This booklet includes:
User Guide (HA029005 Issue 2)
Manuale di uso (HA029005ITA Versione 2)
Guía del usuario (HA029005SPA Edición 2)
Part number HA029005. Issue 2.0 May-06. 1
3200i Series Process Indicators and Alarm Units
Applies to Model numbers 3216i, 32h8i and 3204i
Contents
1. What Instrument Do I Have?.........................................................................................4
1.1 Unpacking Your Indicator ................................................................................................................... 5
1.2 Dimensions Front Views..................................................................................................................... 5
1.3 Dimensions – Side and Top Views ....................................................................................................... 6
1.4 Step 1: Installation ............................................................................................................................. 7
1.4.1 Panel Mounting the Indicator.................................................................................................................................................... 7
1.4.2 Panel Cut-out Sizes........................................................................................................................................................................ 7
1.4.3 Recommended minimum spacing of indicators................................................................................................................... 8
1.4.4 To Remove the Indicator from its Sleeve............................................................................................................................... 8
1.5 Ordering Code..................................................................................................................................... 9
2. Step 2: Wiring............................................................................................................ 10
2.1 Terminal Layout 3216i Indicator.........................................................................................................10
2.2 Terminal Layout 32h8i Indicator ........................................................................................................11
2.3 Terminal Layout 3204i Indicators .......................................................................................................12
2.4 Wire Sizes...........................................................................................................................................13
2.5 Sensor Input (Measuring Input) .........................................................................................................13
2.6 Outputs - 1/8 and 1/4 DIN Indicators .................................................................................................14
2.6.1 Output 1 & Output 4 (AA Relay) ............................................................................................................................................14
2.6.2 Output 3 Retransmission (Output 2 3216i) .........................................................................................................................15
2 Part number HA029005. Issue 2.0 May-06.
2.6.3 Transmitter Supply ...................................................................................................................................................................... 15
2.6.4
Digital Inputs A and B ................................................................................................................................................................ 15
2.6.5 Transducer Supply....................................................................................................................................................................... 15
2.7 Indicator Power Supply ..................................................................................................................... 16
2.8 Example Wiring Diagram ................................................................................................................... 16
2.9 Digital Communications (Optional) ................................................................................................... 17
2.10 Additional Connections for 3216i ...................................................................................................... 18
2.10.1 Input/Output 1 & Output 2 ............................................................................................................................................... 18
3. Safety and EMC Information .......................................................................................19
3.1 Installation Safety Requirements....................................................................................................... 20
4. Switch On ................................................................................................................... 24
4.1 New Indicator .................................................................................................................................... 24
4.1.1 To Re-Enter Quick Code Mode ............................................................................................................................................... 28
4.2 Pre-Configured Indicator or Subsequent Starts................................................................................. 28
4.3 Front panel layout ............................................................................................................................. 29
4.3.1 Alarm Indication .......................................................................................................................................................................... 30
4.3.2 Out of Range Indication ............................................................................................................................................................ 30
4.3.3 Sensor Break Indication............................................................................................................................................................. 30
4.3.4 Diagnostic Alarms........................................................................................................................................................................ 30
4.4 Operator Parameters in Level 1......................................................................................................... 31
4.4.1 Tare Correction ............................................................................................................................................................................ 32
5. Operator Level 2......................................................................................................... 33
5.1 To Enter Level 2 ................................................................................................................................. 33
5.1.1 To Return to Level 1................................................................................................................................................................... 33
Part number HA029005. Issue 2.0 May-06. 3
5.2 Level 2 Parameters .............................................................................................................................34
5.3
Strain Gauge Calibration ....................................................................................................................38
5.3.1 To configure the different modes:- .......................................................................................................................................38
5.3.2 Load Cell Calibration .................................................................................................................................................................. 39
5.3.3 Comparison Calibration .............................................................................................................................................................40
5.3.4 Shunt Calibration .........................................................................................................................................................................40
5.3.5 Manual Calibration......................................................................................................................................................................41
5.3.6 Automatic Calibration ................................................................................................................................................................ 41
5.3.7 Calibration Using a Digital Input .............................................................................................................................................42
5.4 Recipes ...............................................................................................................................................43
5.4.1 To Store Values in a Recipe...................................................................................................................................................... 43
5.4.2 To Load a Recipe .........................................................................................................................................................................43
5.5 FM and DIN 3440 Alarm Units............................................................................................................44
Issue Status of this Manual
Issue 2 of this manual applies to firmware version 1.03 and contains the following changes:-
Load cell and shunt calibration explained in more detail.
Separate ‘Set 2’ codes for 32h8i/3204i and 3216i for clarity
Add note on sensor break for transducers
Add note on FM DIN3440 indicators.
4 Part number HA029005. Issue 2.0 May-06.
Installation and Basic Operation
1. What Instrument Do I Have?
Thank you for choosing this 3200i series Process
Indicator.
These are available as:-
Model Size Inputs Outputs
3216i 1/16
DIN
Thermocouple
Pt100 RTD
V/mA/mV
1 – Relay, Logic,
Analogue or dig in
2 – Relay, or
Analogue
4 Changeover
relay
32h8i 1/8
DIN
Thermocouple
Pt100 RTD
V/mA/mV
2 Digital
1 Changeover
relay
3 Retransmission
4. Changeover
relay
and Transmitter
PSU
32h8i/SG 1/8
DIN
Strain gauge As 32h8i
3204i 1/4
DIN
As 3216i As 32h8i
Relay outputs can be configured for alarm and events
and analogue retransmission of process variable. 2-
wire Modbus digital communications is available in
all models.
The indicator may have been ordered to a hardware
code only or pre-configured using an optional ‘Quick
Start’ code. The label fitted to the side of the sleeve
shows the ordering code of the indicator. If the Quick
Code shows ***** the indicator will need to be
configured when it is first switched on.
This User Guide takes you through step by step
instructions to help you to install, wire, configure and
use the indicator. For features not covered in this
User Guide, a detailed Engineering Manual, Part No
HA029006, and other related handbooks can be
downloaded from www.eurotherm.co.uk.
Part number HA029005. Issue 2.0 May-06. 5
1.1 Unpacking Your Indicator
The following items are included in the box:
Indicator mounted in its sleeve
Two panel retaining clips
AN IP65 sealing gasket mounted on the sleeve
Component packet containing a snubber for
each relay output and a 2.49 resistor for
current inputs (see section 2)
This User Guide
1.2 Dimensions Front Views
96mm (3.78in)
48mm
(1.89in)
Models 32h8i
48mm
(1.89in)
48mm
(1.89in)
Latching
ears
Model 3216i
96mm
(3.78in)
Model 3204i
Latching
ears
96mm (3.78in)
6 Part number HA029005. Issue 2.0 May-06.
1.3 Dimensions – Side and Top Views
1 Latching ears
2 Panel retaining clip
3 IP65 Sealing Gasket
Side View –1/8 DIN & 1/4 DIN
90mm (3.54in)
d
96mm
(3.78in)
1
3
d
23
1
Top View
1/16 & 1/8 DIN
Side View
1/16 DIN
90mm (3.54in)
1
90mm (3.54in)
d
48mm
(1.89in)
48mm
(1.89in)
2
1
2
2
3
3
d = Fascia depth 1.25mm (0.5in)
Part number HA029005. Issue 2.0 May-06. 7
1.4 Step 1: Installation
This indicator is intended for permanent installation,
for indoor use only, and enclosed in an electrical
panel
Select a location which is subject to minimum
vibrations, the ambient temperature is within 0 and
55
o
C (32 - 131
o
F) and humidity 5 to 95% RH non
condensing.
The indicator can be mounted on a panel up to
15mm thick
To ensure IP65 and NEMA 4 front sealing against
dust and water, mount on a non-textured surface.
Please read the safety information in section 3
before proceeding. The EMC Booklet part number
HA025464 gives further installation information.
1.4.1 Panel Mounting the Indicator
1. Prepare a cut-out in the mounting panel to the
size shown. If a number of instruments are to
be mounted in the same panel observe the
minimum spacing shown.
2. Fit the IP65 sealing gasket behind the front
bezel of the indicator
3. Insert the indicator through the cut-out
4. Spring the panel retaining clips into place.
Secure the indicator in position by holding it
level and pushing both retaining clips forward.
5. Peel off the protective cover from the display
1.4.2 Panel Cut-out Sizes
45 mm
- 0.0 + 0.6
1.77 inch
-0.00, +0.02
45 mm
- 0.0 + 0.6
1.77 inch
-0.00, +0.02
Model
3216i
Model 32h8i
Model 3204i
92 mm
- 0.0 + 0.8
3.62 inch
-0.00, +0.03
92 mm - 0.0 + 0.8
3.62 inch -0.00, +0.03
8 Part number HA029005. Issue 2.0 May-06.
1.4.3 Recommended minimum spacing of
indicators.
Applies to all Model sizes
1.4.4 To Remove the Indicator from its
Sleeve
The indicator can be unplugged from its sleeve by
easing the latching ears outwards and pulling it
forward out of the sleeve. When plugging it back
into its sleeve, ensure that the latching ears click
back into place to maintain the IP65 sealing.
10mm (0.4 inch)
38mm (1.5 inch)
(Not to scale)
Part number HA029005. Issue 2.0 May-06. 9
1.5 Ordering Code
1 2 3 4 5 6 7 8 9 10 11 12 13 14 Quick Start Code (see section 4)
8/9 Product/Manual Language
ENG English
FRA French
GER German
ITA Italian
SPA Spanish
7. Fascia colour/type
G Green
S Silver
6. Options
XXX Not fitted
(3216i only)
XXL Digital input A (not 32h8i/SG,
optional in 3216i)
2XL RS232 & Digital input A
(includes Dig In A except
32h8i/SG)
4XL RS485 & Digital input A
(includes Dig In A except
32h8i/SG)
11. Warranty
Standard XXXXX
Extended WL005
12. Certificates
None XXXXX
CERT1 Cert of
conformity
CERT2 5 Point Factory
calibration
13. Custom Label
XXXXX None
14. Special and Accessories
XXXXXX None
RES250 250 ; 0-5Vdc
OP
RES500 500 ; 0-10Vdc
OP
5. AA Relay (OP4)
R Relay (Form C)
4. Outputs (OP1, OP2, OP3)
LRXX OP1 Logic, OP2 Relay *
RRXX OP1 Relay, OP2 Relay *
LDXX OP1 Logic, OP2 Analogue *
DRXX OP1 Analogue, OP2 Relay *
RXXX OP1 Relay
(32h8i & 3204i only)
RXDX OP1 Relay, OP3 Analogue
(32h8i & 3204i only)
* 3216i only
10. Input Adaptor
XX None
V1 1-10Vdc
A1 mA Burden Resistor
(2.49)
3. Power Supply
VL 24Vac/dc
VH 100–240Vac
2. Function
AL Standard Unit
FM FM Alarm Unit
DN DIN 3440 alarm unit
SG Strain Gauge Input 32h8i only
1. Model No.
3216i 1/16 DIN size
32h8i 1/8 DIN size (horizontal)
3204i 1/4 DIN size
10 Part number HA029005. Issue 2.0 May-06.
2. Step 2: Wiring
2.1 Terminal Layout 3216i Indicator
!
Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied
806
100K
COM
A(+)
B(-)
Digital Communications
RS232
RS485
A
A relay (OP4)
AA
AB
AC
VI
V+
V-
1A
1B
2A
2B
L
N
CT
C
LA
HD
HE
HF
-
+
mV
+
-
Sensor Input
2.49
T/C
Pt100 mA
-
+
+ +
- -
+
-
Line Supply 100 to 240Vac 50/60Hz
OR Low Voltage Supply 24Vac/dc
Input/Output 1
Output 2
Digital input A
10V Potential divider
module
Part No SUB21/IV10
-
+
10V
Input
Key to Symbols used in the wiring diagrams
Logic (SSR drive) output
Relay output
Contact input
mA analogue output
Part number HA029005. Issue 2.0 May-06. 11
2.2 Terminal Layout 32h8i Indicator
!
Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied
Cal
1
Signal | Txdcr Supply
Input Connections for
32h8i/SG Indicator - Strain gauge input
Note: Dig in A is not available with this indicator
- +
OP3 DC
Retrans
V/mA
24V
Transmitter
Supply
Dig in B
Output 1 (OP1)
Changeover
Relay
AA Relay
(OP4)
B(-) A(+) COM
Digital Comms
-
+
T/C
Sensor Input
Pt100
V- V+ VI LA C CT HF HE HD AC AB AA
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
-
2.49
mV/V
+
- +
Dig in A
- +
32h8i Indicator
Line Supply 100 to 240Vac 50/60Hz
OR
Low Voltage Supply 24Vac/dc
mA include the 2.49 load resisto
r
- +
Cal
2
Ext
-
Ext
+
12 Part number HA029005. Issue 2.0 May-06.
2.3 Terminal Layout 3204i Indicators
!
Ensure that you have the correct supply for your indicator. Check order code of the indicator supplied
10V Potential divider
module
Part No SUB21/IV10
Line Supply
100 to 240Vac 50/60Hz
OR
Low Voltage Supply
24Vac/dc
1A
1B
2A
2B
LB
LC
+
24V
-
24V Transmitter Supply
3A
3B
3C
3D
L
N
DC Retrans (OP3)
mA only
+
-
Digital Input B
Digital
Communications
RS232 or RS485
A
A Relay (OP4)
AA
AB
AC
HD
HE
HF
CT
C
LA
VI
V+
V-
COM
A(+)
B(-)
-
+
T/C
Sensor Input
Pt100 mA/mV
-
2.49
+
Digital
input A
-
+
10V Input
Output 1 (OP1)
100K
806
3204i Indicator
Part number HA029005. Issue 2.0 May-06. 13
2.4 Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5
mm (16 to 22AWG). Hinged covers prevent hands or
metal making accidental contact with live wires. The
rear terminal screws should be tightened to 0.4Nm
(3.5lb in).
2.5 Sensor Input (Measuring Input)
Do not run input wires with power cables
When shielded cable is used, it should be
grounded at one point only
Any external components (such as zener barriers)
connected between sensor and input terminals
may cause errors in measurement due to
excessive and/or un-balanced line resistance, or
leakage currents.
Not isolated from the logic outputs & digital
inputs
Thermocouple Input
Use the correct
compensating cable
preferably shielded.
It is not recommended to
connect two or more instruments to one thermocouple.
RTD Input
PRT
PRT
Lead compensation
The resistance of the three wires must be the same.
The line resistance may cause errors if it exceeds
22.
Linear mA, or mV Inputs
Positive
Negative
For a mA input connect the 2.49 burden resistor
supplied between the V+ and V- terminals as shown.
For mV omit this resistor.
Linear Voltage Inputs
An external potential
divider, part no
SUB21/IV10, is available
for 3216i and 3204i.
Sensor break alarm does not operate when this adaptor
is fitted.
- Negative
+ Positive
V+
V-
2.49
+
-
V+
V-
100K
806
+
0-10V
-
V+
V-
VI
V+
V-
14 Part number HA029005. Issue 2.0 May-06.
2.6 Outputs - 1/8 and 1/4 DIN
Indicators
32h8i and 3204i indicators are supplied as standard
with two changeover relay outputs.
2.6.1 Output 1 & Output 4 (AA Relay)
Relay (Form C, changeover)
Isolated output 240Vac CATII
Contact rating:: 2A 264Vac resistive
Output functions: Alarm/Event
* General Notes about Relays and Inductive
Loads
High voltage transients may occur when switching
inductive loads such as some contactors or solenoid
valves. Through the internal contacts, these transients
may introduce disturbances which could affect the
performance of the instrument.
For this type of load it is recommended that a
‘snubber’ is connected across the normally open
contact of the relay switching the load. The snubber
recommended consists of a series connected
resistor/capacitor (typically 15nF/100). A snubber
will also prolong the life of the relay contacts.
A snubber should also be connected across the output
terminal of a triac output to prevent false triggering
under line transient conditions.
WARNING
When the relay contact is open, or it is connected
to a high impedance load, it passes a current
(typically 0.6mA at 110Vac and 1.2mA at 240Vac).
You must ensure that this current will not hold on
low power electrical loads. If the load is of this
type the snubber should not be connected.
OP4
AA
AB
AC
1A
1B
2A
OP1
Part number HA029005. Issue 2.0 May-06. 15
2.6.2 Output 3 Retransmission (Output 2
3216i)
Isolated output 240Vac CATII
Software configurable: 0-20mA
or 4-20mA plus 0-5V, 0-10V, 1-
5V and 2-10V.
Max load resistance: 500
Calibration accuracy: +(<0.25% of reading +
<50µA
Output functions: PV retransmission.
Output 2 non-isolated on 3216i
2.6.3 Transmitter Supply
A fixed 24Vdc supply is available to power an
external transducer (not 3216i).
Isolated output 240Vac CATII
2.6.4 Digital Inputs A and B
Digital input A is not available in 32h8i/SG and
optionally available on 3216i.
Not isolated from the sensor input
Switching: 12Vdc at 40mA max
Contact open > 500. Contact closed < 200
Input functions: Please refer to the list in the
quick codes.
2.6.5 Transducer Supply
In 32h8i/SG a 10Vdc supply is available as an
excitation voltage for a bridge type transducer
Minimum load resistance 300
Isolated output 240Vac CATII
+
-
OP3
3A
3B
Dig In A
LA
C
Dig In B
LB
LC
+
-
3C
3D
+
-
Ext1
Ext2
16 Part number HA029005. Issue 2.0 May-06.
2.7 Indicator Power Supply
1. Before connecting the indicator to the power
line, make sure that the line voltage corresponds
to the description on the identification label.
2. Use copper conductors only.
3. The power supply input is not fuse protected.
This should be provided externally.
4. For 24V the polarity is not important.
High voltage supply: 100 to 240Vac, -15%,
+10%, 50/60 Hz
Low voltage supply: 24Vac/dc, -15%, +10%
Recommended external fuse ratings are as
follows:-
For 24 V ac/dc, fuse type: T rated 2A 250V
For 100-240Vac, fuse type: T rated 2A 250V.
2.8 Example Wiring Diagram
This shows 32h8i connected to a strain gauge bridge.
Safety requirements for permanently connected
equipment state:
A switch or circuit breaker shall be included in
the building installation
It shall be in close proximity to the equipment
and within easy reach of the operator
It shall be marked as the disconnecting device for
the equipment.
Note: a single switch or circuit breaker can drive more
than one instrument.
Line
Neutral
Power Supply
L
N
24V
24V
24
24
Signal
+
-
N
Fuse
L
N L 3D 3C 3B 3A LC LB 2B 2A 1B 1A
-
+
32h8i/SG Indicator
R
CAL
Strain
Gauge
Cal
1
Cal
2
Ext
-
Ext
+
- +
HE
HD
HF
AC AB AA
Txdcr
Suppl
y
Interna
FET
switch
Part number HA029005. Issue 2.0 May-06. 17
2.9 Digital Communications (Optional)
Digital communications uses the Modbus protocol.
The interface may be ordered as RS232 or RS485 (2-
wire).
Isolated 240Vac CATII.
RS232 Connections
RS485 Connections
Com
Tx
Rx
HD Common
HE Rx A(+)
HF Tx B(-)
Local Ground
Screen
220 termination
resistor
* RS232/RS485 2-wire
communications converter
eg Type KD485
Daisy Chain to
further
instrument
Com
220 termination
resistor on last
instrument in the line
Twisted pairs
Tx Rx Com
HD Common
HE Rx A(+)
HF Tx B(-)
Rx Tx Com
Screen
RxB/
TxB
RxA/
TxA
*
18 Part number HA029005. Issue 2.0 May-06.
2.10 Additional Connections for 3216i
Connections for the 3216i indicator are similar to the
3216 controller.
2.10.1 Input/Output 1 & Output 2
I/O1 may be configured as input or output.
Outputs can be logic (SSR drive), or relay, or mA dc.
Input is contact closure.
Relay Output (Form A, normally open)
Isolated output 240Vac CATII
Contact rating: 2A 264Vac
resistive
Output functions: Alarm or event
Logic (SSR drive) Output
Not isolated from the sensor
input
Output ON state: 12Vdc at
40mA max
Output OFF state: <300mV,
<100µA
Output functions: Alarm or event
DC Output
Not isolated from the sensor input
Software configurable: 0-20mA
or 4-20mA.
Max load resistance: 500
Calibration accuracy: 1%,
+
100µA
Output functions: Retransmission.
Logic Contact Closure Input (OP1 only)
Not isolated from the sensor input
Switching: 12Vdc at 40mA max
Contact open > 500. Contact
closed < 150
Input functions: Please refer to
the list in the Quick Start codes.
OP1/2
1/2A
1/2B
+
-
OP1/2
1A
1B
OP1
+
-
1/2A
1/2B
OP1
1A
1B
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144

Eurotherm 3200 Manuale del proprietario

Tipo
Manuale del proprietario
Questo manuale è adatto anche per