2
DR 0
DR 1
DR 2
No bit access No bit access No bit access
R
0
R
1
R
2
R
3
R
4
R
5
R
6
R
7
R
8
R
9
R
A
R
B
R
C
R
D
R
E
R
F
R
10
R
11
R
12
R
13
R
14
R
15
R
16
R
17
R
18
R
19
R
1A
R
1B
R
1C
R
1D
R
1E
R
1F
R
20
R
21
M
0
WM 0
M
1
M
2
M
D
M
E
M
F
M
10
WM 1
M
11
M
12
M
1D
M
1E
M
1F
M
20
WM 2
M
21
M
22
M
2D
M
2E
M
2F
DM 0
DM 1
DM 2
Note : L is available only for the LINK module
[ R, WR ]
8
I/O address of MICRO-EH
The I/O address of MICRO-EH is fixed.
X0 X5
Input
Y100 Y103
Output
X0 X7
Y100 Y105
X0 X15
Y100 Y111
n
10/14/28 points
DI × 6
DO × 4
DI × 8
DO × 6
DI × 16
DO × 12
X0 X12
Y100 Y109
WX30,31
WY40
n
23 points
DO × 10
DI × 13 AI × 2
AO × 1
n
Expansion units
DI
DO
AI
AO
: Digital Input
: Digital Output
: Analog Input
: Analog Output
Y1016 Y1021
X2000 X2007
Y2016 Y2021
X3000 X3007
Y3016 Y3021
X4000 X4007
Y4016 Y4021
X1000 X1007DI × 8
DO × 6
9
I/O address of EH-150
The I/O address of EH-150 depends on the module location and I/O type.
& Hexadecimal expression
As mentioned above, each hexadecimal code can be expressed as 4 bits.
0 : 0000 4 : 0100 8 : 1000 C : 1100
1 : 0001 5 : 0101 9 : 1001 D : 1101
2 : 0010 6 : 0110 A : 1010 E : 1110
3 : 0011 7 : 0111 B : 1011 F : 1111
Since one word (WX, WY, WM, etc.) consists of 16 bits (X, Y, M, etc.), the relation between WX/WY
and X/Y is as follows. (H stands for hexadecimal.)
WX 0 = H1234 = 0001 0010 0011 0100
WY 5 = H00FF = 0000 0000 1111 1111
X15 X0X7X8
Y15 Y0Y7Y8
Bit number (decimal)
Slot number (0 - 7)
Unit number (0 - 1)
I/O type
Word number
Slot number (0 - 7)
Unit number (0 - 1)
I/O type
[ Bit ]
X
¨
¨
¨¨
[ Word ]
WX
¨
¨
¨
X0000 X0015
CPU
Power supply
Basic unit
(Unit 0)
Expansion unit
(Unit 1)
I/O controller module
EH-XD16
EH-YTP64
EH-YTP32
EH-AX8V
EH-XD16
EH-AX8V
X0100 X0115
WX020 WX027
EH-AY4V
Y0300 Y0363
WY040 WY043
Y1200 Y1231
EH-XD64
X1000 X1063
WX140 WX147
16 DI
16 DI
8 AI
64 DO
4 AO
64 DI
32 DO
4 AI
0 1 2 3 4
0 1 2 3 4
* 16 DI : 16 points Digital Input module, 4 AO : 4 channels Analog Output module
10
3. Technical specifications
EH-150MICRO-EH
10/14/23,28
CPU104 CPU208 CPU308 CPU316 CPU448
General specification
Speed of
Binary
command
0.9µs 1.0µs 0.1µs
Memory size 3 kstep 4 kstep 8 kstep 8 kstep 16 kstep 48 kstep
I/O points 10/70/84 512 1,024
Exp. unit Up to 4 - 1
Commands 98 152
PID -
ü
Clock
ü *1
-
ü
Port 1 RS-232C RS-232C/422/485
Port 2
RS-422/485 *1
RS-232C
Memory
board
(planned) - ü (optional)
Modem
ü
-
ü
Internal memory
R
1984 bits (R0 R7BF)
WR
4,096 word
(WR0 FFF)
8,192 w.
(WR0 1FFF)
17,408 w.
(WR0 43FF)
22,528 w.
(WR0 57FF)
50,176 w.
(WR0 C3FF)
M, WM
16,384 points = 1,024 w. (M0 3FFF = WM0 3FF)
L, WL
-
16,384 points ×2 = 1,024 w. ×2
(L0 3FFF = WM0 3FF, L10000 13FFF = WL1000 13FF
Special R
64 points (R7C0 7FF
Special WR
512 words (WRF000 F1FF)
Timer (TD)/
counter (CU)
points
256 points
(TD + CU)
0.01s : 64 pts.
512 points (TD + CU) *2
(TD : up to 256 points, 0.01s base TD : up to 64 points.)
TD /CU
setting value
TD : 65,535 with 0.01, 0.1 or 1 sec. time base
CU : 65,535 times
Edge detect 512 points (DIF0 - 511) / 512 points (DFN0 - 511)
*1 : Only 23, 28 points module.
*2 : (TD) is up to 256 (TD0 - 255), and counter (CU) is up to 511 (CU0 - 511) for EH-150 series. TD number
is not allowed to use same as CU number, and vice versa.
Special internal registers R, WR
The special internal registers are some flags, diagnostic information and parameter setting area to operate
the PLC easily and flexibly. The following list is a part of this area and error code in WRF000.
Address Description Set by Reset by Error code in WRF000
R7E3 ON while the first scan CPU
CPU
H13 micro processor error
R7E4 Always ON CPU CPU H33 memory size error
R7E5 0.02s clock (0.01s ON, 0.01s OFF) CPU CPU H34 program (syntax) error
R7E6 0.1s clock (0.05s ON, 0.05s OFF) CPU CPU H41 I/O configuration error
R7E7 1s clock (0.5s ON, 0.5s OFF) CPU CPU
R7EC Clear error code user CPU
H44
scan time error
(normal scan)
WRF000 Error code (See right table.) CPU user
WRF00B 00F Calendar CPU -
H45
scan time error
(periodic scan)
WRF010 012 Scan time (max. / current / min.) CPU CPU H71 Battery low
WRF01B 01F Calendar to read/write user user
WRF050 ROM version CPU CPU
WRF051 FLASH ROM version CPU CPU
(see below)
(see below)
11
4. Setting up
Baud rate for PLC
n
MICRO-EH
Configure baud rate for communication port 1 and 2. For normal use, set the dip switch 1 ON. The
port 1 will then be available for programming with 19.2kbps.
Dip switchPort No. Communication type /
baud rate
1 2 3 4
WRF01A WRF03D
38.4 kbps ON - ON - - -
19.2 kbps ON
- - - - -
9600 bps - - ON - - -
Standard
4800 bps - - - - - -
4800 bps - ON - - H0000 -
9600 bps - ON - - H0100 -
19.2 kbps - ON - - H0200 -
38.4 kbps - ON - - H0300 -
57.6 kbps - ON - - H0400 -
Port 1
RS-232C
Dedicated port
(Programming
/ HMI)
Modem
mode
2400 bps - ON - - H0500 -
4800 bps - - - - - H8000
9600 bps - - - - - H8100
19.2 kbps
- - - - - H8200
Standard
38.4 kbps - - - - - H8300
4800 bps - - - - - HA0xx
9600 bps - - - - - HA1xx
19.2 kbps - - - - - HA2xx
Port 2
RS422/485
Dedicated port
(Programming
/ HMI)
Multidrop
38.4 kbps - - - - - HA3xx
ON
1 2 3 4
Behind the cover
12
n
EH-150
Configure baud rate for communication port 1 and 2. For normal use, set the dip switch 1, 3, 5 all
ON, and the toggle switch ON. Both ports will then be available for programming with 19.2kbps.
Dip switch and toggle switch configuration
Remote SW 1 : ONRUN/STOP
Mode
RUN switch SW 1 : OFF
4,800 bps SW 3, 4 : ON, ON
9,600 bps SW 3, 4 : OFF, ON
19,200 bps SW 3, 4 : ON, OFF
Dedicated port
(Programming / HMI)
SW 5 : ON
38,400 bps SW 3, 4 : OFF, OFF
Modem mode SW 2 : ON
Port 1
General purpose port SW 5 : OFF
Normal mode SW 2 : OFF
4,800 bps SW 6, T : OFF, OFF
9,600 bps SW 6, T : ON, OFF
19,200 bps SW 6, T : OFF, ON
Port 2 Dedicated port
(Programming / HMI)
38,400 bps SW 6, T : ON, ON
SW1-6 = Dip switch, SW T = Toggle switch
Baud rate for PC (Programming software)
The baud rate setting procedure depends on the programming software.
Pro-H Right mouse click on Resource - [Setting] [Communication]
Ladder Editor for Win. [Utility] [Environment] [Communication]
Dip switch 1, 3, 5 : ON
Toggle switch : ON
19.2 kbps for both ports
Toggle switch
CPU module
Dip switch
8
ON
OFF
ONOFF
7
6
5
4
3
2
1
13
5. Configuration
The user program is up/downloaded from/to the PLC as described above.
Besides the user program, several other pieces of important information are up/downloaded from/to
the PLC together with user program. Ensure the following settings are configured correctly.
The I/O configuration and Memory size in the PC program must be same as the actual I/O
configuration and memory size in the PLC.
I/O configuration
n MICRO-EH
The I/O configuration of MICRO-EH is fixed for each model. This table can be read out from the PLC
when on-line.
10, 14, 28 points basic module
Unit 0 Unit 1
Slot 0 X48
Slot 1 Y32
Slot 2
Slot 3
Slot 4
23 points basic module
Unit 0 Unit 1
Slot 0 X48
Slot 1 Y32
Slot 2
Empty 16
Slot 3
WX 4
Slot 4
WY 4
Expansion module
Unit 0
Unit 1
Slot 0 X48
B1/1
Slot 1 Y32
Slot 2
Slot 3
Slot 4
PC
Ø I/O configuration
Ø Memory size
Ø Operation parameters
Ø Retentive area, etc.
User program
PLC
I/O configurationMemory size
28 points
14 points
14 points exp.
10 points
23 points
28 points
I/O configuration of 10,14 and 28
points module is fixed (X48, Y32).
14
n
EH-150
Since the module configuration of EH-150 depends on the user, the I/O configuration table (module
configuration table) must be declared in the PC. This table can be read out from PLC when on-line.
[ I/O configuration table in PC ]
Unit 0 Unit 1
Slot 0 X64
Slot 1 WX 8
Slot 2 Y16
Slot 3 Y16
Slot 4 WY4
Slot 5
Slot 6
Slot 7
Note : The assignment of a 12 point relay module is Y16.
Note : Each module has its own I/O assignment. Please refer to the application manual for further
information.
Note : If the downloaded I/O configuration table does not accord with the actual I/O configuration, the
PLC will not start. However the programming software has a special option setting, which
allows the PLC to work with the wrong I/O configuration.
Memory size
Configure memory size in programming software accordingly. The memory size can be read out from
PLC when on-line as well as the I/O configuration.
MICRO-EH all models 3 k step (4 k step*)
EH-CPU104 4 k step
EH-CPU208 8 k step
EH-CPU308 8 k step
EH-CPU316 16 k step
EH-150
EH-CPU448 48 k step
*Note : Actual memory size of MICRO-EH is 3 k step however, the configuration on PC should be 4 k step.
On programming software
This setting is configured in the following way depending on programming software.
I/O configuration
Pro-H Double click on Resource configuration- [I/O Configuration]
Ladder Editor for Win. [Utility] - [CPU setting] - [I/O assignment]
Memory size
Pro-H Double click on Resource configuration - [Memory Allocation]
Ladder Editor for Win. [Utility] - [CPU setting] - [CPU information]
EH-XD64
EH-AX8V
EH-YR12
EH-YTP16
EH-AY4V
15
Operation parameters
Several optional parameters are available. Configure if necessary.
Operation parameters Default Enable
RUN input Disable Set the address
Max. scan time 100 ms Set the time
Operation mode in wrong I/O configuration STOP RUN
Operation mode in expansion unit error STOP RUN
Operation mode in remote unit error STOP RUN
LINK area range Disable Set the range
etc.
If the Operation mode in wrong I/O configuration is enabled, CPU can work without actual I/O
modules, which is useful for debugging or testing.
On programming software
Pro-H Double click on Resource configuration- [Operation parameters]
Ladder Editor for Win. [Utility] - [CPU setting] - [Operation parameters]
Retentive area
Internal memory R, WR, WM, TD can be configured as Retentive area, which will be kept by a
battery after power off. The battery keeps data not only in the retentive area, but also the real time
clock. User program is kept in FLASH memory, which does not require battery back up.
On programming software
Pro-H Double click on Resource configuration- [Memory allocation]
Ladder Editor for Win. [Utility] - [CPU setting] - [CPU information]
PLC
FLASH memory
User program
Battery
Data in
Retentive area
Real time clock
Lost after power off
Normal data
16
6. Wiring
Wiring diagram for some modules are shown below. Implement wiring based on these drawings for
other MICRO-EH also. Each I/O module for EH-150 has a wiring label at the terminal block.
Note : All DC inputs can be connected as either positive or negative logic.
24V 1
00V
3 4
C02
6 C1
75
8 10
9C2
12 IN1+
IN1-11
IN2-
IN2JP
IN2+
IN1JP
AC 0
GNDAC
V0 2
1C0
4 5
C13
6 7
C3C2
8 C5
9C4
IO VO
VCIC
-
+
-
+
Connect jumper
in current mode
-
+
+
-
DC input Analog input
Transistor
output
Relay output Analog output
0
1
8
9
2
3
10
11
4
5
12
13
6
7
14
15
C
S
+
-
MICRO-EH [EH-D10DTP] EH-150 [EH-YTP16]
MICRO-EH [EH-A23DRP]
RUN
NC 0 1 2 3 C0 4 5
-
+
DC input
Transistor output
-
+
24V
0V
GND
0 1 2 3 C0 V0
-
+
RUN input
CH 0 / CH 1
V / V : WRF06E = H0000
V / I : WRF06E = H4000
I / V : WRF06E = H8000
I / I : WRF06E = HC000
17
7. Programming
One of the most popular and basic programming language is ladder (LD), however SFC or FBD is
becoming very popular. In this chapter, LD is introduced for easy understanding.
The simplest LD circuit consists of one contact and one coil as below.
In this picture, while the switch is ON, the light is ON.
This LD circuit is almost the same meaning as the above picture. The contact is condition for the coil
to be ON, and the coil is the result.
Basically input X is used for the contact, and output Y is used for the coil. The internal I/Os R, “M”
can be used for both cases depending on your program. (Y can work as a contact.)
Hitachi PLC handles the following I/O types.
A contact
(Normally open)
Normal coil
B contact
(Normally close)
Set / Reset coil
(MCS / MCR coil available)
Edge detection
(Low è High)
Timer (Other timers ; SS, MS, TMR,
WDT available)
Edge detection
(High è Low)
Counter (Other counters ; RCU, CTU,
CTD, CL available)
NOT
X0 Y100
X0
Y100
A Contact / Coil
X0
Y100
B Contact / Coil
X0 Y100
Contact
Coil
(=Input) (=Output)
Switch Light
S
R
TD
CU
18
& De Morgans Laws
NOT ( A AND B ) = ( NOT A ) OR ( NOT B ) A × B = A + B
NOT ( A OR B ) = ( NOT A ) AND ( NOT B ) A + B = A × B
X0
Y100
Edge detection (
á
) : DIF
X0 Y100DIF 0
1 scan time
X0
Y100
Edge detection (
â
) : DFN
X0 Y100DFN 0
1 scan time
X0
X1
Set/Reset coil
X0 Y100
S
X1 Y100
R
Y100
X0 Y100
X0
Y100
AND
X1
X1
X0 Y100
X0
Y100
OR
X1
X1
Internal memory R, M can be used instead of X and Y.
X0 Y100
X0
Y100
NOT
19
Note : MICRO-EH supports above 2 timers only.
Note : EH-150 supports Mono-stable timer MS, integral timer TMR and Watch dog timer WDT
besides above ones.
ON delay timer : TD
X0 TD 0
TD 0 Y100
12
0.1s
X0
12
TD 0
0.1s
Y100
n
Pro-H (LD)
n
LADDER EDITOR
TD 0
0.1s
Y100
12
X0
n
Pro-H (FBD)
X0
TD 0
Y100
1.2s
TC 0
12
* TC is a word data counting 0 up to 65,535.
Single Shot timer : SS
X0 SS 0
TD 0 Y100
12
0.1s
n
LADDER EDITOR
X0
12
SS 0
0.1s
Y100
n
Pro-H (LD)
SS 0
0.1s
Y100
12
X0
n
Pro-H (FBD)
X0
TD 0
Y100
1.2s
TC 0
12
* TC is a word data counting 0 up to 65,535.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21